9 OPERATION RANGE
Power Supply
The applicable voltage range for each unit is given in “ the following table”. The working voltage among the three phases
must be balanced within 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher
than 85% of the rated voltage.
Power Supply
Model
Unit Main Power
Applicable Voltage
Phase, Volts
Hz
Maximum
Minimum
A18BB
1~220
50
242
198
1~230
50
253
207
1~240
50
264
216
Indoor and Outdoor Temperature All Models
Operating
Hz
Indoor Temp. (D.B./W.B.) (°C)
Outdoor Temp. (D.B./W.B.) (°C)
Maximum
Minimum
Maximum
Minimum
Cooling
50
32/23
21/15
43/-
-5/-
Heating
50
27/-
16/-
24/18
-10/-
25
Correction of cooling and heating capacities according to
the connecting pipe length.
The data of cooling capacities (marked on the name plate)
are based on 5 metres connecting pipe and horizontal
installation.
(Cooling)
Equivalent Length = actual pipe length +
number of elbow x ELE + number of oil
trap x ELO
ELE : equivalent length of elbow.
ELO : equivalent length of oil trap.
10.2. REFRIGERANT ADDITIONAL
CHARGE
     • 
• 
• 
• 
The piping length exceeds 10 metres.
APPLICABLE FOR ALL MODELS
Before shipment, this air conditioner is filled with the rated
amount of refrigerant subject to 10m piping length. (The
rated amount of refrigerant is indicated on the name plate.)
But when the piping length exceeds 10m, additional charge
is required according to the following table.
For other pipe length of other installation multiply
by the following correction factor to determine the
revised cooling capacity.
(Heating)
Outer diameter of gas
side pipe mm (inch)
ELE
6.35 (1/4)
0.18
12.7 (1/2)
0.20
15.88 (5/8)
0.25
19.05 (3/4)
0.35
Model
Ref. Charge
2.0 & 2.5HP
20g per 1m
3~6HP
50g per 1m
Example :
CS-A18BD3P
In case of 10 m long pipe (one-way), the
amount of refrigerant to be replenished is:
(10 - 10) x 20 = 0g
CS-A43BD3P
In case of 50m long pipe (one-way), the
amount of refrigerant to be replenished is:
(50 - 30) x 50 = 1,000g
10 PIPE LENGTH
10.1. CORRECTION OF COOLING AND HEATING CAPACITIES
26
10.3. Piping installation by existing piping
It is possible to use the existing piping by adjusting the refrigerant gas volume.
Please do correct piping installation referring to the table below.
Standard piping specification
Heat pump type
Cooling only type
Liquid piping
Gas piping
Gas charge-less length
Additional gas volume
(Ømm)
(Ømm)
(m)
(g/m)
CU-A18BBP5
CU-C18BBP5
6.35
12.7
10
20
Attention
     • 
• 
• 
• 
Please do not decrease the gas piping size. (It causes the breakdown of the compressor)
     • 
• 
• 
• 
The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping
specification.
27
11 OPERATING CHARACTERISTIC
11.1. OPERATING CHARACTERISTIC
HEAT PUMP MODEL
Model
Main Power
Compressor Motor
Indoor Unit
Outdoor Unit
Source
Fan Motor
Fan Motor
Voltage
Frequency
S.C.
R.C.(A)
IPT(kW)
R.C.
IPT
R.C.
IPT
(V)
(Hz)
(A)
COOL/HEAT
COOL/HEAT
(A)
(kW)
(A)
(kW)
CS-A18BD3P
220
50
38
7.9 / 7.9
1.74 / 1.72
0.30
0.06
0.50
0.10
CU-A18BBP5
230
50
40
7.7 / 7.7
1.74 / 1.72
0.30
0.06
0.50
0.10
240
50
42
7.6 / 7.6
1.74 / 1.72
0.30
0.06
0.50
0.10
COOLING ONLY MODEL
CS-A18BD3P
220
50
38
7.9
1.74
0.30
0.06
0.50
0.10
CU-C18BBP5
230
50
40
7.7
1.74
0.30
0.06
0.50
0.10
240
50
42
7.6
1.74
0.30
0.06
0.50
0.10
Legend:
S.C. : Starting Current
R.C. : Running Current
IPT : Power Consumption
28