[Product features]
2.2.1. Low-noise design improves in
surrounding areas
 1. The noise-suppressing winglet fan is a result of new
research into vane design theory. The unique curved shape
suppresses the generation of vortexes, thus reduces air
flow noise.
 2. The adoption of double-orifice rings reduces air passage
resistance.
 3. Strengthening of the noise insulation materials in the
compressor and the sealing-in of mechanical noise allows
vibration noise to be greatly enclosed and suppressed.
 4. The heat exchanger has an L-shaped design to allow air to
flow more smoothly.
 5. Noise is automatically reduced further during night time
operation with lower outdoor air temperatures.
2.2.2. Automatic restart function
When the electric power resumes after a power failure, the unit
will automatically restarts the operation in the pre-failure mode.
2.2.3. Low ambient cooling operation
Cooling operation is possible at outdoor temperature of -5°C.
2.2. New low-noise outdoor units
2.3. Greatly improved workability increases system renewal capability
5
HIDE AWAY TYPE
2.3.1. Pipes that are one size larger can
also be connected for renewal
 • 
If renewing the system, existing refrigerant pipes can be
utilized so that only the indoor units need to be replaced.
 • 
For example, liquid and gas pipes from 10 years ago can be
connected to current pipes with the same size for one size
larger. Effective utilization of materials reduces working
time and trouble. (Adaptor sockets are not supplied.)
2.3.2. Additional refrigerant charging
unnecessary for 30 m
 • 
All models do not require any additional charging of
refrigerant for 30 m of pipe length. This makes installation
much easier.
2.3.3. Drain water dripping-prevention
structure
 • 
The base of the outdoor unit is provided with a single drain
hole in order to prevent drain water from leaking out of the
unit. Body connecting a drain elbow and a discharge pipe,
water leakages can be prevented even when the unit is
installed against a wall.
2.3.4. Space saving design allows units
to be installed side by side
continuously
 • 
Servicing after installation can be carried out by removing
the front covers.
2.3.5. Easy test operation
 • 
Test operation can be carried out for both indoor and
outdoor units.
2.3.6. Long pipe design
Max piping length: 50 (m)
24BB~50BB
Height difference/equivalent pipe
length
30/50
2.3.7. Internal pipe connection
 • 
Pipes are connected inside the units (inside the side
covers), making the final appearance more attractive.
 • 
Pipes can be diverted outward in any of four directions
(forward, right, down, rear).
 • 
Small liquid pipe diameters of 9.52mm for 43BB and 50BB
models, making installation work much easier.
Liquid-side pipe diameters (mm) : 9.52 (43BB~50BB
models)
2.3.8. Centralized draining method
 • 
Even when multiple outdoor units are installed to a wall, the
drain outlets can be concentrated into a single drain pipe.
This
makes
installation
easier
and
also
improve
appearance.
2.4. A brand-new control method
using the latest in technology
2.4.1. Power supply wiring is also easier
Power supply wiring and other wiring tasks can be carried out
more easily.
 • 
Twin non-polar wires used to connect indoor and outdoor
units.
 • 
Adoption of connection error prevention circuits for drives
wires and signal wires. If a connection error is made, the
relay does not operate and current does not flow to the
circuit boards.
6
HIDE AWAY TYPE
2.4.2. Separate indoor/outdoor unit
power supplies
The power supply can be connected to (1) just the outdoor
units, or (2) to both indoor and outdoor units.
2.4.5. Twin and Triple operation
 • 
Simultaneous air conditioning of wide spaces and corners is
possible. Indoor units of different horsepowers and models
can even be used in combination.
 • 
Master unit and slave-units can be set automatically in twin
and triple systems. No address setting is necessary.
 • 
Multiple indoor units can be operated simultaneously with a
single remote control. Note that individual operation is not
possible.
2.4.3. Automatic setting initialization
function (Remote control and
Indoor unit)
In accordance with the indoor and outdoor units connected and
the connection methods, conditions such as the configuration
(twin or triple format) and remote-control functions such as
cooling only or heat pump model are automatically detected
and set instantly.
Twin and Triple combination table
2.4.4. Group control equipment
7
HIDE AWAY TYPE
ELECTRICAL DATA (50Hz)
3 SPECIFICATION (HEAT PUMP TYPE)
3.1 CS-A24BD3P / CU-A24BBP5
ITEM / MODEL
Indoor Unit
Outdoor unit
Main Body
CS-A24BD3P
CU-A24BBP5
Cooling Capacity
kW
6.50
(BTU/h)
(22,200)
Heating Capacity
kW
7.10
(BTU/h)
(24,200)
Refrigerant Charge-less
m
30
Standard Air Volume for High Medium and
Low Speed
m
3
/min
Hi 20
Hi 43
cfm
Hi 706
1518
External Static Pressure
mmAq
Hi 5 Me 4 Lo 3
-
Pa
Hi 49 Me 39 Lo 29
Air Inlet
Backward Suction
Rear sided Suction
Air Outlet
Front blow-out
Front blow-out
Outside Dimension (H x W x D)
mm
270 x (1000 + 100) x 650
900 x 900 x 320
Net Weight
kg (lbs)
40 (88)
80 (176)
Piping
Connection
Refrigerant
Gas
mm (inch)
O.D Ø 15.88 (5/8) Flared Type
Liquid
mm (inch)
O.D Ø 6.35 (1/4) Flared Type
Drain
mm
Female screw RC1 (PT1)
I.DØ 20 x 1
Compressor Type, Number of Set
-
Hermetic-1 (Rotary), 1
Starting Method
-
Direct on-line starting
Motor
Type
-
2-pole single phase induction motor
Input
kW
-
Cool/Heat 2.31/2.30
Rated Output
kW
-
1.9
Fan
Type, Number of Set
Sirocco fan-2
Prop. fan-1
Air Volume Control
Three-Step and Auto mode
-
(Remote Control)
Motor
Type
4-pole single phase induction motor
6-pole single phase induction motor
Input
kW
0.15
0.11
Rated Output
kW
0.085
0.05
Air-heat Exchanger
Louvre-fin type
Louvre-fin type
Refrigerant Control
Capillary tube
Capillary tube
Refrigerant Oil (Charged)
L
-
MS32 (1.3)
Refrigerant (Charged)
kg (oz)
-
R-22 2.5 (88)
Running
Adjustment
Control Switch
Wired Remote Control
-
Room Temperature
Thermostat (Main Body)
-
Safety Devices
Internal protector for compressor, Internal thermostat for F.M, Crankcase heater,
High pressure switch, Current Transformer
Noise Level (Sound Pressure)
dB (A)
Hi 35 Lo 35
Cooling 50, Heating 51
 1. Cooling capacities are based on indoor temp. 27°C D.B (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air temp. 35°C
D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
 2. Heating capacities are based on indoor temp. 20° CD.B (68.0° FD.B.) and outdoor air temp. 7°C D.B. (44.6°F D.B.), 6°C W.B.
(42.8°F D.B.)
MODEL / ITEM
CS-A24BD3P/CU-A24BBP5
Condition by JIS B 8616
Volts
V
220
230
240
Phase
Single
Single
Single
Input Power
kW
Cool
2.59
2.59
2.59
Heat
2.50
2.50
2.50
Running Current
A
Cool
12.1
11.9
11.6
Heat
11.5
11.2
11.3
Starting Current
A
49
51
52
Power Factor
%
Cool
97
95
93
Heat
99
97
92
*Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
Panasonic
Power source
AC, 1~220V, 230V, 240V 50Hz
8
HIDE AWAY TYPE