DOWNLOAD Panasonic CS-E21HKDS / CS-E24HKDS / CU-E21HKD / CU-E24HKD Service Manual ↓ Size: 8.34 MB | Pages: 80 in PDF or view online for FREE

Model
CS-E21HKDS CS-E24HKDS CU-E21HKD CU-E24HKD
Pages
80
Size
8.34 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-e21hkds-cs-e24hkds-cu-e21hkd-cu-e24hkd.pdf
Date

Panasonic CS-E21HKDS / CS-E24HKDS / CU-E21HKD / CU-E24HKD Service Manual ▷ View online

57
15.4. Error Codes Table
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “CHECK” button at Remote Control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using Remote Control or Auto Switch at indoor unit. However, the Remote Control signal receiving sound is
changed from one “beep” to four “beep” sounds.
Abnormality / Protection control
Abnormality
Judgement
Emergency 
operation
Primary location to verify
Diagnosis
display
H00
No abnormality detected
Normal operation
H11
Indoor / outdoor abnormal 
communication
> 1 min after starting 
operation
Indoor fan operation 
only
• Internal / external cable connections
• Indoor / Outdoor PCB
H12
Connection capability rank abnormal
H14
Indoor intake air temperature sensor 
abnormality
Continue for 5 sec.
• Intake air temperature sensor 
(defective or disconnected)
H15
Outdoor compressor temperature sensor 
abnormality
Continue for 5 sec.
• Compressor temperature sensor 
(defective or disconnected)
H16
Outdoor Current Transformer open 
circuit
• Outdoor PCB
• IPM (Power transistor) module
H19
Indoor fan motor merchanism lock
• Indoor PCB
• Fan motor
H23
Indoor heat exchanger temperature 
sensor abnormality
Continue for 5 sec.
O
 (Cooling only)
• Heat exchanger temperature sensor 
(defective or disconnected)
H25
E-Ion breakdown
• Indoor PCB
• E-Ion PCB
H27
Outdoor air temperature sensor 
abnormality
Continue for 5 sec.
O
• Outdoor temperature sensor (defective 
or disconnected)
H28
Outdoor heat exchanger temperature 
sensor abnormality
Continue for 5 sec.
O
• Outdoor heat exchanger temperature 
sensor (defective or disconnected)
H30
Discharge temperature sensor 
abnormality
H33
Indoor/Outdoor wrong connection
• Indoor/Outdoor supply voltage
H38
Indoor/Outdoor mismatch
H58
Abnormal gas sensor
Continue for 6 hours
• Gas sensor                                    
(defective or disconnected)
H97
Outdoor Fan Motor lock abnormality
• Outdoor PCB
• Outdoor Fan Motor
H98
Indoor high pressure protection
• Air filter dirty
• Air circulation short circuit
H99
Indoor heat exchanger anti-freezing 
protection
• Insufficient refrigerant
• Air filter dirty
F11
Cooling / Heating cycle changeover 
abnormality
4 times occurance 
within 30 minutes
• 4-way valve
• V-coil
F90
PFC control
4 times occurance 
within 10 minutes
• Voltage at PFC
F91
Refrigeration cycle abnormality
7 times occurance 
continuously
• No refrigerant
(3-way valve is closed)
F93
Outdoor compressor abnormal revolution
4 times occurance 
within 20 minutes
• Outdoor compressor
F95
Cool high pressure protection
4 times occurance 
within 20 minutes
• Outdoor refrigerant circuit
F96
IPM (power transistor) overheating 
protection
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
F97
Outdoor compressor overheating 
protection
4 times occurance 
within 20 minutes
• Insufficient refrigerant
• Compressor
F98
Total running current protection
3 times occurance 
within 20 minutes
• Excess refrigerant
• Improper heat radiation
F99
Outdoor Direct Current (DC) peak 
detection
7 times occurance 
continuously
• Outdoor PCB
• IPM (Power transistor)
• Compressor
58
16 Disassembly and Assembly Instructions
16.1. Indoor Electronic Controllers, Cross Flow Fan and Indoor Fan Motor
Removal Procedures
16.1.1.
To remove front grille
16.1.2.
To remove power electronic controller
WARNING
High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding
with repair work. Failure to heed this caution may result in electric shocks.
59
60
16.1.3.
To remove discharge grille
16.1.4.
To remove control board
Page of 80
Display

Click on the first or last page to see other CS-E21HKDS / CS-E24HKDS / CU-E21HKD / CU-E24HKD service manuals if exist.