DISPOSAL OF OUTDOOR UNIT DRAIN WATER
     • 
• 
• 
• If a drain elbow is used, the unit should be placed on a
stand which is taller than 3 cm.
     • 
• 
• 
• If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan
will not rotate.
CHECK THE DRAINAGE
     • 
• 
• 
• Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)
     • 
• 
• 
• Pour a glass of water into the drain tray-styrofoam.
     • 
• 
• 
• Ensure that water flows out from drain hose of the indoor
unit.
EVALUATION OF THE PERFORMANCE
     • 
• 
• 
• Operate the unit at cooling operation mode for fifteen
minutes or more.
     • 
• 
• 
• Measure the temperature of the intake and discharge air.
     • 
• 
• 
• Ensure the difference between the intake temperature and
the discharge is more than 8°C.
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut
connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable being clamped firmly?
Is the drainage OK?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
Is the air purifying filter installed?
10.3.6. CONNECT THE CABLE TO THE OUTDOOR UNIT
 1. Remove the control board cover from the unit by loosening the screw.
 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 × 2.5 mm
2
(C18CK,
C24CK, RS/RU-C18/24CK) or 5 × 2.5 mm
2
( A18CK, A24CK) flexible cord, type designation 245 IEC 57 or heavier cord.
 3. Secure the cable onto the control board with the holder (clamper).
 4. Attach the control board cover back to the original position with the screw.
10.3.7. PIPE INSULATION
 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
with thickness 6 mm or above.
49
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
11 2-way, 3-way Valve
2-way Valve (Liquid Side)
3-way Valve (Gas Side)
Works
Shaft Position
Shaft Position
Service Port
Shipping
Close
Close
Close
(With valve cap)
(With valve cap)
(With cap)
Evacuation
Close
Close
Open
(Installation and
(Counter-Clockwise)
(Clockwise)
(Push-pin)
Re-installation)
Operation
Open
Open
Close
(With valve cap)
(With valve cap)
(With cap)
Pumping down
Close
Open
Open
(Transferring)
(Clockwise)
(Counter-Clockwise)
(Connected manifold
gauge)
Evacuation
Open
Open
Open
(Servicing)
With vacuum pump
Gas charging
Open
Open
Open
(Servicing)
(With charging cylinder)
Pressure check
Open
(Servicing)
Open
Open
(Connected manifold
gauge)
Gas releasing
Open
(Servicing)
Open
Open
(Connected manifold
gauge)
50
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
11.1.1. Evacuation of Installation
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO
EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES
in the following procedure.
 1. Connect a charging hose with a push pin to the Low
side of a charging set and the service port of a 3-way
valve.
     • 
• 
• 
• Be sure to connect the end of the charging hose with the
push pin to the service port.
 2. Connect the centre hose of the charging set to a
vacuum pump.
 3. Turn on the power switch of the vacuum pump and
make sure that the needle in the gauge moves from 0
MPa (0 cmHg) to -0.1 MPa (-76 cmHg). Then evacuate
the air for approximately ten minutes.
 4. Close the Low side valve of the charging set and turn
off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
BE SURE TO TAKE THIS PROCEDURE IN ORDER TO
AVOID GAS LEAKAGE.
If air remain in the indoor unit and refrigeration pipes, it will
affect the compressor, reduce to cooling capacity, and could
lead to a malfunction.
 5. Disconnect the charging hose from the vacuum pump
and from the service port of the 3-way valve.
 6. Tighten the service port cap at a torque of 18 N.m with
a torque wrench.
 7. Remove the valve caps of the 2-way valve and the 3-
way valve. Position both of the valves to “open” using
a hexagonal wrench (4 mm).
 8. Mount the valve caps onto the 2-way and 3-way valves.
     • 
• 
• 
• Be sure to check for gas leakage.
Caution
If gauge needle does not move from 0 cmHg to -76
cmHg in step (3) above, take the following measures:
If the leaks stop when the piping connections are
tightened further, continue working from step (3).
If the leaks do not stop when the connections are
retightened, repair the location of the leak.
11.1. Evacuation of the Equipment (For Europe & Oceania Destination)
Procedure:
51
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
11.1.2. Pumping down
Procedure:
 1. Confirm that both the 2-way and 3-way valves are set to
the opened position.
     • 
• 
• 
• Remove the valve stem caps and confirm that the valve
stems are in the opened position.
     • 
• 
• 
• Be sure to use a hexagonal wrench to operate the valve
stems.
 2. Operate the unit for 10 to 15 minutes.
 3. Stop operation and wait for 3 minutes, then connect the
charge set to the service port of the 3-way valve.
     • 
• 
• 
• Connect the charge hose with the push pin to the Gas
service port.
 4. Air purging of the charge hose.
     • 
• 
• 
• Open the low-pressure valve on the charge set slightly
to purge air from the charge hose.
 5. Set the 2-way valve to the closed position.
 6. Operate the air conditioner at the cooling cycle and
stop it when the gauge indicates 0 MPa (0 kg/cm
2
G).
If the unit cannot be operated at the cooling condition
(weather is rather cool), short the Pumping Down pins
on the Main Control P.C.B.
(Simply press the pumping down button if it is
equipped.)
So that the unit can be operated.
 7. Immediately set the 3-way valve to the closed position.
     • 
• 
• 
• Do this quickly so that the gauge ends up indicating 0.1
MPa (1 kg/cm
2
G) to 0.3 MPa (3 kg/cm
2
G).
 8. Use
refrigerant
reclaiming
equipment
to
collect
refrigerant from indoor unit and pipes.
 9. Disconnect the charge set, and mount the 2-way and 3-
way valve’s stem caps and the service port caps.
     • 
• 
• 
• Use a torque wrench to tighten the service port cap to a
torque of 18 N.m.
     • 
• 
• 
• Be sure to check for gas leakage.
 10. Disconnect pipes from indoor unit and outdoor unit.