61
15.5. Self-diagnosis Method
15.5.1.
H11 (Indoor/Outdoor Abnormal Communication)
Malfunction Decision Conditions
• During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is
checked whether it is normal.
Malfunction Caused
• Faulty indoor unit PCB.
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
• Faulty outdoor unit PCB.
• Indoor unit-outdoor unit signal transmission error due to wrong wiring.
• Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor
units.
• Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.
Troubleshooting
62
15.5.2.
H12 (Indoor/Outdoor Capacity Rank Mismatched)
Malfunction Decision Conditions
• During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
• Wrong models interconnected.
• Wrong indoor unit or outdoor unit PCBs mounted.
• Indoor unit or outdoor unit PCBs defective.
• Indoor-outdoor unit signal transmission error due to wrong wiring.
• Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor
• Wrong indoor unit or outdoor unit PCBs mounted.
• Indoor unit or outdoor unit PCBs defective.
• Indoor-outdoor unit signal transmission error due to wrong wiring.
• Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor
units.
Troubleshooting
63
15.5.3.
H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are
used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting
64
15.5.4.
H15 (Compressor Temperature Sensor Abnormality)
Malfunction Decision Conditions
• During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor
are used to determine sensor errors.
Malfunction Caused
• Faulty connector connection.
• Faulty sensor.
• Faulty PCB.
• Faulty sensor.
• Faulty PCB.
Troubleshooting