8.2.2. Protection Control For Cooling & Soft Dry Operation
8.2.2.1. Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.
8.2.2.2. Cooling Overload Control
i. Pipe temperature limitation/restriction
  • Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)
  • The compressor stop if outdoor pipe temperature exceeds 62°C
  • If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection)
ii. Electrical part temperature rise protection control
  • To prevent electrical component temperature rise during cooling overload.
  • Judgement condition is by outdoor temperature (sampled every 10s).
  • Control contents:
Outdoor fan speed (switch to zone A and B minimum fan speed).
Outdoor total current (zone C) higher than the specified.
  • Cancellation condition: When one of above is not satisfied.
33
CS-E24CKE CU-E24CKE
8.2.2.3. Anti-Freezing Control
 1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
 2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
 3. At the same time, indoor fan speed increase +40 rpm compared to its normal operation.
 4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
8.2.2.4. Anti-Dew Formation Control
a) Control 1
This control is perform if the following conditions is fulfilled during cooling/dry operation.
i. Control Start Condition
1) Indoor Intake Temperature
24°C & above
2) Outdoor Temperature
Refer below
3) Remote Control Setting Temperature
16°C & above, below 30°C
4) Fan tab
Refer below
Control start after 1) ~ 4) continued for more than 1 minutes.
ii. Control Contents
* If the outdoor temperature
30°C
Me & above (include auto air flow)
0
T < 30 min
74
30 min
T < 90 min
67
90 min
T < 420 min
67
0
T < 30 min
67
30 min
T < 90 min
54
90 min
T < 420 min
54
34
CS-E24CKE CU-E24CKE
* If the outdoor temperature < 30°C
Me & above (include auto air flow)
0
T < 30 min
74
30 min
T < 90 min
67
90 min
T < 420 min
67
0
T < 30 min
67
30 min
T < 90 min
54
90 min
T < 420 min
47
b) Control 2
  • When the following conditions occurs for 20 minutes continuously, anti-dew formation is controlled and air vane change
Horizontal vane shift to 2nd position and Vertical vane shift to center position.
 1. Indoor intake air temperature is 25°C or above and less than 29°C.
 2. Outdoor air temperature is less than 30°C.
 3. Air vane control: Manual Horizontal Airflow and Manual Vertical Airflow.
 4. Fan speed is quiet Lo.
8.2.3. Protection Control For Heating Operation
8.2.3.1. 
Anti Cold Draft Control
Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown
below.
 1. Manual Fan Speed
35
CS-E24CKE CU-E24CKE
 2. Auto Fan Speed
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1300 rpm (E24CK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1300 rpm (E24CK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1100 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
8.2.3.2. Intake Air Temperature Control
Compressor will operate at freq 67 Hz if either one of the below conditions occur:
 1. When the indoor intake air temperature is above 10°C and remote control setting fan speed is lower Me-.
 2. When the indoor intake air temperature is 30°C or above.
36