Panasonic CS-HE9MKD / CU-HE9MKD / CS-HE12MKD / CU-HE12MKD Service Manual ▷ View online

57
15.3.
Error Codes Table
Abnormality / 
Protection control
Abnormality
Judgement
Protection
operation
Problem
Check location
Diagnosis
display
H00
No memory of failure
Normal operation
H11
Indoor/outdoor 
abnormal 
communication
After operation for 
1 minute
Indoor fan only 
operation can 
start by entering 
into force cooling 
operation
Indoor/outdoor 
communication not establish
• Indoor/outdoor wire terminal
• Indoor/outdoor PCB
• Indoor/outdoor connection wire
H12
Indoor unit capacity 
unmatched
90s after power 
supply
Total indoor capability more 
than maximum limit or less 
than minimum limit, or 
number of indoor unit less 
than two.
• Indoor/outdoor connection wire
• Indoor/outdoor PCB
• Specification and combination 
table in catalogue
H14
Indoor intake air 
temperature sensor 
abnormality
Continuous for 5s
Indoor intake air temperature 
sensor open or short circuit
• Indoor intake air temperature 
sensor lead wire and connector
H15
Compressor 
temperature sensor 
abnormality
Continuous for 5s
Compressor temperature 
sensor open or short circuit
• Compressor temperature sensor 
lead wire and connector
H16
Outdoor current 
transformer (CT) 
abnormality
Current transformer faulty or 
compressor faulty
• Outdoor PCB faulty or 
compressor faulty
H19
Indoor fan motor 
merchanism lock
Continuous 
happen for 7 times
Indoor fan motor lock or 
feedback abnormal
• Fan motor lead wire and 
connector
• Fan motor lock or block
H23
Indoor heat exchanger 
temperature sensor 
abnormality
Continuous for 5s
Indoor heat exchanger 
temperature sensor open or 
short circuit
• Indoor heat exchanger 
temperature sensor lead wire and 
connector
H25
Indoor E-Ion 
abnormality
Port is ON for 10s 
during E-Ion off
• E-Ion PCB
H27
Outdoor air temperature 
sensor abnormality
Continuous for 5s
Outdoor air temperature 
sensor open or short circuit
• Outdoor air temperature sensor 
lead wire and connector
H28
Outdoor heat exchanger 
temperature sensor 1 
abnormality
Continuous for 5s
Outdoor heat exchanger 
temperature sensor 1 open 
or short circuit
• Outdoor heat exchanger 
temperature sensor 1 lead wire 
and connector
H30
Outdoor discharge pipe 
temperature sensor 
abnormality
Continuous for 5s
Outdoor discharge pipe 
temperature sensor open or 
short circuit
• Outdoor discharge pipe 
temperature sensor lead wire and 
connector
H32
Outdoor heat exchanger 
temperature sensor 2 
abnormality
Continuous for 5s
Outdoor heat exchanger 
temperature sensor 2 open 
or short circuit
• Outdoor heat exchanger 
temperature sensor 2 lead wire 
and connector
H33
Indoor / outdoor 
misconnection 
abnormality
Indoor and outdoor rated 
voltage different
• Indoor and outdoor units check
H34
Outdoor heat sink 
temperature sensor 
abnormality
Continuous for 2s
Outdoor heat sink 
temperature sensor open or 
short circuit
• Outdoor heat sink sensor
H36
Outdoor gas pipe 
temperature sensor 
abnormality
Continuous for 5s Heating protection 
operation only
Outdoor gas pipe 
temperature sensor open or 
short circuit
• Outdoor gas pipe temperature 
sensor lead wire and connector
H37
Outdoor liquid pipe 
temperature sensor 
abnormality
Continuous for 5s Cooling protection 
operation only
Outdoor liquid pipe 
temperature sensor open or 
short circuit
• Outdoor  liquid pipe temperature 
sensor lead wire and connector
H38
Indoor/Outdoor 
mismatch (brand code)
Brand code not match
• Check indoor unit and outdoor 
unit.
58
H39
Abnormal indoor 
operating unit or 
standby units
3 times happen 
within 40 minutes
Wrong wiring and connecting 
pipe, expansion valve 
abnormality, indoor heat 
exchanger sensor open 
circuit
• Check indoor/outdoor connection 
wire and connection pipe
• Indoor heat exchanger sensor 
lead wire and connector
• Expansion valve and lead wire 
and connector
H41
Abnormal wiring or 
piping connection
Wrong wiring and connecting 
pipe, expansion valve 
abnormality
• Check indoor/outdoor connection 
wire and connection pipe
• Expansion valve and lead wire 
and connector.
H58
Indoor gas sensor 
abnormality
Continuous for 6 
hours
Indoor gas sensor open or 
short circuit
• Indoor gas sensor
• Indoor PCB
H59
ECO patrol sensor 
abnormality
Continuous for 
70s
ECO patrol sensor open or 
short circuit
• ECO patrol sensor
• ECO patrol and Indoor PCB
H64
Outdoor high pressure 
sensor abnormality
Continuous for 1 
minutes
High pressure sensor open 
circuit during compressor 
stop
• High pressure sensor
• Lead wire and connector
H97
Outdoor fan motor 
mechanism lock
2 times happen 
within 30 minutes
Outdoor fan motor lock or 
feedback abnormal
• Outdoor fan motor lead wire and 
connector
• Fan motor lock or block
H98
Indoor high pressure 
protection
Indoor high pressure 
protection (Heating)
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
H99
Indoor operating unit 
freeze protection
Indoor freeze protection 
(Cooling)
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
F11
4-way valve switching 
abnormality
4 times happen 
within 30 minutes
4-way valve switching 
abnormal
• 4-way  valve
• Lead wire and connector.
F17
Indoor standby units 
freezing abnormality
3 times happen 
within 40 minutes
Wrong wiring and connecting 
pipe, expansion valve 
leakage, indoor heat 
exchanger sensor open 
circuit
• Check indoor/outdoor connection 
wire and pipe
• Indoor heat exchanger sensor 
lead wire and connector
• Expansion valve lead wire and 
connector.
F90
Power factor correction 
(PFC) circuit protection
4 times happen 
within 10 minutes
Power factor correction 
circuit abnormal
• Outdoor PCB faulty
F91
Refrigeration cycle 
abnormality
2 times happen 
within 20 minutes
Refrigeration cycle abnormal
• Insufficient refrigerant or valve 
close
F93
Compressor abnormal 
revolution
4 times happen 
within 20 minutes
Compressor abnormal 
revolution
• Power transistor module faulty or 
compressor lock
F94
Compressor discharge 
pressure overshoot 
protection
4  times happen 
within 30 minutes
Compressor discharge 
pressure overshoot
• Check refrigeration system
F95
Outdoor cooling high 
pressure protection
4 times happen 
within 20 minutes
Cooling high pressure 
protection
• Check refrigeration system
• Outdoor air circuit
F96
Power transistor module 
overheating protection
4 times happen 
within 30 minutes
Power transistor module 
overheat
• PCB faulty
• Outdoor air circuit (fan motor)
F97
Compressor 
overheating protection
3 times happen 
within 30 minutes
Compressor overheat
• Insufficient refrigerant
F98
Total running current 
protection
3 times happen 
within 20 minutes
Total current protection
• Check refrigeration system
• Power source or compressor lock
F99
Outdoor direct current 
(DC) peak detection
Continuous 
happen for 7 times
Power transistor module 
current protection
• Power transistor module faulty or 
compressor lock
Abnormality / 
Protection control
Abnormality
Judgement
Protection
operation
Problem
Check location
Diagnosis
display
59
15.4. Self-diagnosis Method
15.4.1. H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused
• Faulty indoor unit PCB.
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
units.
• Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting
60
15.4.2. H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
• Wrong models interconnected.
• Wrong indoor unit or outdoor unit PCBs mounted.
• Indoor unit or outdoor unit PCBs defective.
• Indoor-outdoor unit signal transmission error due to wrong wiring.
• Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor
units.
Troubleshooting
Page of 107