At the best location, start installation according to Indoor-
Outdoor Unit Installation Diagram.
 1. Fix the unit on concrete or rigid frame firmly and horizontally
by bolt nut (ø10 mm).
 2. When installing at roof, please consider strong wind. Please
fasten the installation stand firmly with bolt or nails.
Model
A
B
C
D
V12CT
570
105
18.5
320
V18 / 24CT
540
129
15
330
Please make flare after inserting flare nut (locate at joint portion
of indoor piping) onto the copper pipe.
(in case of using long piping)
Connect the piping
  • Align the center of piping and sufficiently tighten the flare
nut with fingers
  • Further tighten the flare nut with torque wrench to the
specified torque as stated in the table.
Connecting The Piping To Outdoor Unit
 1. Align the center of the pipings and sufficiently tighten
the flare nut with fingers.
 2. Finally, tighten the flare nut with torque wrench until the
wrench clicks.
  • When tightening the flare nut with torque wrench,
ensure the direction for tightening follows the arrow
on the wrench.
Pipe size
Torque
Liquid Side 1/4”
18 N.m
Gas Side 1/2”
55 N.m
Gas Side 5/8”
65 N.m
9.3. OUTDOOR UNIT
9.3.1. SELECT THE BEST LOCATION
(Refer to “Select the best location” section)
9.3.2. INSTALL THE OUTDOOR UNIT
9.3.3. CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
CUTTING AND FLARING THE PIPING
 1. Please cut using pipe cutter and then remove the burrs.
 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
 3. Please make flare after inserting the flare nut onto the copper pipes.
45
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
 1. Remove the Service port caps from both 3-way valves.
 2. Connect the Manifold gauge set to the service port of Liquid
side 3-way valve.
 3. Connect the Charging Cylinder to the Manifold gauge set
and open the valve of the Cylinder.
 4. Open the low pressure side valve of the Manifold gauge for
approx. 10 seconds and then close.
 5. Check a gas-leakage of the connecting portion of pipings.
 6. Open the low pressure side valve of the Manifold gauge
again.
9.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES
in the following procedure.
 1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
  • Be sure to connect the end of the charging hose with the push pin to the service port.
 2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
 4. Close the valve at the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after
approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
 6. Tighten the service port caps of both of the 3-way valves at a torque of 18 N·m with a torque wrench.
 7. Remove the caps of both of the 3-way valves. Position both of the valves to “OPEN” using a hexagonal wrench (4 mm).
 8. Mount caps onto both of the 3-way valves.
  • Be sure to check for gas leakage.
CAUTION
  • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
  • If the leak stops when the piping connections are tightened further, continue working from step 3.
  • If the leak does not stop when the connections are retightened, repair the location of leak.
  • Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
9.3.5. (b) AIR PURGING OF THE PIPING AND INDOOR UNIT
CS-C/A/V/W18/24CT
1) Checking a gas-leakage
46
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
The remaining air in the Refrigeration cycle which contains
moisture may cause malfunction on the compressor.
 1. Remove the caps from the 2-way and 3-way valves.
 2. Remove the service-port cap from the 3-way valves.
 3. To open the valve, turn the valve stem of 2-way valve
counter-clockwise approx. 90° and hold it there for ten
seconds, then close it.
 4. Check gas-leakage of the connecting portion of the pipings.
 5. To open 2-way valve again, turn the valve stem counter-
clockwise until it stops.
2) Air Purging
The air which contains a moisture is remaining in the Refrigeration cycle may cause a malfunction on the Compressor.
 1. To purge the air, push the pin on the Gas side 3-way valve for three seconds using with a Hexagonal wrench and set it free
for one minute.
  • Repeat this three times.
 2. To balance the refrigerant, close the low pressure side valve on the Manifold gauge and release a refrigerant from the piping
through service port until the gauge indicates 0.49 ~ 0.294 MPa.
 3. Set the both 3-way valves to open position with the hexagonal wrench for the unit operation.
CS-C/A/V/W12CT
47
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5
 1. If you may connect an additional drain hose, the end of the
drain-outlet should keep distance from the ground.
CAUTION
(Do not dip it into water, and fix it on the wall to avoid
swinging in the wind.)
In case of the Outdoor unit is installed
below position of the indoor unit.
 2. Tape the Pipings, drain hose and Connecting Cable from
down to up.
 3. From the pipings gathered by taping along the exterior wall
and fix it onto the wall by saddle or equivalent.
(Refer to the right side diagram)
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
  • If a drain elbow is used, the unit should be placed on a
stand which is taller than 3 cm.
  • If the unit is used in an area where temperature falls below
0°C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan
will not rotate.
 1. Tape the Pipings, and Connecting cable from down to up.
 2. From the pipings gathered by taping along the exterior wall
and the trap is required to prevent water from entering the
room.
 3. Fix the pipings onto the wall by saddle or equivalent.
(Refer to the left side diagram)
9.3.6. CONNECT THE CABLE TO THE OUTDOOR UNIT
 1. Remove the control board cover from the unit by loosening the screw.
 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 x 1.5mm
2
(C/V12CT) or
5 x 1.5mm
2
(A/W12CT) or 3 x 2.5mm
2
(C/V18/24CT) or 5 x 2.5mm
2
(A/W18/24CT)
 3. Secure the cable onto the control board with the holder (clamper).
 4. Attach the control board cover back to the original position with the screw.
9.3.7. PIPE FORMINGS, INSULATION AND FINISHING
In case of the Outdoor unit is installed upper position of the indoor unit.
48
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5