8.1.4. Soft Dry Operation
8.1.4.1. Thermostat control
  • Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFF
point.
8.1.5. Heating Operation
8.1.5.1. Thermostat control
  • Compressor is OFF when Intake Air Temperature - Internal Setting > +1.5°C.
  • Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFF
point -0.5°C.
8.1.6. 
Automatic Operation
This mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake air
temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detect
the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.
17
CS-E24DKD CU-E24DKD
Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2
and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on
the above operation mode chart, every 30 minutes.
Remote Control Setting Temperature (°C)
T1
T2
T3
16 ~ 18
+10
+8
-5
19 ~ 22
+8
+7
-7
23 ~ 26
+7
+6
-7
27 ~ 30
+6
+5
-8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice
verse.
Operation Mode change from
Temperature shifts (°C)
Cooling/Soft Dry
→ Heating
-2
Heating
→ Cooling/Soft Dry
+2
Example of operation mode chart adjustment:
From the above table, if remote control setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
8.1.7. Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
  • Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)
[Cooling, Dry, Fan]
Remote Control
O
O
O
O
O
Tab (rpm)
SHI
Hi
Me+
Me
Me-
Lo
Lo-
SLo
SSLo
E24DK
1670
1580
1480
1390
1290
1200
930
840
630
[Heating]
Remote Control
O
O
O
O
O
Tab (rpm)
SSHI
SHi
Me+
Me
Me-
Lo
Lo-
SLo
SSLo
E24DK
1690
1690
1590
1500
1400
1310
930
400
300
18
CS-E24DKD CU-E24DKD
B. Indoor Fan Control
i. Indoor fan control operation outline
 1. Cooling / Dry
 2. Heating
19
CS-E24DKD CU-E24DKD
ii. Auto Fan Speed
 1. Cooling
 2. Heating
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E24DK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E24DK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
20
CS-E24DKD CU-E24DKD