DOWNLOAD Panasonic CS-E10KB4EA / CU-E10HBEA Service Manual ↓ Size: 19 MB | Pages: 98 in PDF or view online for FREE

Model
CS-E10KB4EA CU-E10HBEA
Pages
98
Size
19 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / AIR CONDITIONER
File
cs-e10kb4ea-cu-e10hbea.pdf
Date

Panasonic CS-E10KB4EA / CU-E10HBEA Service Manual ▷ View online

49
12.5. Timer Control
12.5.1.
ON Timer Control
ON timer can be set using remote control, the unit with timer set will start operate earlier than the setting time. This is to provide a
comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to determine the
indoor intake air temperature and outdoor air temperature in order to judge the operation starting time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
12.5.2.
OFF Timer Control
OFF timer can be set using remote control, the unit with timer set will stop operate at set time.
12.6. Auto Restart Control
1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after
power supply resumes. 
2. This type of control is not applicable during ON/OFF Timer setting.
12.7. Indication Panel
Note:
• If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation mode judgment, or
ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
LED
POWER
TIMER
QUIET
POWERFUL
AIR SWING
Color
Green
Orange
Orange
Orange
Orange
Light ON
Operation ON
Timer Setting ON
Quiet Mode ON
Powerful Mode ON
Auto Air Swing ON
Light OFF
Operation OFF
Timer Setting OFF
Quiet Mode OFF
Powerful Mode OFF
Auto Air Swing OFF
50
12.8. Drain Pump Control Operation
• To drain out the condensed watar trapped in the drain pan in order to prevent the condensed water from overflowing from the
drain pan and leaking.
• Drain Pump starts to operate 10 sec. after compressor and Indoor fan ON.
• Drain Pump stop to operate 90 sec. after compressor OFF.
Drain Pump Error
Drain Pump Error occurs when:
- Within 20 minutes, the float switch is ON twice.
- Float switch is ON continuously for 2 minutes 30 seconds.
When error occurs, the timer indicator blinks and the unit stops its operation.
51
13 Protection Control
13.1. Protection Control For All Operations
13.1.1.
Restart Control (Time Delay Safety Control)
• The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by
pressing OFF/ON button at remote control within this period.
• This control is not applicable if the power supply is cut off and on again.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2.
30 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 30 seconds in a normal operation although the intake air
temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON button at the remote
control is permitted or the Auto OFF/ON button at indoor unit.
• The reason for the compressor to force operation for minimum 30 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
13.1.3.
Total Running Current Control
1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.
4. The first 30 minutes of cooling operation, (A) will be applied.
E10HB
Operation Mode
 X (A)
Y (A)
Cooling/Soft Dry (A) & (C)
4.95
15.06
Cooling/Soft Dry (B)
4.43
15.06
Heating
6.21
15.06
52
13.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 110
°C, compressor operation will stop immediately.
2. Compressor operation restarts after three minutes the temperature decreases to 95
°C.
B. DC Peak Current Control
1. When electric current to IPM exceeds set value of 22.33 ± 5.0 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after two
minutes. 
3. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute. If
this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
13.1.5.
Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
If compressor discharge temperature exceeds 112
°C, compressor will be stop, occurs 4 times per 20 minutes, timer LED will be
blinking (“F97” is to be confirmed).
13.2. Protection Control For Cooling & Soft Dry Operation
13.2.1.
Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust base on Outdoor Air Temperature.
Page of 98
Display

Click on the first or last page to see other CS-E10KB4EA / CU-E10HBEA service manuals if exist.