12.5. Indoor Fan Speed Control
• Indoor Fan Speed can be set using remote control.
12.5.1.
Fan Speed Rotation Chart
12.5.2.
Automatic Fan Speed Control
• When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.
- Fan speed rotates in the range of Hi, Me and Lo-.
- Deodorizing Control will be activated.
• Auto Fan Speed during Cooling operation:
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher volume of refrigerant
in liquid form returning to the compressor.
5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the
room. 
This is to obtain the actual reading of the intake air temperature.
6. For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and lesser noise
environment, after 70 seconds from the restart of compressor.
COOL/DRY
CS-C24GKD
CS-C18GKD
S Hi
1590
1460
Hi
1500
1400
Me
1390
1250
H Lo
1330
1220
C Lo
1240
1150
Lo-
1100
980
S Lo
860
780
Q Hi
1400
1300
Q Me
1290
1150
Q Lo
1140
1050
34
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
12.5.3.
Manual Fan Speed Control
• Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control.
• There are 3 types of fan speed settings: Lo, Me, Hi.
12.6. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor (C18GK).
• There is 2 speed for outdoor fan motor.Outdoor fan speed can be changed to Hi or Lo according to outdoor temperature.
• For Cooling or Soft Dry operation when outdoor temperature reaches to 31
°C (Hi-speed), 29°C (Lo-speed).
• When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
• Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
35
12.7. Vertical Airflow Direction Control
12.7.1.
Auto Control
• When the vertical airflow direction is set to Auto using the remote control, the louver swings up and down as shown in the
diagram.
• When stopped with remote control, the discharge vent is reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the
louver will stop swinging and rest at the upper limit.
12.7.2.
Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stopped with remote control, the discharge vent is reset, and stop at the closing position.
12.8. Horizontal Airflow Direction Control
12.8.1.
Auto Control
• When the horizontal airflow direction is set to Auto using the remote control, the vanes swings left and right as shown in the
diagram.
• When stopped with remote control, the discharge vane is reset, and stop at the reset position.
• During Cooling operation or Soft Dry operation, indoor fan motor may stop to rotate at certain periods. At that condition, the vane
will stop swinging and rest at 22
° angle.
36
12.8.2.
Manual Control
• When the horizontal airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction vane move left and right in the range shown in the diagram.
The louver can be adjusted by pressing the button to the desired vane position.
• When stopped with remote control, the vanes is reset, and stopped at reset position.
12.9. Powerful Operation
• The Powerful operation is to achieve the setting temperature quickly.
• When Powerful operation is set, the setting temperature will be automatically decreased 3
°C internally against the present
setting temperature (Lower temperature limit: 16
°C).
• This operation automatically will be running under SHi Fan Speed (Cooling).
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10
° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10
° downward.
• Powerful operation stops when:-
- Powerful operation has operate for 4 hours.
- Powerful button is pressed again.
- Quiet button is pressed.
- Stopped by OFF/ON operation button.
- Timer OFF activates.
- Operation mode is changed.