LG LW-C0960HL Service Manual ▷ View online
— Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to
discharge the refrigerant system using a Freon
TM
recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the Freon
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the Freon
TM
. Leave the valve in place after servic-
ing the system.
2. After discharging the unit completely, remove the
desired component, and unbraze the pinch-off
tubes.
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Evacuate as follows.
1) Connect the vacuum pump, as illustrated Figure
18A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns
counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vaccum is obtained. Close
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure
18B.
Open valve C.
Discharge the line at the manifold connection.
18B.
Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.
5. Recharge as follows :
1) Refrigeration cycle systems are charged from
the High-side. If the total charge can not be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in figure
18B.
With valve C open, discharge the hose at the
manifold connection.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, the High-side will not
take it. Close valve A.
5) With the unit running, open valve B and add the
balance of the charge.
a. Do not add the liquid refrigerant to the Low-
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps B and C until the balance of the
d. Repeat steps B and C until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.
12
NOTES
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.
CAUTION
Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capa-
ble of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
ble of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
13
A
B
COMPOUND GAUGE
EVAPORATOR
(LOW PRESSURE SIDE)
(LOW PRESSURE SIDE)
SEE INSETS
BELOW
BELOW
CONDENSER
(HIGH PRESSURE SIDE)
(HIGH PRESSURE SIDE)
MANIFOLD
GAUGE
COMPRESSOR
CAPILLARY TUBE
B
A
EXTERNAL
VACUUM PUMP
VACUUM PUMP
LOW
HI
B
A
C
CHARGING
CYLINDER
CYLINDER
Figure 18A-Pulling Vacuum
(COOLING)
Figure 18B-Charging
4.2 PIPING SYSTEM
Following is a brief description of the important components and their function in what is called the refrigeration
system. Reference should made to Figure 25 to follow the refrigeration cycle and the flow of the refrigerant in the
cooling cycle.
system. Reference should made to Figure 25 to follow the refrigeration cycle and the flow of the refrigerant in the
cooling cycle.
16
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH
AIR FOR REFRIGERANT
PASS THROUGH
SUCTION LINE
COOL LOW PRESSURE VAPOR
COOL LOW PRESSURE VAPOR
COOLED
AIR
AIR
COMPLETE LIQUID
BOIL OFF POINT
BOIL OFF POINT
LIQUID
PRESSURE
DROP
PRESSURE
DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT
DISCHARGED
AIR
DISCHARGED
AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR
LIQUID REFRIGERANT
LOW PRESSURE VAPOR
ROOM AIR CONDITIONER
EVAPORATOR COILS
CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 25
CAPILLARY TUBE
COMPRESSOR
BLOWER
EVAPORATOR COIL
CONDENSER COIL
FAN
MOTOR
: COOLING CYCLE
: HEATING CYCLE
: HEATING CYCLE
(COOLING)
25
COMPLAINT
CAUSE
REMEDY
Check the system for a restriction.
If restricted, clean or replace.
Close if open.
Determine if the unit is properly sized for the
area to be cooled.
area to be cooled.
Check the set screw, or clamp. If loose or missing,
correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.
correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.
Remove the cabinet and carefully rearrange
tubing not to contact cabinet, compressor, shroud,
and barrier.
tubing not to contact cabinet, compressor, shroud,
and barrier.
Check the voltage at outlet. If none, correct.
Check the teminals. If loose, repair or replace.
Check for continuity, refer to the wiring diagram for
teminal identification. Replace the switch if the
circuit is open.
teminal identification. Replace the switch if the
circuit is open.
Check setting. Turn to warmest position.
Check the position of knob. If not at the warmest
setting, advance knob to this setting. Check conti-
nuity of the thermostat. Check continuity of control
by removing lead from terminal, turn the
selector switch to heat, and check between com-
mon terminal and H terminal. (NOTE: Room tem-
perature should be 30°C(86°F) or lower when test-
ing the temperature control.) If no continuity
exists, replace thermostat.
setting, advance knob to this setting. Check conti-
nuity of the thermostat. Check continuity of control
by removing lead from terminal, turn the
selector switch to heat, and check between com-
mon terminal and H terminal. (NOTE: Room tem-
perature should be 30°C(86°F) or lower when test-
ing the temperature control.) If no continuity
exists, replace thermostat.
Selecter switch must be in the " " mode.
Check continuity of the switch. Continuity should
be between terminals identified on wiring diagram
when the switch is in heat mode.
be between terminals identified on wiring diagram
when the switch is in heat mode.
Check continuity of the reverse valve coil.
Continuity should be between two lead wires.
If none, check the reverse valve body.
Replace the part which is defective.
Continuity should be between two lead wires.
If none, check the reverse valve body.
Replace the part which is defective.
Refrigerating system
Air filter
Exhaust damper door
Unit undersized
Blower or fan
Copper tubing
No power
Wiring
Rotary switch
Temperature control position
Thermostat
(Temperature control)
(Temperature control)
Selector switch position
Selector switch
Reverse valve
Insufficient cooling or
heating.
heating.
Excessive noise.
No heat.
Click on the first or last page to see other LW-C0960HL service manuals if exist.