d. Airflow direction (Horizontal, Vertical) Control
• During any operation mode combines with Patrol operation, airflow direction follows respective operation mode.
• During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is pressed, no signal
is sent to air conditioner, and no change on LCD display.
• During Patrol individual operation if e-ion stops, Airflow direction louver closed.
e. Indicator
• When Patrol operation starts, Patrol Sensor indicator ON.
• When e-ion operation starts based on dirtiness level, e-ion indicator ON.
g. Timer Control
• When ON timer activates when unit stops, previous operation resumes without Patrol operation.
• When ON timer activates during any operation, no change and carry on current operation.
• When OFF timer activates during any operation, all operation stops.
h. Power failure
• During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual operation resumes 
immediately.
• During combination operation, if power failure occurs, after power resumes combination operation resume immediately.
12.10. e-ion Operation
A. Purpose
This operation provides clean air by producing negative ions to attract dust captured at the positively charged e-ion filters.
B. Control Condition
a. e-ion operation start condition
• During unit running at any operation mode, if “e-ion” button is pressed, combination operation (operation mode + e-ion
operation) starts.
• During unit is OFF, if “e-ion” button is pressed, e-ion individual operation starts.
b. e-ion operation stop condition
• When “OFF/ON” button is pressed to stop the operation.
• When “e-ion”  button is pressed again.
• When “Patrol” button is pressed.
• When OFF Timer activates.
f.  Remote Control Receiving Sound
• Normal Operation
• Patrol Mode
• Patrol Mode
• Stop



Patrol Mode
Stop
Normal Operation
Patrol
:
:
:
:
Beep
Long Beep
Beep
Beep
34
c. e-ion operation pause condition
• When indoor fan stop (during deice, odor cut control, thermostat off, etc.). e-ion operation resume after indoor fan restarts.
• When indoor intake temperature   40
°C. e-ion operation resume after indoor intake temperature < 40°C continuously for 30
minutes.
C. Control Content
a. Indoor fan control
• During any operation mode combines with e-ion operation, fan speed follows respective operation mode.
• During e-ion individual operation - only Auto Fan Speed and no Powerful operation is allowed. Even if Fan Speed button is
pressed, no signal is sent to air conditioner, and no change on LCD display.
Auto Fan Speed for e-ion operation switches between HLo and CLo at pattern below:
b. Airflow direction control
• During any operation mode combines with e-ion operation, airflow direction follows respective operation mode.
• During e-ion individual operation, only Auto Air Swing is allowed. Even if Air Swing button is pressed, no signal is sent to air
conditioner, and no change on LCD display.
c. Timer control
• When ON timer activates when unit stops, previous operation resumes without e-ion operation.
• When ON timer activates during any operation, no change and carry on current operation.
• When OFF timer activates during any operation, all operation stops.
d. Indicator
• When e-ion operation starts, e-ion indicator ON.
e. e-ion Check Mode
• To check if e-ion is malfunctioning, during e-ion operation press “e-ion” button for 15 seconds and release to enter e-ion Check
Mode and supplies power to the e-ion Air Purifying System.
• If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion indicator blinks 
immediately.
f. Power failure
• During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation resumes 
immediately.
• During combination operation, if power failure occurs, after power resumes, combination operation resume immediately.
g. Error Detection Control
When e-ion indicator blink, it indicates error listed below:
i. e-ion Air Purifying system main connector to PCB is open:
Judgement Method
• During e-ion operation (include during Patrol operation), e-ion Air Purifying system main connector to PCB is opened.
Troubleshooting Methods
• Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
ii. Abnormal Discharge
Judgement Method
• During e-ion operation, when feedback voltage is -Lo (at microcontroller) is detected, it is judged abnormal discharge and
stops power supplies to the e-ion Air Purifying system.
• The unit retries after 30 minutes and repeat for 24 times. (not applicable for e-ion Check Mode)
35
Troubleshooting Method
• Press “e-ion” button or “OFF/ON” button to stop the operation and check the e-ion Air Purifying system main connector to
PCB.
• After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
• The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
Error Reset Method
• Press “OFF/ON” button to OFF the operation.
• Press AUTO OFF/ON button at indoor unit to OFF the operation.
• OFF Timer activates.
• Press “e-ion” button during e-ion individual mode.
• Power supply reset.
iii. e-ion breakdown
Judgement Method
• When hi-feedback voltage (at microcontroller) supplied to filter during e-ion stop, due to PCB or filter’s high voltage power
supply damage.
• Operations except e-ion continue. Both Timer indicator and e-ion indicator blink.
Troubleshooting Method
• Press “e-ion” button or “OFF/ON” button to stop the operation.
• Change main circuit board or filter’s high voltage power supply.
• When lo-feedback voltage supplied to e-ion Air Purifying system during e-ion operation, e-ion indicator and Timer indicator
stop blinking.
36
13 Protection Control
13.1. Protection Control For All Operations
13.1.1.
Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
13.1.2.
30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
13.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
13.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110
°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95
°C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 25.0 ± 4.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minute. 
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
Operation Mode
E18GK
E21GK
 
X  (A)
Y  (A)
 
X  (A)
Y  (A)
Cooling/Soft Dry (A)
8.8
15.0
11.0
15.0
Cooling/Soft Dry (B)
7.7
15.0
9.6
15.0
Heating
10.8
17.0
11.5
17.0
Page of 63