CHECK THE DRAINAGE
  • Connect the drain hose, as described below.
  • Pour water into the drain pan to ensure that water is drained
smoothly through the drain hose.
AUTO SWITCH OPERATION
The below operations will be performed by pressing the
“AUTO” switch.
 1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the
Auto Switch is pressed.
 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
PURPOSE)
The Test Run operation will be activated if the Auto Switch
is pressed continuously for more than 5 sec. to below 10
sec.. A “pep” sound will occur at the fifth sec., in order to
identify the starting of Test Run operation.
 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote Controller receiving sound can be
changed over by pressing the “AUTO” Switch continuously
for 10 sec. and above. A “pep”, “pep” sound will occur at the
tenth sec., in order to indicate the “ON/OFF” change over of
remote control receiving sound.
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut
connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable ends being clamped firmly?
Is the drainage OK?
Is the earth wire connection properly done?
Is the cooling operation normal?
Is the indoor unit properly secured to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the thermostat operation normal?
Is the remote control’s LCD operation normal?
NOTE:
These equipment shall be connected to a suitable mains network with a main impedance less than the following:
CS-A18CTP/CU-A18CTP5 : 0.10
CS-A24CTP/CU-A24CTP5 : 0.07
CS-V24CTP/CU-V24CTP5 : 0.13
49
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
  • Remote Control Reset
When the batteries are inserted for the first time, or the
batteries are replaced, all the indications will blink and the
remote control might not work.
If this happen, you will find a resetting terminal, and by
shorting it with a minus screwdriver, it will return to normal.
  • Changing the wireless remote control transmission
code
When two indoor units are installed in the same room, in
order to prevent operating errors caused by using two
remote controls, cut a jumper wire at the remote control
printed circuit board (A - B) and cut a jumper wire at the
indoor printed circuit board (JX4). It is possible to select
from 4 types of transmission codes including one at time of
delivery condition (0).
10 Servicing Information
Caution:
  • Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
  • Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
50
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
11.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table on the right.
11 Troubleshooting Guide
51
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
11.1.1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Heating Mode
Condition of the air
conditoner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube
or Strainer
Short circuit in the
indoor unit
Heat radiation
deficiency of the
outdoor unit
Inefficient compression
  • Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
11.1.2. Diagnosis methods of a malfunction of a compressor and 4-way valve
Nature of fault
Symptom
  • Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
  • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
  • The difference between high pressure and low pressure becomes almost zero.
  • Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
  • The compressor is a humming sound.
  • Electric current during operation becomes approximately 80% lower than the normal value.
Insufficient switches of the 4-way valve
  • The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.
52
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
Page of 73
Display

Click on the first or last page to see other CS-A12CTP / CU-A12CTP5 / CS-A18CTP / CU-A18CTP5 / CS-A24CTP / CU-A24CTP5 service manuals if exist.