Panasonic CS-C18CKE / CU-C18CKE / CS-C24CKE / CU-C24CKE Service Manual ▷ View online

     • 
• 
• 
• The mode judging temperature and standard setting temperature can be increased by 2°C, by open the circuit of JX1 at indoor
electronic controller.
8.6. Powerful Mode Operation
     • 
• 
• 
• Purpose of this operation is to obtain the setting temperature quickly.
     • 
• 
• 
• When the Powerful Mode is set, the set temperature will be automatically decreased 3°C against the present setting
temperature (Lower temperature: 16°C).
     • 
• 
• 
• This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry).
     • 
• 
• 
• Vertical Airflow Direction:-
- In “Manual” setting, the vane will automatically shift down 10° lower than previous setting.
- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.
     • 
• 
• 
• Powerful Mode will operate for 15 minutes only, after that it will shift back to previous operation mode.
     • 
• 
• 
• Powerful Mode will stop if:-
- Powerful mode button is pressed again.
- Stopped by ON / OFF switch.
- Timer OFF activates.
- Quiet mode button is pressed.
- Operation mode button is changed.
8.7. Random Auto Restart Control
     • 
• 
• 
• If there is a power failure during air conditioners operation, operation will be automatically restarted after 3 to 4 minutes when
the power is resumed.
It will start with previous operation mode and airflow direction.
     • 
• 
• 
• Restart time is decided randomly using 4 parameter:-
Intake air temperature, setting temperature, fan speed and Air Swing Blade position.
     • 
• 
• 
• Auto Restart Control is not available when Timer is set.
     • 
• 
• 
• This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)
25
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
Vertical Airflow Direction Auto-Control
     • 
• 
• 
• When set a Airflow Direction Auto-Control with remote
control, the louver swings up and down as shown in the
diagram.
     • 
• 
• 
• The louver does not swing when the Indoor Fan Motor
stops during operation at the upper limit.
     • 
• 
• 
• When stopped with remote control, the discharge vent is
reset, and stopped at the closing position.
     • 
• 
• 
• During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 36° to 12° - 28° under
Cooling and Soft Dry operation mode.
Vertical Airflow Direction manual Control
     • 
• 
• 
• When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in
the diagram.
The louver can be adjusted by pressing the button to the
desired louver position.
     • 
• 
• 
• When the remote control is used to stop the operation, the
discharge vent is reset, and stopped at the closing position.
     • 
• 
• 
• During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 14°, 19°, 24°, 30°, 36° to
16°, 18°, 20°, 22°, 24° under Cooling and Soft Dry operation
mode.
Horizontal Airflow Direction Auto-Control
     • 
• 
• 
• When set a Airflow Direction Auto-Control with remote
control, the vanes swings left and right as shown in the
diagram.
     • 
• 
• 
• The vanes does not swing when the Indoor Fan Motor stops
during operation at 22° angle.
     • 
• 
• 
• When stopped with remote control, the discharge vent is
reset, and stopped at the reset position.
     • 
• 
• 
• During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0° - 44° to 14° - 30° under
Cooling and Soft Dry operation mode.
8.8. Airflow Direction Control
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation.
1. There is no swinging while indoor fan motor is stopped during Cooling, Ion and Soft Dry operation.
26
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
Horizontal Airflow Direction manual Control
     • 
• 
• 
• When the manual Airflow Direction Selection Button is
pressed, the automatic airflow is released and the airflow
direction vane move left and right in the range shown in the
diagram.
The louver can be adjusted by pressing the button to the
desired vane position.
     • 
• 
• 
• When the remote control is used to stop the operation, the
vanes is reset, and stopped at reset position.
     • 
• 
• 
• During Anti-dew condensation prevention, Airflow Direction
Manual control angle change from 0°, 11°, 22°, 33°, 44° to
14°, 18°, 22°, 26°, 30° under Cooling and Soft Dry operation
mode.
8.9. Delay ON Timer Control
     • 
• 
• 
• When the Delayed ON Timer is set by using the remote control, the unit will start operate slightly before the set time, so that
the room will reach nearly to the set temperature by the desired time.
     • 
• 
• 
• For Cooling and Soft Dry mode, the operation will start 15 minutes before the set time.
     • 
• 
• 
• For Automatic mode, the indoor fan will operate at SLo speed for 20 seconds, 15 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
8.10. Remote Control Signal Receiving Sound
     • 
• 
• 
• Long beep sound will be heard when:-
     − 
− 
− 
− Stopping the Air Conditioner using ON/OFF switch.
     − 
− 
− 
− Stopping the Quiet Mode.
     − 
− 
− 
− Stopping the Powerful Mode.
     − 
− 
− 
− Stopping the Ion Mode.
     • 
• 
• 
• Short beep sound will be heard for others.
     • 
• 
• 
• To switch off the beep sound:-
Press the “Automatic Operation Button” continuously for 10 seconds or more (“beep” “beep” will be heard at the 10th second).
Repeat the above if you want to switch ON the beep sound.
However, if the “Automatic Operation Button” has been pressed the Automatic operation will be activated.
If you do not require this operation, you may change it by using the remote control.
27
CS-C18CKE CU-C18CKE / CS-C24CKE CU-C24CKE
8.11. Ionizer Operation
Purpose
To provide fresh air effect to user by discharging minus Ion to air.
Control Condition
a. Ionizer Only Operation.
 1. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at remote control is pressed.
Fan & ionizer on, ION LED illuminates, but power LED maintain off. (1
→ 2)
However, fan speed can be adjusted later by customer during this operation.
Airflow direction (Horizontal Vane) control:
Follow vane direction control at cooling mode.
Horizontal vane can be changed by customer during ion only operation.
 2. Ion only operation can be off by pressed ION button again. (2
→ 1)
 3. It can be changed to previous operated mode (Auto, Cool, Dry, Fan) + ion operation by OFF/ON switch. (2
→ 4)
 4. During ion only operation, if power failure occur, after power resume, ionizer & air-conditioner resumes immediately.
 5. After error = 24 times, (about 11h 30 min.), ion & fan off with Ion LED blinks continuously.
(Detail refer to Ionizer Error detection control.)
b. Operation Mode + Ionizer Operation.
 1. Ionising Operation Start Condition
When air-conditioner unit is in “ON” condition (Cool, Dry, Fan, Auto mode) and ION operation button at remote control is
pressed. Ionizer on & ION LED illuminates. (3
→ 4)
Power LED also illuminates.
 2. Ionising Operation Stop Condition
When one of the following condition is satisfied, ION operation stops.
 a. Stopped by ON/OFF switch.
 b. Timer OFF activates.
 c. 
ION operation button is pressed again.
 d. ION feedback signal shows error.
28