DOWNLOAD LG LWG0760AHG_AHN_AHE Service Manual ↓ Size: 2.87 MB | Pages: 60 in PDF or view online for FREE

Model
LWG0760AHG_AHN_AHE
Pages
60
Size
2.87 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
lwg0760ahg-ahn-ahe.zip
Date

LG LWG0760AHG_AHN_AHE Service Manual ▷ View online

—25—
COMPLAINT
CAUSE
REMEDY
If not running, determine the cause. Replace if required.
Remove the cabinet. inspect the interior surface of the
condenser; if restricted, clean carefully with a vacuum cleaner
(do not damage fins) or brush. Clean the interior base before
reassembling.
If condenser fins are closed over a large area on the coil
surface, head pressures will increase, causing the
compressor to overload. Straighten the fins or replace the
coil.
Test capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean of replace.
Close if open.
Determine if the unit is properly sized for the area to be
cooled.
Check the set screw or clamp. If loose or missing, correct. If
the blower or fan is hitting air guide, rearrange the air
handling parts.
Remove the cabinet carefully and rearrange tubing not to
contact cabinet, compressor, shroud, and barrier.
Check the voltage at outlet. If none, correct.
Check the teminals. If loose, repair or replace.
Check for continuity, refer to the wiring diagram for teminal
identification. Replace the switch if the circuit is open.
Check setting. Turn to warmest position.
Check the position of knob. If not at the warmest setting,
advance knob to this setting. Check continuity of the
thermostat. Check continuity of control by removing lead from
terminal, turn the selector switch to heat, and check between
common terminal and H terminal. (NOTE: Room temperature
should be 30°C(86°F) or lower when testing the temperature
control.) If no continuity exists, replace thermostat.
Selecter switch must be in the HEAT (      ) mode.
Check continuity of the switch. Continuity should be between
terminals identified on wiring diagram when the switch is in
heat mode. 
Check continuity of the reverse valve coil.
Continuity should be between two lead wires.
If none, check the reverse valve body.
Replace the part which is defective.
Fan motor
Condenser air flow
restriction
Condenser fins
(damaged)
Capacitor
Wiring
Refrigerating system
Air filter
Exhaust damper door
Unit undersized
Blower or fan
Copper tubing
No power
Wiring
Rotary switch
Temperature control position
Thermostat
(Temperature control)
Selector switch position
Selector switch
Reverse valve
Compressor cycles on
overload(Cont’d)
Insufficient cooling or
heating
Excessive noise.
No heat.
—17—
4.2 PIPING SYSTEM
Following is a brief description of the important components and their function in the refrigeration system. 
Refer to figure 30 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE 
OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH
SUCTION LIME
COOL LOW PRESSURE VAPOR
COOLED
AIR
COMPLETE LIQUID
BOIL OFF POINT
LIQUID
PRESSURE
DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT
DISCHARGED
AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR
LIQUID PEFRIGERANT
LOW PRESSURE VAPOR
ROOM AIR CONDITIONER
EVAPORATOR COILS
CONDENSER COILS
CYCLE OF REFRIGERATION
CAPILLARY  TUBE
COMPRESSOR
BLOWER
EVAPORATOR  COIL
CONDENSER  COIL
FAN
MOTOR
:  COOLING CYCLE
:  HEATING CYCLE
Figure 30
(COOLING)
—18—
4.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but poor cooling or heating.
Ineffective Cooling or Heating
Check of outdoor coil
(heat exchanger) & the fan
operation
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ;
COOLING :   7~10
°
C
HEATING  : 15~17
°
C
Check heat load increase in
cooling operation.
Unexpected residue
Added heat load
Check of inside gas
pressure
Adjusting of refrigerant
charge
Malfunction of compressor
Replacement of
compressor
Check of cold (warm) air cir-
culation for smooth flowing
Dirty indoor coil
(Heat exchanger)
Malfunction of fan
Clogged of air filter
Obstruction at air outlet
Countermeasure against
above trouble.
Check clogging in refrigera-
tion circuit.
Repair clogging in refrigera-
tion circuit.
—19—
Fails to start.
Check of circuit breaker
and fuse
Gas leakage of feeler bulb
of thermostat
Check of control switch
Only fan fails to start.
Improper wiring
Defect of fan motor
capacitor
Irregular motor resistance
(      )
Irregular motor insulation
(      )
Replacement of fan motor
Regular but fails to start.
Replacement of compressor
(locking of rotor, metal)
Improper thermostat setting
Loose terminal connection.
Improper wiring
Irregular motor resistance (    )
Irregular motor insulation (    )
Replacement of compressor
(Motor damaged)
Drop of power voltage
Capacitor check
Replacement
Only compressor fails to
start.
Defect of compressor
capacitor
Check of power source
Check of control switch
setting
Page of 60
Display

Click on the first or last page to see other LWG0760AHG_AHN_AHE service manuals if exist.