 a. UP:
  • If move from Lo, the fan speed will be shifted to Maximum 1520 rpm (E21DK), 1480 rpm (E18DK).
  • If move from Maximum, the fan speed no change.
  • In up zone, 10 rpm is added for every 10s until Maximum 1520 rpm (E21DK), 1480 rpm (E18DK).
 b. DOWN:
  •  The fan speed will be decreased one step every 10 sec. until Minimum 1270 rpm.
 c. 
Current Output Fixed:
  • Maintain at present fan speed.
 d. Instantaneous Maximum:
  • Fan speed will be increased to maximum auto fan speed.
 e. Temperature in ( ) is for Powerful Mode operation.
8.2.3.2. Intake Air Temperature Control
Compressor will operate at freq. 86 Hz (E18DK), 92 Hz (E21DK) or less respectively if either one of the below conditions occur:
 1. When the indoor intake air temperature is above 10°C and remote control setting fan speed is lower Me-.
 2. When the indoor intake air temperature is 30°C or above.
8.2.3.3. Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the below figures. This
control will begin one minute after the compressor starts.
41
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
8.2.3.4. Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
8.2.3.5. Outdoor Temperature Control
  • Outdoor temperature is detected and the following control is perform.
  • Control operates after more than 1 minute the compressor has started.
42
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
8.2.3.6. Deice Control
A. Deice operation (Normal Deice Operation)
 1. Detection methods
Outdoor heat exchanger temperature sensor, timer.
 2. Deice operation time chart
Notes
 a. During deice operation, the relationship between outdoor pipe temperature and time T1 is such operation will
proceed to next stage.
 b. The deice will be performed only after 1 hour from when the operation has started.
 c. 
When Comp. OFF by the sequence No. 1, 6, 7 compressor can restart back without 3 minutes waits (immediate
restart).
Outdoor heat exchanger temperature
a
15°C
b
18°C
c
25°C
43
CS-E15DKDW CU-E15DKD / CS-E18DKDW CU-E18DKD / CS-E21DKDS CU-E21DKD
 3. Explanation of operation
1) Before the deice is started, compressor frequency is set to the specified value for T0-timer.
2) After deice is started, the 4-way valve, OD Fan and ID fan are OFF.
3) After 4-way valve is OFF for 30 s, compressor frequency is set to the specified value.
4) Before deice is ended, if the outdoor heat exchanger temperature exceeds a°C, set compressor frequency and expansion valve to the
specified values.
5) When outdoor heat exchanger temperature exceeds b°C, or 10.5 minutes has passed since the 4-way valve is OFF, operation at timer
T5 will be started.
6) After the above 5) operation, if the specified time has passed, the deice operation ending signal will be produced. The comp. Hz is set
to the specified value and at the same time outdoor fan motor ON signal is produced.
7) After T6 the deice ending signal is produced, 4-way valve is set to ON, indoor fan is ON, Compressor frequency is FREE, and return to
normal heating operation.
 4. Deice operation judgement condition
When any of below a, b, c, d condition is satisfied, deice signal is produced.
 a. Continuously, outdoor heat exchanger temperature < 3°C for 120 minutes and outdoor heat exchanger temperature <
-5°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
 b. Continuously, outdoor heat exchanger temperature < 3°C for 80 minutes and outdoor heat exchanger temperature < -
6°C for 3 minutes and outdoor air temperature > -1°C and Comp. is ON.
 c. 
Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < -
7°C and outdoor air temperature
-3°C for 3 minutes and Comp. is ON.
 d. Continuously, outdoor heat exchanger temperature < 3°C for 40 minutes and outdoor heat exchanger temperature < -
8°C for 3 minutes and outdoor air temperature < -3°C and Comp. is ON.
However, the first deice will start only after minimum of 60 minutes in operation.
(2nd deice and onward shall follow above conditions)
B. Auto clean deice
 1. Purpose
To improve heating start-up operation by detecting the residual ice on OD heat exchanger and perform deice operation
automatically before operation is started by ON Timer.
 2. Control Content:
1). Auto deice is performed 15 min. before standby operation (pre-deice operation in 15 min.).
2). When below deice conditions are fulfilled, auto clean deice operation will start.
3). After auto clean deice is completed, standby operation is performed as per load.
4). When deice conditions are not fulfilled, auto clean deice will not happen and will continue with standby operation.
44