D. Deodorizing Control
i. Control condition
Control at cooling/dry operation and auto fan speed.
No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.
ii. Operation
The odor status is arranged as below and it is shifted as follow.
* When COMP is ON
1
→ 2 → 3
(Shift to 4 when COMP is OFF)
* When COMP is OFF
4
→ 5 → 4 ←→ 5
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
Odor Status
1
2
3
4
5
4
5
4.5.4...
1
Status Shift
according to COMP
ON
OFF
ON
Status Shift
according
Cooling
zone
40
50
20
90
20
90
.......
to time (s)
Dry zone
ON
Fan Speed
Cooling
zone
OFF
SLo
Auto Fan Speed
SLo
OFF
SLo
OFF
.......
Dry zone
OFF
SLo
OFF
8.1.8. Outdoor Fan Motor Operation
Outdoor fan motor is operated with 15 fan speed. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation.
21
CS-E24CKE CU-E24CKE
Basic Rotation Speed
8.1.9. Airflow Direction
 1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
 2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature
and intake air temperature) and manual (angles of direction can be adjusted using remote control).
Vertical Airflow
Operation Mode
Airflow Direction
Vane Angle (°)
1
2
3
4
5
Heating
Auto with Heat Exchanger
17
Temperature
58
7
Manual
7
17
33
49
67
Cooling, Soft Dry and Fan, Ion
Auto
7 ~ 37
Manual
7
17
25
33
41
Mode Judgment in Auto
Auto
7
Manual
7
17
25
33
41
 1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
22
CS-E24CKE CU-E24CKE
 2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the
positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to
close position.
Horizontal Airflow
 1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
Operation Mode
Vane Angle (°)
Heating, with heat exchanger temperature
A
68 ~ 112
B
90
Cooling, Soft Dry and Fan, Ion
68 ~ 112
 2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern
1
2
3
4
5
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)
90
68
79
101
112
23
CS-E24CKE CU-E24CKE
8.1.10. Quiet operation (Cooling Mode/Cooling area of Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
  • When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
 1. When one of the following conditions is satisfied, quiet operation stops:
 a. Powerful button is pressed.
 b. Stop by OFF/ON switch.
 c. 
Timer “off” activates.
 d. When change mode to fan only mode.
 e. Quiet button is pressed again.
 2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
 3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
 4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
 5. During quiet operation, if timer “on” activates, quiet operation maintains.
 6. After off, when on back, quiet operation is not memorised.
D. Control contents
 1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
 2. Fan speed for quiet operation is -100 rpm from setting fan speed. (Cool and fan mode)
8.1.10.1. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
Automatic Fan Speed (Dry operation)
Manual Fan Speed (Dry operation)
24
CS-E24CKE CU-E24CKE
Page of 93