1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions
of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close
position.
12.2.2.
Horizontal Airflow
1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above. 
12.3. Quiet operation (Cooling Mode/Cooling area of Soft Dry Mode)
A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
•  When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
Operation Mode
Vane Angle (
q)
Heating, with heat exchanger temperature
A
68  ~  112
B
90
Cooling and Soft Dry
68 ~ 112
Pattern
1
2
3
4
5
Airflow Direction
Patterns at Remote
Control
Vane Angle (
q)
90
68
78
102
112
42
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. Quiet button is pressed again.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
C. Control contents
1. Auto fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
2. Manual fan speed for quiet operation is reduced from setting fan speed.
3. Outdoor fan speed is changed to Q-Lo
4. Compressor frequency reduced.
12.3.1.
Quiet operation (Heating)
A. Purpose
To provide quiet heating operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
•  When “quiet” button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
1. When one of the following conditions is satisfied, quiet operation stops:
a. Powerful button is pressed.
b. Stop by OFF/ON switch.
c. Timer “off” activates.
d. Quiet button is pressed again.
2. When quiet operation is stopped, operation is shifted to normal operation with previous setting.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains. 
6. After off, when on back, quiet operation is not memorised.
C. Control contents
a. Fan Speed Auto
•  Indoor FM RPM depends on pipe temperature sensor of indoor heat exchanger.
Auto fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi, Me, Lo for 3dB.
b. Fan Speed Manual
•  Manual fan speed for quiet operation is reduced from setting fan speed.
c. Compressor frequency reduced.
12.4. Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift higher up to 3.5
qC (for Heating) or lower up to 2qC
(for Cooling/Soft Dry) than remote control setting temperature for 20 minutes to achieve the setting temperature quickly.
43
12.5. ON Timer Control
ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a
comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the
indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
12.6. OFF Timer Control
OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
12.7. Auto Restart Control
1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after
power supply resumes. 
2. This type of control is not applicable during ON/OFF Timer setting.
12.8. Indication Panel
Note:
• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or
ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
• If e-ion LED is blinking, there is an abnormality of e-ion occurs.
• If PATROL LED is blinking, there is a gas sensor error detection.
LED
POWER
TIMER
QUIET
POWERFUL
e-ion
MILD DRY
PATROL SENSOR
Color
Green
Orange
Orange
Orange
Blue
Blue
Blue
Light ON
Operation ON
Timer Setting ON
Quiet Mode ON
Powerful Mode ON
e-ion ON
Mild Dry ON
Patrol ON
Light OFF
Operation OFF
Timer Setting OFF Quiet Mode OFF
Powerful Mode OFF
e-ion OFF
Mild Dry OFF
Patrol OFF
44
12.9. Patrol Operation
A. Purpose
To monitor air dirtiness level by using Patrol sensor and to maintain air freshness by activates e-ion operation.
B. Control Condition
a. Patrol operation start condition
• When the unit operation is started with “OFF/ON” button.
• When the unit stops, “Patrol” button is pressed, Patrol individual operation will start.
• During cooling only operation, “Patrol” button is pressed.
b. Patrol operation stop condition
When any of the following condition is fulfilled:
• When “OFF/ON” button is pressed.
• During any operation with Patrol, “Patrol” button is pressed again.
• When “e-ion” button is pressed.
• When OFF Timer activates.
c. Patrol operation disable
• To disable the Patrol Operation during unit start (default) with “OFF/ON” button, press “Patrol” button and hold for 5 seconds,
then release.
• To disable the Patrol Operation, press “Patrol” button and hold for 15 seconds, then release.