 1. The inside and outside connecting cable can be connected
without removing the front grille.
 2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 × 2.5 mm
2
(C18CK, C24CK, RS/RU-C18/24CK) or 5 × 2.5 mm
2
(A18CK, A24CK) flexible cord, type designation 245 IEC 57
or heavier cord.
     • 
• 
• 
• Ensure the color of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
     • 
• 
• 
• Earth lead wire shall be longer than the other lead wires
as shown in the figure for the electrical safety in case of
the slipping out of the cord from the anchorage.
     • 
• 
• 
• Secure the cable onto the control board with the holder
(clamper).
INSTALLATION OF AIR PURIFYING FILTERS
 1. Open the front panel.
 2. Remove the air filters.
 3. Put air purifying filters (left) and triple refreshing deodorizing
filter (right) into place as shown in illustration below.
10.2.5. CONNECT THE CABLE TO THE INDOOR UNIT
45
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if
necessary such as when servicing.
 1. Open the intake grille and remove the screw at the front of
the front grille.
 2. Set the vertical airflow direction louver to the horizontal
position.
 3. Slide down the 3 caps on the front grille as shown in the
illustration below, and then remove the 3 mounting screws.
 4. Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, first set the vertical
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order.
     • 
• 
• 
• After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
 1. Fix the unit on concrete or rigid frame firmly and horizontally
by bolt nut. (ø10 mm).
 2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly with
bolt or nails.
10.3.3. CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
Connect the piping
     • 
• 
• 
• Align the center of piping and sufficiently tighten the flare
nut with fingers.
     • 
• 
• 
• Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the
“AUTO” switch.
 1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the
Auto Switch is pressed.
 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
PURPOSE)
The Test Run operation will be activated if the Auto Switch
is pressed continuously for more than 5 sec. to below 10
sec.. A “beep” sound will occur at the fifth sec., in order to
identify the starting of Test Run operation
 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote Controller receiving sound can be
change over by pressing the “AUTO” Switch continuously
for 10 sec. and above. A “beep”, “beep” sound will occur at
the tenth sec., in order to indicate the “ON/OFF” change
over of remote control receiving sound.
MODEL
Piping size (Torque)
Gas
Liquid
C18CK, A18CK, RS-C18CK
1/2” (55 N.m)
1/4” (18 N.m)
C24CK, A24CK, RS-C24CK
5/8” (65 N.m)
1/4” (18 N.m)
10.3. OUTDOOR UNIT
10.3.1. SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
10.3.2. INSTALL THE OUTDOOR UNIT
46
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
CUTTING AND FLARING THE PIPING
 1. Please cut using pipe cutter and then remove the burrs.
 2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
 3. Please make flare after inserting the flare nut onto the
copper pipes.
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut
(located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
10.3.4.  EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
 1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
     • 
• 
• 
• Be sure to connect the end of the charging hose with the push pin to the service port.
 2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
 4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
 6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
 7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
 8. Mount valve caps onto the 2-way valve and the 3-way valve.
     • 
• 
• 
• Be sure to check for gas leakage.
47
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
1) Checking a gas leakage
 1. Remove the service-port cap from the 3-way valves.
 2. Connect the Manifold gauge set to the service port of
Liquid side 3-way valve.
 3. Connect the Charging Cylinder to the Manifold gauge
set and open the valve of the Cylinder.
 4. Open the low pressure side valve of the Manifold gauge
for approx. 10 seconds and then close.
 5. Check gas-leakage of the connecting portion of pipings
with the gas-leak detector.
2) Air purging
The air remaining in the Refrigeration cycle which contains
moisture may cause malfunction on the Compressor.
 1. To purge the air, push the pin on the Gas side 3-way
valve for three seconds with a Hexagonal wrench and
set it free for one minute.
     • 
• 
• 
• Repeat this for three times.
 2. To balance the refrigerant, close the low pressure side
valve on the Manifold gauge and release refrigerant
from the piping through service port until the gauge
indicates 0.5 - 0.3 MPa.
 3. Set both 3-way valves to open position with the
Hexagonal wrench for the unit operation.
CAUTION
     • 
• 
• 
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
     • 
• 
• 
• If the leak stops when the piping connections are tightened further, continue working from step 3.
     • 
• 
• 
• If the leak does not stop when the connections are retightened, repair the location of leak.
     • 
• 
• 
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
10.3.5. AIR PURGING OF THE PIPING AND INDOOR UNIT
<For the left pipings>
1) Measure the pressure.
2) Keep it for 5-10 minutes
     • 
• 
• 
• Ensure if the pressure indicated on the gauge is as same as that of measured at first time
48