— 14 —
4.2 PIPING SYSTEM
CONDENSER COILS
FAN
MOTOR
BLOWER
EVAPORTOR
COILS
CAPILLARY
YUBE
Following is a brief description of the important components and their function in what is called the refrigeration
system. Reference should be made to Figure 29 to follow the refrigerating cycle and the flow of the refrigerant in
the cooling cycle.
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE 
SUCTION LIME
COOL LOW PRESSURE VAPOR
COOLED
AIR
COMPLETE LIQUID
BOIL OFF POINT
LIQUID
PRESSURE
DROP
ROOM AIR HEAT LOAD
VAPOR INLET
HOT
DISCHARGED
AIR
LIQUID OUTLET
HIGH PRESSURE VAPOR
LIQUID PEFRIGERANT
LOW PRESSURE VAPOR
ROOM AIR CONITIONER
EVAPORATOR COILS
CONDENSER COILS
CYCLE OF REFRIGERATION
Figure 29
OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH
DISCHARGE
LINE
NOT HIGH PRESSURE
VAPOR
4.3 TROUBLE SHOOTING GUIDE
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective. 
Ñ
15
Ñ
Ineffective Cooling 
Check of outdoor coil
(heat exchanger) & the fan
operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ;
44~50
°
F (7~10
°
C)
Check heat load increase.
Unexpected residue
Overloaded Circuit
Check of inside gas
pressure.
Adjusting of refrigerant
charge.
Malfunction of compressor.
Replacement of
compressor.
Check of cold  air     
dirculation for smooth
 flow.
Dirty indoor coil
(Heat exchanger.)
Malfunction of fan.
Clogged of air filter.
Obstruction at air outlet.
Correct above trouble
Stop of auto air-swing
Check clogging in 
refrigeration circuit.
Repair clogging in 
refrigeration circuit.
— 16 —
Fails to Start
Check of circuit breaker
and fuse.
Gas leakage of feeler bulb
of thermostat.
Check of control switch.
Only fan fails to start.
Improper wiring.
Defect of fan motor
capacitor.
Irregular motor resistance
(      ).
Irregular motor insulation
(      ).
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor
(locking of rotor, metal).
Improper thermostat setting.
Loose terminal connection.
Improper wiring.
Irregular motor resistance (    )
Irregular motor insulation (    )
Replacement of compressor
(Motor damaged).
Drop of power voltage.
Capacitor check.
Replacement.
Only compressor fails to
start.
Defect of compressor
capacitor.
Check of power source.
Check of control switch
setting.
¥
¥
¥
¥
— 17 —
COMPLAINT
CAUSE
REMEDY
Check voltage at outlet. Correct if none.
Check voltage to retary switch. If none, check
power supply cord. Replace cord if circuit is open.
Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if
defective.
Connect wire. Refer to wiring diagram for terminal
identification. Repair or replace loose terminal.
Test capacitor.
Replace if not within ±10% of manufacturer's
rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or blower wheel hitting
scroll. Realign assembly.
Units using slinger ring condenser fans must
have 
1
/
4
to 
5
/
6
inch clearance to the base. If it is
hitting the base, shim up the bottom of the fan
motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not
rotate, replace the motor.
Check voltage. If not within limits, call an
electrician.
Test capacitor.
Check bearings. Does the fan blade rotate freely.
If not, replace fan motor.
Pay attention to any change from high speed to
low speed. If the speed does not change, replace
the motor.
No power
Power supply cord
Rotary switch
Wire disconnected or
connection loose
Capacitor. (Discharge
capacitor before testing.)
Will not rotate
Revolves on overload.
Fan motor will not run.
Fan motor runs.
ROOM AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING 
MINIMUM
MAXIMUM
220V / 240V
198V
264V
220V
198V
242V
Page of 24