— 18 —
COMPLAINT
CAUSE
REMEDY
If cracked, out of balance, or partially missing,
replace it.
If cracked, out of balance, or partially missing,
replace it.
Tighten it.
If knocking sounds continue when running or loose,
replace the motor. If the motor hums or noise
appears to be internal while running, replace motor.
Check voltage. See the limits on the preceding page.
If not within limits, call an electrician.
Check the wire connections ; if loose, repair of
replace the terminal. If the wires are disconnected,
refer to wiring diagram for identification, and replace
the wires. Check the wire connections ; if not
according to the wiring diagram, correct the
connections.
Check for continuity, refer to the wiring diagram for
terminal identification. Replace the switch if the
circuit is open.
Check the position of knob. If not at the coldest
setting, advance the knob to this setting and restart
the unit.
Check the continuity of the thermostat. Replace the
thermostat if the circuit is open.
Check the capacitor.
Replace if not within 
¡
10% of manufacturer's rating,
replace if shorted, open, or damaged.
Check the compressor for open circuit or graond. If
open or grounded, replace the compressor.
Check the compressor overload if externally
mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool and retest.)
Check the voltage. See the limits on the preceding
page. If voltage is not within these limits, call an
electrician.
Check overload, if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)
Fan
Blower
Loose set screw
Worm bearings
Voltage
Wiring
Rotary
Thermostat
Capacitor (discharge
capacitor before
servicing)
Compressor
Overload
Voltage
Overload
Fan motor noise.
Compressor will not run,
fan motor runs.
Compressor cycles on
overload.
— 19 —
COMPLAINT
CAUSE
REMEDY
If not running, determine the cause. Replace if
required.
Remove the cabinet, inspect the interior surface of
the condenser. If restricted, clean carefully with a
vacuum cleaner (do not damage fins) or brush.
Clean the interior base before re-assembling.
If the condenser fins are closed over a large area on
the coil surface, head pressures will increase,
causing the compressor to cycle.
Straighten the fins or replace the coil.
Test the capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean or replace.
Determine if the unit is properly sized for the area to
be cooled.
Check the set screw, or clamp. If loose or missing,
correct. If the blower or fan is hitting scroll or barrier,
rearrange the air handling parts.
Remove teh cabinet and carefully rearrange the
tubing not to contact the cabinet, compressor,
shroud, and Barrier.
Fan motor
Condenser air flow
restriction
Condenser fins
(damaged)
Capacitor
Wiring
Refrigeration system
Air filter
Unit undersized
Blower or fan
Copper tubing
Compressor cycles on
overload
Insufficient cooling.
Excessive noise.
— 3 —
1. PREFACE
This 
Service Manual
provides various service information, including the mechanical and electrical parts
etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 FEATURES
• DESIGNED FOR COOLING ONLY
• POWERFUL AND INCREDIBLE COOLING
• TOP-DOWN CHASSIS FOR THE SIMPLE INSTALLATION AND SERVICE
• BUILT IN THE ADJUSTABLE THERMOSTAT
• WASHABLE ONE-TOUCH FILTER
• COMPACT SIZE
1.2 SPECIFICATIONS
LW-A0560CL
LW-A0620CL
COOLING CAPACITY (BTU/h)
5,000
5,754
POWER SUPPLY (Phase, V, Hz)
1ø, 220/240V, 50Hz
1ø, 220V, 60Hz
INPUT (W)
610/625
589
OPERATING CURRENT (AMP.)
2.9/2.8
2.8
REFRIGERANT CONTROL
CAPILLARY TUBE
REFRIGERANT CHARGE (R-22)
255g (9.0 oz)
290g (10.2 oz)
INSIDE FAN
BLOWER
OUTSIDE FAN
PROPELLER FAN WITH SLINGER RING
AIR DISCHARGE
2-WAY (RIGHT AND LEFT)
CHASSIS
TOP-DOWN
PROTECTOR
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
TEMPERATURE CONTROL
THERMOSTAT
ROTARY SWITCH
5 STEP (LOW FAN, HIGH-FAN, O(OFF), HIGH COOL, LOW COOL)
FAN MOTOR
6POLES, 25W
• NOTE : Specifications are subject to minor change without notice for further improvement.
5. CIRCUIT DIAGRAM
•  MODEL : LW-A0560CL/A0620CL
— 20 —
PART NO.
POWER CORD ASM
FAN MOTOR
COMPRESSOR
ROTARY SWITCH
THERMOSTAT
CAPACITOR
CONDUCTOR ASM
OVERLOAD PROTECTOR
CONNECTOR ASM
CONNECTOR ASM
CONNECTOR ASM
1
2
3
4
5
6
7
8
9
10
11
1
1
1
1
1
1
1
1
1
1
1
LOCATION
NO.
DESCRIPTION
Q'TY
PER SET
H
L
RD
RD
11
4
9
3
7
5
1
3
2
4
5
6
7
8
2
1
10
6
8
ROTARY  SWITCH
BK          BK
YL
YL
OR(BR)
MOTOR
COMP.
BK(BR)
OR(BR)
POWER INPUT
THERMOSTAT
ROCKER SWITCH
(Plain)
(Ribbed)
WL(BL)
GN(GN/YL)
CAPACITOR
F
R
S
C
C
H
BK
RD
RD
BL
BL
BL
BL
BR
YL
SYNC. M.
BR
BR
BR
OLP
BK
3854AR2330A
WIRING DIAGRAM
M
LW-A0560CL
LW-A0620CL
3H02255E
4681AR2177C
4681AR2177D
5416AR2179E
5416AR2179F
2H00154H
2H01109G
2A00986P
2H01451N
2H01045E
6750U-L011A
6750U-L003A
3H03216G
3H03226D
4933AR3336A
Page of 24
Display

Click on the first or last page to see other LW-A0560CL service manuals if exist.