—26—
COMPLAINT
CAUSE
REMEDY
Test capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean of replace.
Close if open.
Determine if the unit is properly sized for the area to
be cooled.
Check the set screw or clamp. If loose or missing,
correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.
Remove the cabinet and carefully rearrange tubing
not to contact cabinet, compressor, shroud, and
barrier.
Set the knob to COOL (      ) or HEAT (      ) while
rocker switch is ON.
Check terminals. If loose, repair or replace.
Check the synchronous motor for open circuit.
Check the voltage at outlet. If none, correct.
Check the teminals. If loose, repair or replace.
Check for continuity, refer to the wiring diagram for
teminal identification. Replace the switch if the
circuit is open.
Check setting. Turn to warmest position.
Check the position of knob. If not at the warmest
setting, advance knob to this setting. Check conti-
nuity of the thermostat. Check continuity of control
by removing lead from terminal, turn the
selector switch to heat, and check between com-
mon terminal and H terminal. (NOTE: Room tem-
perature should be 30°C(86°F) or lower when test-
ing the temperature control.) If no continuity
exists, replace thermostat.
Selecter switch must be in the HEAT (      ) mode.
Check continuity of the switch. Continuity should
be between terminals identified on wiring diagram
when the switch is in heat mode.
Check continuity of the reverse valve coil.
Continuity should be between two lead wires.
If none, check the reverse valve body.
Replace the part which is defective.
Capacitor
Wiring
Refrigerating system
Air filter
Exhaust damper door
Unit undersized
Blower or fan
Copper tubing
Rotary switch.
Wiring
Synchronous motor.
No power
Wiring
Rotary switch
Temperature control position
Thermostat
(Temperature control)
Selector switch position
Selector switch
Reverse valve
Compressor cycles on
overload
Insufficient cooling or
heating
Excessive noise.
Auto air-swing fails.
No heat.
—17—
3.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling or heating.
Ineffective Cooling or Heating
Check of outdoor coil
(heat exchanger) & the fan
operation
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ;
COOLING :   7~10
°
C
HEATING  : 15~17
°
C
Check heat load increase in
cooling operation.
Unexpected residue
Added heat load
Check of inside gas
pressure
Adjusting of refrigerant
charge
Malfunction of compressor
Replacement of
compressor
Check of cold (warm) air cir-
culation for smooth flowing
Dirty indoor coil
(Heat exchanger)
Malfunction of fan
Clogged of air filter
Obstruction at air outlet
Countermeasure against
above trouble.
Check clogging in refrigera-
tion circuit.
Repair clogging in refrigera-
tion circuit.
—18—
Fails to Start
Check of circuit breaker
and fuse.
Gas leakage of feeler bulb
of thermostat
Check of control switch.
Only fan fails to start.
Improper wiring.
Defect of fan motor
capacitor.
Irregular motor resistance
(    ).
Irregular motor insulation
(    ).
Replacement of fan motor
Regular but fails to start
Replacement of compressor
(locking of rotor, metal)
Improper thermostat setting
Loose terminal connection.
Improper wiring
Irregular motor resistance (   )
Irregular motor insulation (   )
Replacement of compressor
(Motor damaged)
Drop of power voltage.
 Check capacitor.
Replacement.
Only compressor fails to
start.
Defect of compressor
capacitor.
Check of power source.
Check of control switch
setting.
Electrical Parts Troubleshooting Guide : LWN1860QHG(QHL)/ LWN2260QHG(QHL)
—19—
Possible Trouble 1
The unit does not operate.
• Check the Fuse.
• Check the wiring diagram.
Is the Trans output power
AC 220V?
Is the Trans output power
about AC 14V?
Is shorted the Trans. output?
Is output Voltage of IC01D
DC 12V?
Is output Voltage of IC02D
DC 5V?
Is the voltage No.20 of Micom
DC 5V?
Exchange Main PCB Ass'y.
Is the 
connection between
Main and Display 
all right?
Is the reset circuit all right?
(The No.16 of
Micom is 5V.)
• Check the Fuse.
• Check the wiring diagram.
• Check the Main 
  PCB pattern.
• Exchange the Trans.
• Exchange D02D~D05D.
• Exchange IC01D.
• Exchange IC02D.
• Exchange IC01A, C02A.
• Connect connector
  exactly.
• Check the PCB 
  pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES