DOWNLOAD Panasonic CS-A18BD3P / CU-A18BBP5 Service Manual ↓ Size: 8.28 MB | Pages: 102 in PDF or view online for FREE

Model
CS-A18BD3P CU-A18BBP5
Pages
102
Size
8.28 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / ROOM AIR CONDITIONER
File
cs-a18bd3p-cu-a18bbp5.pdf
Date

Panasonic CS-A18BD3P / CU-A18BBP5 Service Manual ▷ View online

 1 
SERVICE INFORMATION 
3
 2 
FEATURES 
4
 3 
SPECIFICATION (HEAT PUMP TYPE) 
7
 4 
SPECIFICATION (COOLING ONLY TYPE ) 
8
 5 
TECHNICAL DRAWING 
9
 6 
CIRCUIT DIAGRAM 
11
 7 
OPERATING INSTRUCTION 
22
 8 
REFRIGERATION CYCLE 
24
 9 
OPERATION RANGE 
25
 10 PIPE LENGTH 
26
 11 OPERATING CHARACTERISTIC 
28
 12 FAN PERFORMANCE 
29
 13 SAFETY DEVICE 
30
CS-A18BD3P CU-A18BBP5
CS-A18BD3P CU-C18BBP5
 14 COMPONENT SPECIFICATION 
31
 15 CAPACITY AND POWER CONSUMPTION 
33
 16 DISCHARGE AND SUCTION PRESSURE 
36
 17 POSITION OF THE CENTRE GRAVITY 
37
 18 SOUND DATA 
38
 19 TWIN AND TRIPLE 
39
 20 WIRING MISTAKE PREVENTION 
45
 21 TEST OPERATION AND SELF DIAGNOSIS 
46
 22 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 
50
 23 GROUP CONTROL 
51
 24 TROUBLE SHOOTING 
52
 25 EMERGENCY OPERATION 
58
 26 CONTROL 
59
AIR CONDITIONER
CONTENTS
 Page 
Page
ORDER NO. MAC0208031C8
 27 INSTALLATION (INDOOR UNIT) 
70
 28 INSTALLATION (OUTDOOR UNIT) 
87
 29 REPLACEMENT PARTS 
97
2
1 SERVICE INFORMATION
Caution:
Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please
use a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ±
10°C).
Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
Notice of Address setting for NEW Hide-Away / NEW Outdoor Unit.
The new Hide-Away / New Outdoor models are possible to have address setting for twin / triple control or group control
by automatic when main power supply is switched on.
(Manual address setting is also possible by using Dip switch on Indoor unit P.C. board.) However, this address setting is only
possible when made proper wiring connection and also Indoor unit should be original virgin unit
.
1.1. Example of trouble at test operation
If found out as following phenomenon at test operation on site, it may have possibility of wrong address setting.
Therefore, please ensure of the address setting.
 1. LCD display of wired remote control had not illuminate although the main power supply switch is ‘on’.
 2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated.
(But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control ON/OFF switch is ‘on’.)
 3. P.C. board had memorized wrong setting information.
 a. If main power supply is switched ‘on’ with the wrong connection.
 b. When changing the connection or combination of units due to re-installation etc.
     • 
• 
• 
• 
When changing the system from twin to triple (triple to twin).
     • 
• 
• 
• 
When changing the system from group control to normal one to one system.
     • 
• 
• 
• 
When making the replacement of units as master and slave etc.
1.2. Caution of test operation
Do not touch the remote control switch and do not change any wirings for one minute when the main power supply switch is ‘on’.
(Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When main power supply switch is ‘on’, the P.C. board will automatically memorized the connecting system.
Consequently, when initial power supply is ‘on’, there will not be interchangeability of units even of the same type and same
capacity unit. Therefore unable to connect the unit to another system.
3
2.1. Variety of excellent features
2.1.1. Compact design, height 27 cm
     • 
• 
• 
• 
The height has been reduced to 27 cm (for 2.0HP to
6.0HP), the equipment can be installed in limited spaces.
2.1.2. Versatile installation
     • 
• 
• 
• 
The indoor unit is designed in order that air will also enter
from below, for easier installation under different conditions.
     • 
• 
• 
• 
The equipment has two drain outlets on the right and left
side for adoption to the installation conditions in the
building.
2.1.3. Easy maintenance
     • 
• 
• 
• 
Equipped with a filter as standard. The filter can be
removed in three directions for easier maintenance.
2.1.4. Static pressure selection
     • 
• 
• 
• 
The static pressure is selectable; 5mmAq or 7mmAq. The
static pressure can be selected according to the condition
of the duct.
2.1.5. Quiet operation
     • 
• 
• 
• 
The sound level is as low as 33db (A) for 2.0 HP. The
models is ideal for installation in offices, shop and houses
where quiet operation is important.
2.1.6. 
Auto fan mode operation
     • 
• 
• 
• 
Auto fan mode is added to existing modes Hi, Me and Lo.
It aotomatically adjusts the fan speed according to the
indoor temperature.
2.1.7. Dry mode function
     • 
• 
• 
• 
Dry mode can make a comfortable indoor environment
during wet season.
2.1.8. 
Automatic changeover function
(heat pump models)
     • 
• 
• 
• 
The unit automatically switches between cooling and
heating in accordance with operating load in order to
maintain a confortable indoor temperature.
2.1.9. Common design for Indoor unit
and Remote Control
     • 
• 
• 
• 
The indoor unit and the wire remote control are design as a
common specification between Cooling only and Heat
Pump models.
2.1.10. Wired Remote Control
     • 
• 
• 
• 
The new design includes an easily -visible red pilot lamp.
The power can be turned on and off at a single touch,
without opening the cover.
     • 
• 
• 
• 
A built-in thermistor, allowing indoor temperature detection
in accordance with indoor conditions by switching with main
unit thermistor.
     • 
• 
• 
• 
Twin non-polar wires make installation work easy, (10 m
cable supplied as accessories)
2.1.11.  Automatic restart function
When the electric power resumes after a power failure, the unit
will automatically restarts the operation in the pre-failure mode.
2.1.12. Low ambient cooling operation
Cooling operation is possible at outdoor temperature of -5°C
(2.5 HP ~ 6 HP models), 10°C (2 HP model).
2 FEATURES
4
Page of 102
Display

Panasonic CS-A18BD3P / CU-A18BBP5 Service Manual ▷ Download

  • DOWNLOAD Panasonic CS-A18BD3P / CU-A18BBP5 Service Manual ↓ Size: 8.28 MB | Pages: 102 in PDF or view online for FREE
  • Here you can View online or download the Service Manual for the Panasonic CS-A18BD3P / CU-A18BBP5 in PDF for free, which will help you to disassemble, recover, fix and repair Panasonic CS-A18BD3P / CU-A18BBP5 Air Conditioner. Information contained in Panasonic CS-A18BD3P / CU-A18BBP5 Service Manual (repair manual) includes:
  • Disassembly, troubleshooting, maintenance, adjustment, installation and setup instructions.
  • Schematics, Circuit, Wiring and Block diagrams.
  • Printed wiring boards (PWB) and printed circuit boards (PCB).
  • Exploded View and Parts List.