In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
13 Troubleshooting Guide
13.1. Refrigeration cycle system
77
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
13.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Heating Mode
Condition of the air
conditoner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube
or Strainer
Short circuit in the
indoor unit
Heat radiation
deficiency of the
outdoor unit
Inefficient compression
  • 
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
13.1.2. Diagnosis methods of a malfunction of a compressor and 4-way valve
Nature of fault
Symptom
  • 
Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
  • 
The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
  • 
The difference between high pressure and low pressure becomes almost zero.
  • 
Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
  • 
The compressor is a humming sound.
  • 
Electric current during operation becomes approximately 80% lower than the normal value.
Insufficient switches of the 4-way valve
  • 
The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.
78
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
14 Technical Data
79
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.03
1.54
0.60
1.90
1.48
0.65
1.77
1.42
0.70
1.72
1.35
0.75
19.0°C
2.05
0.66
19.5°C
2.23
1.61
0.62
2.09
1.55
0.66
1.94
1.49
0.71
1.77
1.42
0.76
22.0°C
2.43
1.67
0.63
2.27
1.61
0.67
2.12
1.55
0.72
1.92
1.48
0.78
220V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
1.98
1.50
0.55
1.85
1.44
0.59
1.72
1.39
0.63
1.57
1.32
0.68
19.0°C
2.00
0.60
19.5°C
2.18
1.57
0.56
2.04
1.51
0.60
1.89
1.46
0.64
1.72
1.39
0.69
22.0°C
2.37
1.63
0.57
2.22
1.57
0.61
2.06
1.51
0.66
1.88
1.44
0.71
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.63
1.99
0.86
2.46
1.91
0.93
2.28
1.84
0.99
2.08
1.75
1.07
19.0°C
2.65
0.94
19.5°C
2.89
2.09
0.88
2.70
2.00
0.94
2.51
1.93
1.01
2.28
1.84
1.09
22.0°C
3.15
2.16
0.89
2.94
2.08
0.96
2.73
2.01
1.03
2.49
1.91
1.11
220V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.58
1.96
0.82
2.41
1.88
0.88
2.24
1.80
0.94
2.04
1.71
1.01
19.0°C
2.60
0.89
19.5°C
2.83
2.05
0.83
2.65
1.97
0.89
2.46
1.89
0.96
2.24
1.80
1.03
22.0°C
3.09
2.12
0.85
2.88
2.04
0.91
2.68
1.97
0.97
2.44
1.88
1.05
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
3.47
2.63
1.15
3.24
2.52
1.23
3.02
2.43
1.32
2.74
2.30
1.42
19.0°C
3.50
1.25
19.5°C
3.81
2.76
1.17
3.56
2.65
1.26
3.31
2.55
1.34
3.01
2.43
1.45
22.0°C
4.15
2.86
1.19
3.88
2.75
1.28
3.61
2.65
1.37
3.28
2.53
1.47
220V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
3.42
2.59
1.12
3.20
2.45
1.20
2.97
2.39
1.29
2.70
2.27
1.39
19.0°C
3.45
1.22
19.5°C
3.76
2.72
1.14
3.51
2.61
1.22
3.27
2.51
1.31
2.97
2.39
1.41
22.0°C
4.10
2.82
1.16
3.83
2.71
1.25
3.56
2.61
1.33
3.24
2.49
1.44
TC - Total Cooling (kW)
Indoor 27°C/19°C
SHC - Sensible Heat Capacity (kW)
Outdoor 35°C/24°C
IP - Input Power (kw)
80
CS-MA95KE CU-MA185KE / CS-MA125KE CU-MA245KE / CS-MA75KE / CS-MA125KE CU-MA195KE
Page of 98
Display