49 
15.4  Error Codes Table 
Diagnosis 
display 
Abnormality / 
Protection control 
Abnormality 
Judgment 
Protection 
Operation 
Problem Check 
location 
H00 
No memory of failure 
— 
Normal operation
— 
— 
H11 
Indoor/outdoor 
abnormal 
communication 
After operation for 
1 minute 
Indoor fan only 
operation can 
start by entering 
into force cooling
operation 
Indoor/outdoor 
communication not 
establish 
 Indoor/outdoor wire terminal 
 Indoor/outdoor PCB 
 Indoor/outdoor connection wire 
H12 
Indoor unit capacity 
unmatched 
90s after power 
supply 
— 
Total indoor capability 
more than maximum limit 
or less than minimum limit, 
or number of indoor unit 
less than two 
 Indoor/outdoor connection wire 
 Indoor/outdoor PCB 
  Specification and combination 
table in catalogue 
H14 
Indoor intake air 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Indoor intake air 
temperature sensor open 
or short circuit 
  Indoor intake air temperature 
sensor lead wire and connector 
H15 
Compressor 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Compressor temperature 
sensor open or short circuit 
 Compressor temperature 
sensor lead wire and connector 
H16 
Outdoor current 
transformer (CT) 
abnormality 
— — 
Current transformer faulty 
or compressor faulty 
  Outdoor PCB faulty or 
compressor faulty 
H19 
Indoor fan motor 
merchanism lock 
Continuous 
happen for 7 times 
— 
Indoor fan motor lock or 
feedback abnormal 
  Fan motor lead wire and 
connector 
  Fan motor lock or block 
H23 
Indoor heat 
exchanger 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Indoor heat exchanger 
temperature sensor open 
or short circuit 
  Indoor heat exchanger 
temperature sensor lead wire 
and connector 
H24 
Indoor heat 
exchanger 
temperature sensor 
2 abnormality 
Continuous for 5s 
— 
Indoor heat exchanger 
temperature sensor 2 open 
or short circuit 
  Indoor heat exchanger 
temperature sensor 2 lead wire 
and connector 
H25 
Indoor ion device 
abnormality 
Port is ON for 10s 
during ion device off 
— — 
  ion device PCB 
H27 
Outdoor air 
temperature sensor 
abnormality 
Continuous for 5s 
— 
Outdoor air temperature 
sensor open or short circuit 
  Outdoor air temperature sensor 
lead wire and connector 
H28 
Outdoor heat 
exchanger 
temperature sensor 
1 abnormality 
Continuous for 5s 
— 
Outdoor heat exchanger 
temperature sensor 1 open 
or short circuit 
  Outdoor heat exchanger 
temperature sensor 1 lead wire 
and connector 
H30 
Outdoor discharge 
pipe temperature 
sensor abnormality 
Continuous for 5s 
— 
Outdoor discharge pipe 
temperature sensor open 
or short circuit 
  Outdoor discharge pipe 
temperature sensor lead wire 
and connector 
H32 
Outdoor heat 
exchanger 
temperature sensor 
2 abnormality 
Continuous for 5s 
— 
Outdoor heat exchanger 
temperature sensor 2 open 
or short circuit 
  Outdoor heat exchanger 
temperature sensor 2 lead wire 
and connector 
H33 
Indoor / outdoor 
misconnection 
abnormality 
— — 
Indoor and outdoor rated 
voltage different 
  Indoor and outdoor units check 
H34 
Outdoor heat sink 
temperature sensor 
abnormality 
Continuous for 2s 
— 
Outdoor heat sink 
temperature sensor open 
or short circuit 
  Outdoor heat sink sensor 
H36 
Outdoor gas pipe 
temperature sensor 
abnormality 
Continuous for 5s 
Heating 
protection 
operation only 
Outdoor gas pipe 
temperature sensor open 
or short circuit 
  Outdoor gas pipe temperature 
sensor lead wire and connector 
H37 
Outdoor liquid pipe 
temperature sensor 
abnormality 
Continuous for 5s 
Cooling 
protection 
operation only 
Outdoor liquid pipe 
temperature sensor open 
or short circuit 
  Outdoor liquid pipe temperature 
sensor lead wire and connector 
H38 
Indoor/Outdoor 
mismatch (brand 
code) 
— 
— 
Brand code not match 
  Check indoor unit and outdoor 
unit 
H39 
Abnormal indoor 
operating unit or 
standby units 
3 times happen 
within 40 minutes 
— 
Wrong wiring and 
connecting pipe, expansion 
valve abnormality, indoor 
heat exchanger sensor 
open circuit 
 Check indoor/outdoor 
connection wire and connection 
pipe 
  Indoor heat exchanger sensor 
lead wire and connector 
  Expansion valve and lead wire 
and connector 
 
 
 
 
50 
Diagnosis 
display 
Abnormality / 
Protection control 
Abnormality 
Judgment 
Protection 
Operation 
Problem Check 
location 
H41 
Abnormal wiring or 
piping connection 
— — 
Wrong wiring and 
connecting pipe, expansion 
valve abnormality 
 Check indoor/outdoor 
connection wire and connection 
pipe 
  Expansion valve and lead wire 
and connector 
H59 
ECONAVI sensor 
abnormality 
Continuous for 25s 
— 
ECONAVI sensor open or 
short circuit 
  ECONAVI sensor (defective or 
disconnected) 
 ECONAVI PCB 
H64 
Outdoor high 
pressure sensor 
abnormality 
Continuous for 1 
minutes 
— 
High pressure sensor open 
circuit during compressor 
stop 
  High pressure sensor 
  Lead wire and connector 
H70 
Light sensor 
abnormality 
Continuous for 24 
hours, 15days 
— 
Light sensor open or 
short circuit 
  Light sensor (defective or 
disconnected) 
H97 
Outdoor fan motor 
mechanism lock 
2 times happen 
within 30 minutes 
— 
Outdoor fan motor lock or 
feedback abnormal 
  Outdoor fan motor lead wire 
and connector 
  Fan motor lock or block 
H98 
Indoor high pressure 
protection 
— — 
Indoor high pressure 
protection (Heating) 
  Check indoor heat exchanger 
  Air filter dirty 
  Air circulation short circuit 
H99 
Indoor operating unit 
freeze protection 
— — 
Indoor freeze protection 
(Cooling) 
  Check indoor heat exchanger 
  Air filter dirty 
  Air circulation short circuit 
F11 
4-way valve 
switching 
abnormality 
4 times happen 
within 30 minutes 
— 
4-way valve switching 
abnormal 
 4-way valve 
  Lead wire and connector 
F17 
Indoor standby units 
freezing abnormality 
3 times happen 
within 40 minutes 
— 
Wrong wiring and 
connecting pipe, expansion 
valve leakage, indoor heat 
exchanger sensor open 
circuit 
 Check indoor/outdoor 
connection wire and pipe 
  Indoor heat exchanger sensor 
lead wire and connector 
  Expansion valve lead wire and 
connector 
F90 
Power factor 
correction 
(PFC) circuit 
protection  
4 times happen 
within 10 minutes 
— 
Power factor correction 
circuit abnormal 
  Outdoor PCB faulty 
F91 
Refrigeration cycle 
abnormality 
2 times happen 
within 20 minutes 
— 
Refrigeration cycle 
abnormal 
  Insufficient refrigerant or valve 
close 
F93 
Compressor 
abnormal revolution 
4 times happen 
within 20 minutes 
— 
Compressor abnormal 
revolution 
  Power transistor module faulty 
or compressor lock 
F94 
Compressor 
discharge overshoot 
protection 
4 times happen 
within 30 minutes 
— 
Compressor discharge 
pressure overshoot 
  Check refrigeration system 
F95 
Outdoor cooling high 
pressure protection 
4 times happen 
within 20 minutes 
— 
Cooling high pressure 
protection 
  Check refrigeration system 
  Outdoor air circuit 
F96 
Power transistor 
module overheating 
protection 
4 times happen 
within 30 minutes 
— 
Power transistor module 
overheat 
 PCB faulty 
  Outdoor air circuit (fan motor) 
F97 
Compressor 
overheating 
protection 
3 times happen 
within 30 minutes 
— Compressor 
overheat 
 Insufficient refrigerant 
F98 
Total running current 
protection 
3 times happen 
within 20 minutes 
— Total 
current 
protection 
  Check refrigeration system 
  Power source or compressor 
lock 
F99 
Outdoor direct 
current (DC) peak 
detection 
Continuous 
happen for 7 times 
— 
Power transistor module 
current protection 
  Power transistor module faulty 
or compressor lock 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
51 
15.5 Self-diagnosis Method 
15.5.1  H11 (Indoor/Outdoor Abnormal Communication) 
Malfunction Decision Conditions 
  During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal 
transmission is checked whether it is normal. 
 
Malfunction Caused 
  Faulty indoor unit PCB. 
  Faulty outdoor unit PCB. 
  Indoor unit-outdoor unit signal transmission error due to wiring error. 
  Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the 
indoor and outdoor units. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
YES 
YES 
YES 
NO
When abnormality indication starts again 
Measure the AC voltage at terminal 1 & 2 of outdoor unit
terminal board  
Is the measured voltage 230/240V? 
●  AC power supply abnormal fluctuation
●  Defect in communication circuitry
of outdoor unit PCB
●  Replace the PCB
●  Improper connection at terminals
indoor/outdoor 
● Check 
indoor/outdoor 
connecting 
cable
Measure the DC voltage at terminal 2 & 3 (communication
terminals) of outdoor unit terminal board 
Is the measured DC voltage fluctuate between 10~70V?  
●  Improper connection at terminals
indoor/outdoor 
● Check 
indoor/outdoor 
connecting 
cable
Measure the AC voltage at terminal 1 & 2 of indoor unit
terminal board
Is the measured voltage 230/240V? 
●  Defect in receiver/transmitter module of 
the communication circuitry in indoor
unit PCB   
●  Replace the indoor unit PCB
YES
Measure the DC voltage at terminal 2 & 3 of indoor unit
terminal board
Is the measured DC voltage fluctuate between 18~25V?
For safety reason and to prevent 
component breakdown, always switch 
off the power before remove and 
connect the component. 
NO
NO
NO
Caution
52 
15.5.2  H12 (Indoor/Outdoor Capacity Rank Mismatched) 
Malfunction Decision Conditions 
  During startup, error code appears when different types of indoor and outdoor units are interconnected. 
 
Malfunction Caused 
  Wrong models interconnected. 
  Wrong indoor unit or outdoor unit PCBs mounted. 
  Indoor unit or outdoor unit PCBs defective. 
  Indoor-outdoor unit signal transmission error due to wrong wiring. 
  Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor 
and outdoor units. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Check the indoor and outdoor unit connection wires.
Check indoor and outdoor units model number.
Is indoor unit and outdoor unit model numbers matched?
Check the spare part numbers of the indoor and outdoor unit 
PCBs and compare with their Part Lists.
Matched compatibility?
Is there any wiring error?
When abnormality indication starts again.
For safety reason and to prevent
component breakdown, always switch 
off the power before remove and 
connect the component.
Correct the indoor-outdoor unit’s connection wires.
Change for the specified indoor or outdoor unit 
PCB.
Replace the indoor and outdoor unit PCBs.
Match the compatible model(s).
NO
NO
NO
YES
YES
YES
Caution
Page of 92