Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2
and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on
the above operation mode chart, every 30 minutes.
Remote Control Setting Temperature (°C)
T1
T2
T3
16 ~ 18
+10
+8
-5
19 ~ 22
+8
+7
-7
23 ~ 26
+7
+6
-7
27 ~ 30
+6
+5
-8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice
verse.
Operation Mode change from
Temperature shifts (°C)
Cooling/Soft Dry
→ Heating
-2
Heating
→ Cooling/Soft Dry
+2
Example of operation mode chart adjustment:
From the above table, if remote control setting temperature = 25,
T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
8.1.7. Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
  • Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)
[Cooling, Dry, Fan]
Remote Control
O
O
O
O
O
Tab (rpm)
SHI
Hi
Me+
Me
Me-
Lo
Lo-
SLo
SSLo
E24CK
1670
1580
1480
1390
1290
1200
930
840
630
[Heating]
Remote Control
O
O
O
O
O
Tab (rpm)
SSHI
SHi
Me+
Me
Me-
Lo
Lo-
SLo
SSLo
E24CK
1690
1690
1590
1500
1400
1310
930
400
300
17
CS-E24CKE CU-E24CKE
B. Indoor Fan Control
i. Indoor fan control operation outline
 1. Cooling / Dry
 2. Heating
18
CS-E24CKE CU-E24CKE
ii. Auto Fan Speed
 1. Cooling
 2. Heating
Note:
 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E24CK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E24CK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
19
CS-E24CKE CU-E24CKE
iii. Max Capacity Condition
a) During Cooling operation, if all to the following condition is fulfilled, the indoor fan speed is set to Shi.
 1. Indoor intake temperature
24°C.
 2. Operation frequency 64 Hz (E24CK) & above.
 3. Remote Control setting temperature 16°C.
 4. Remote Control setting fan speed Hi.
 5. Outdoor temperature
30°C.
 6. Operation start
within 30 minutes.
* If any of above conditions is not valid, the condition is ended.
b) During Heating operation, if all to the following condition is fulfilled, the indoor fan speed is set to SSHi.
 1. Indoor intake temperature is 17°C or above and less than 23°C.
 2. Operation frequency 68 Hz (E24CK) & above.
 3. Remote Control setting temperature 30°C.
 4. Remote Control setting fan speed Hi.
 5. Outdoor temperature < 4°C.
 6. Operation start
2 hours.
* If any of above conditions is not valid, the condition is ended.
C. Fan Motor Control
i. Motor specification
High voltage PWM Motor
ii. Feedback Control
 1. Rotation speed feedback
Immediately after the fan started, rpm is checked and duty is added, and feedback control is performed.
iii. Abnormal Detection
1. Condition
*
*
Step out signal input
Feedback rotation speed is more than 2550 rpm or below 50 rpm.
However, 10s after fan start, rotation abnormality is not detected.
2. Control
* Fan stop
3. Return
* Restart after 5s
However, in case the fan is stopped by the above conditions within 25s after fan has started, and happened
continuously for 7 times, restart will not be performed.
→ Indoor fan motor lock abnormal (H19)
iv. Restart Prohibition Control
Prohibit to restart within 5s after fan stop.
(except when power is ON)