 2. Auto Fan Speed
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1300 rpm (E24DK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1300 rpm (E24DK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1100 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
8.2.3.2. Intake Air Temperature Control
Compressor will operate at freq 67 Hz if either one of the below conditions occur:
 1. When the indoor intake air temperature is above 10°C and remote control setting fan speed is lower Me-.
 2. When the indoor intake air temperature is 30°C or above.
37
CS-E24DKD CU-E24DKD
8.2.3.3. Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the below figures. This
control will begin one minute after the compressor starts.
8.2.3.4. Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
8.2.3.5. Outdoor Temperature Control
  • Outdoor temperature is detected and the following control is perform.
  • Control operates after more than 1 minute the compressor has started.
38
CS-E24DKD CU-E24DKD
8.2.3.6. Deice Control
A. Deice operation (Normal Deice Operation)
 1. Detection methods
Outdoor heat exchanger temperature sensor, timer.
 2. Deice operation time chart
Notes
  • During deice operation, as relationship for outdoor piping temperature and time T5, the priority given to the condition
which is first fulfilled and shift to the next mode.
  • First deice after operation restricted to 60 min. & above.
  • No restart operation if compressor OFF for sequence No. 1~7.
(Instantaneous, restart)
Outdoor heat exchanger temperature
a
15°C
b
18°C
c
25°C
39
CS-E24DKD CU-E24DKD
 3. Explanation of operation
1) At the deice starting signal, the compressor frequency is set to the value as previously mentioned.
2) At 120 sec. after deice starting signal generated, 4 way valve OFF and at the same time outdoor fan is OFF, indoor fan is OFF,
compressor frequency is set to the previously mentioned value.
3) WIthin 30 sec. after the 4 way valve OFF, the compressor frequency is set to the previously mentioned value.
4) If the outdoor heat exchanger temperature is above a°C, the compressor frequency is set to the value as previously mentioned.
5) After the compressor frequency is changed according to the item 4), in case either outdoor heat exchanger temperature more than b°C
or 10.5 minutes lapsed after 4 way valve OFF is fulfilled, 30 sec. calculation start.
6) After 5) operated, if the outdoor heat exchanger temperature is more than c°C or 30 sec. lapsed, deice operation completion signal
transmit, the compressor frequency is set to the previously mentioned value. And timingly ON signal transmit on outdoor FM.
7) After 59 sec. lapsed after deice operation completion signal generated, 4 way valve/indoor fan is ON, compressor frequency become
FREE, and recover to normal heating operation.
 4. Deice operation judgement condition
When any of below a, b, c, d condition is satisfied, deice signal is produced.
 a. Continuously, outdoor heat exchanger temperature < 3°C for 120 minutes and outdoor heat exchanger temperature
< -6°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
 b. Continuously, outdoor heat exchanger temperature < 3°C for 80 minutes and outdoor heat exchanger temperature
< -7°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
 c. 
Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature
< -9°C for 3 minutes and outdoor air temperature > -3°C and Comp. is ON.
 d. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature
< -11°C for 3 minutes and outdoor air temperature > -3°C and Comp. is ON.
However, the first deice will start only after minimum of 60 minutes in operation.
(2nd deice and onward shall follow above conditions)
40
CS-E24DKD CU-E24DKD
Page of 94
Display