61
16.4. Error Codes Table
Abnormality or Protection Control
Abnormality
Judgement
Protection 
Operation
Problem
Check Location
Diagnosis
Display
H00
No memory of failure
Normal operation
H11
Indoor / outdoor abnormal 
communication
After operation for 
1 minute
Indoor fan only 
operation can start 
by entering into 
force cooling
operation
• Indoor / outdoor
communication not 
establish
• Indoor / outdoor wire 
terminal, indoor / 
outdoor PCB, indoor /
outdoor connection 
wire
H12
Indoor unit capacity unmatched
90s after power 
supply
• Total indoor
capability more than 
maximum limit or less 
than minimum limit, 
or number of indoor 
unit less than two
• Indoor / outdoor
connection wire, 
indoor / outdoor PCB, 
specification and 
combination table in 
catalogue
H14
Indoor intake air temperature sensor 
abnormality
Continuous for 5s
• Indoor intake air 
temperature sensor 
open or short circuit
• Indoor intake air 
temperature sensor 
lead wire and 
connector
H15
Compressor temperature sensor 
abnormality
Continuous for 5s
• Compressor
temperature sensor 
open or short circuit
• Compressor
temperature sensor 
lead wire and
connector
H16
Outdoor current transformer (CT) 
abnormality
• Current transformer 
faulty or compressor 
faulty
• Outdoor PCB faulty 
or compressor faulty
H19
Indoor fan motor merchanism lock
Continuous
happen for 7 times
• Indoor fan motor lock 
or feedback
abnormal
• Fan motor lead wire 
and connector, fan 
motor lock or block
H23
Indoor heat exchanger temperature 
sensor abnormality
Continuous for 5s
• Indoor heat 
exchanger
temperature sensor 
open or short circuit
• Indoor heat 
exchanger
temperature sensor 
lead wire and
connector
H25
Indoor E-Ion abnormality
Port is ON for 10s 
during E-Ion off
• E-Ion PCB
H27
Outdoor air temperature sensor 
abnormality
Continuous for 5s
• Outdoor air 
temperature sensor 
open or short circuit
• Outdoor air
temperature sensor 
lead wire and
connector
H28
Outdoor heat exchanger temperature
sensor 1 abnormality
Continuous for 5s
• Outdoor heat 
exchanger
temperature sensor 1 
open or short circuit
• Outdoor heat 
exchanger
temperature sensor 1 
lead wire and
connector
H30
Outdoor discharge pipe temperature 
sensor abnormality
Continuous for 5s
• Outdoor discharge 
pipe temperature 
sensor open or short 
circuit
• Outdoor discharge 
pipe temperature 
sensor lead wire and 
connector
H32
Outdoor heat exchanger temperature
sensor 2 abnormality
Continuous for 5s
• Outdoor heat 
exchanger
temperature sensor 2 
open or short circuit
• Outdoor heat 
exchanger
temperature sensor 2 
lead wire and
connector
H33
Indoor / outdoor misconnection
abnormality
• Indoor and outdoor 
rated voltage
different
• Indoor and outdoor 
units check
H34
Outdoor heat sink temperature sensor 
abnormality
Continuous for 2s
• Outdoor heat sink 
temperature sensor 
open or short circuit
• Outdoor heat sink 
sensor
H36
Outdoor gas pipe temperature sensor 
abnormality
Continuous for 5s Heating protection 
operation only
• Outdoor gas pipe 
temperature sensor 
open or short circuit
• Outdoor gas pipe 
temperature sensor 
lead wire and
connector
62
H37
Outdoor liquid pipe temperature sensor 
abnormality
Continuous for 5s Cooling protection 
operation only
• Outdoor liquid pipe 
temperature sensor 
open or short circuit
• Outdoor liquid pipe 
temperature sensor 
lead wire and
connector
H38
Indoor / outdoor mismatch
(brand code)
• Brand code not 
match
• Check indoor unit 
and outdoor unit
H39
Abnormal indoor operating unit or 
standby units
3 times happen 
within 40 minutes
• Wrong wiring and 
connecting pipe, 
expansion valve 
abnormality, indoor 
heat exchanger
sensor open circuit
• Check indoor / 
outdoor connection 
wire and connection 
pipe, indoor heat 
exchanger sensor 
lead wire and
connector,
expansion valve and 
lead wire and
connector
H41
Abnormal wiring or piping connection
• Wrong wiring and 
connecting pipe, 
expansion valve 
abnormality
• Check indoor / 
outdoor connection 
wire and connection 
pipe, expansion valve 
and lead wire and 
connector
H58
Indoor gas sensor abnormality
Continuous for 6 
hours
• Indoor gas sensor 
open or short circuit 
• Indoor gas sensor, 
indoor PCB
H64
Outdoor high pressure sensor
abnormality
Continuous for 1 
minutes
• High pressure
sensor open circuit 
during compressor 
stop
• High pressure
sensor, lead wire and 
connector
H97
Outdoor fan motor mechanism lock
2 times happen 
within 30 minutes
• Outdoor fan motor 
lock or feedback 
abnormal
• Outdoor fan motor 
lead wire and
connector, fan motor 
lock or block
H98
Indoor high pressure protection
• Indoor high pressure 
protection (Heating)
• Check indoor heat 
exchanger, air filter 
dirty, air circulation 
short circuit
H99
Indoor operating unit freeze protection
• Indoor freeze
protection (Cooling)
• Check indoor heat 
exchanger, air filter 
dirty, air circulation 
short circuit
F11
4-way valve switching abnormality
4 times happen 
within 30 minutes
• 4-way  valve
switching abnormal
• 4-way valve, lead 
wire and connector
F17
Indoor standby units freezing
abnormality
3 times happen 
within 40 minutes
• Wrong wiring and 
connecting pipe, 
expansion valve
leakage, indoor heat 
exchanger sensor 
open circuit
• Check indoor / 
outdoor connection 
wire and pipe, indoor 
heat exchanger
sensor lead wire and 
connector,
expansion valve lead 
wire and connector
F90
Power factor correction (PFC) circuit 
protection
4 times happen 
within 10 minutes
• Power  factor
correction circuit 
abnormal
• Outdoor PCB faulty
F91
Refrigeration cycle abnormality
2 times happen 
within 20 minutes
• Refrigeration cycle 
abnormal
• Insufficient 
refrigerant or valve 
close
F93
Compressor abnormal revolution
4 times happen 
within 20 minutes
• Compressor
abnormal revolution
• Power transistor 
module faulty or
compressor lock
F94
Compressor discharge pressure
overshoot protection
4 times happen 
within 30 minutes
• Compressor
discharge pressure 
overshoot
• Check refrigeration 
system
F95
Outdoor cooling high pressure
protection
4 times happen 
within 20 minutes
• Cooling high
pressure protection
• Check refrigeration 
system, outdoor air 
circuit
F96
Power transistor module overheating 
protection
4 times happen 
within 30 minutes
• Power transistor 
module overheat
• PCB faulty, outdoor 
air circuit (fan motor)
F97
Compressor overheating protection
3 times happen 
within 30 minutes
• Compressor
overheat
• Insufficient
refrigerant
63
F98
Total running current protection
3 times happen 
within 20 minutes
• Total current
protection
• Check refrigeration 
system, power 
source or
compressor lock
F99
Outdoor direct current (DC) peak 
detection
Continuous
happen for 7 times
• Power transistor 
module current
protection
• Power transistor 
module faulty or
compressor lock
64
16.5. Self-diagnosis Method
16.5.1.
H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
• During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused
• Faulty indoor unit PCB.
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
units.
• Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting