8 Operation Details
8.1. Cooling Operation
 • Cooling operation can be set using remote control.
 • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control.
 • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C
to 30°C.
 • During cooling operation, the compressor will stop running and restart as shown in below figure.
8.1.1. Cooling Operation Time Diagram
17
CS-C18DKD CU-C18DKD / CS-C24DKD CU-C24DKD
8.2.1. Soft Dry Operation Time Diagram
8.2. Soft Dry Operation
 • Soft Dry operation can be set using remote control.
 • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
 • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
 • When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown
in below figure.
 • However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
18
CS-C18DKD CU-C18DKD / CS-C24DKD CU-C24DKD
8.3. Automatic Operation
 • Automatic operation can be set using remote control.
 • This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature.
 • After judged the temperature, the operation mode is determined by refering to the below standard.
 • Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
 • The setting temperature for all the operations can be changed one level up or one level down from the standard temperature
as shown in below table by pressing on the temperature up or temperature down button at remote control.
 • The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX1 at indoor electronic controller.
19
CS-C18DKD CU-C18DKD / CS-C24DKD CU-C24DKD
8.4. Operation Control
(For 8.4.1. to 8.4.7. information applies only to Cooling and Soft Dry Operation)
8.4.1. Restart Control (Time Delay Safety Control)
 • When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
 − Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
 − Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
 • If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
 • This phenomenon is to balance the pressure inside the refrigerant cycle.
8.4.2. 7 Minutes Time Save Control
 • The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
 • This phenomenon is to reduce the built up humidity inside a room.
8.4.3. 60 Seconds Forced Operation
 • Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
 • The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
8.4.4. Anti-Freezing Control
 • If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
 • This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
 • Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
 • Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
20
CS-C18DKD CU-C18DKD / CS-C24DKD CU-C24DKD
Page of 72