8.1.10. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. Quiet button is pressed again.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
D. Control contents
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -100 rpm from setting fan speed.
8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
Automatic Fan Speed (Dry operation)
Manual Fan Speed (Dry operation)
25
CS-E24DKD CU-E24DKD
8.1.10.2. Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. Quiet button is pressed again.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
C. Control contents
a. Fan Speed manual
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -100 rpm from setting fan speed.
 3. Fan Speed Auto
  • If FM Lo
-100 rpm reduce from normal Heating Auto Fan Speed
  • If FM Lo
maintain RPM
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
26
CS-E24DKD CU-E24DKD
8.1.11. Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly.
(a) Cooling Operation
(b) Soft Dry Operation
(c) Heating Operation
8.1.12. Delay ON Timer Control
Delay ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to
provide a comfortable environment when reaching the set ON time.
Seventy minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine
the indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
8.1.13. Delay OFF Timer Control
Delay OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
27
CS-E24DKD CU-E24DKD
8.1.14.  Auto Restart Control
 1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power
supply resumes.
 2. This type of control is not applicable during ON/OFF Timer setting.
8.1.15. Indication Panel
LED
POWER
TIMER
QUIET
POWERFUL
ION
ALLERGEN
BUSTER
Color
Green
Orange
Orange
Orange
Green
Blue
Light ON
Operation ON
Timer Setting ON
Quiet Mode ON
Powerful Mode ON
Ion Mode ON
Operation ON
Light OFF
Operation OFF
Timer Setting OFF
Quiet Mode OFF
Powerful Mode OFF
Ion Mode OFF
Operation OFF
Note:
  • If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode
judgment, or delay ON timer sampling.
  • If Timer LED is blinking, there is an abnormality operation occurs.
  • If Ionizer, LED is blinking, there is an abnormality of Ionizer occurs.
8.1.16.  Auto Operation Switch
 1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
 2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
 3. When the switch is pressed between 8 to 11 seconds, the unit will enter forced Heating Mode standby. Press timer decrement
button for 5S for the unit to operate in Heating Mode.
 4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control (timer decrement button
for 5S), the unit can be changed to different controlling setting (4 type of transmission codes).
 5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote control signal
receiving sound can be cancelled or turned on.