–19–
9. Deice Control
• Deicing operation is controlled by timer and sensing the outdoor piping temperature.
• The first deicing starts only when the outdoor pipe temperature falls below -6°C after 45(30) minutes passed
from starting of heating operation.
• Deicing ends after 10(6) minutes passed from starting of deice operation or when the outdoor pipe temperature
rises over 12°C even if before 10(6) minutes.
• The second deicing starts only when the outdoor pipe temperture falls below -6°C after 45(30) minutes passed
from ending of the first deicing.
More than 45(30) minutes 
of heating operation
Within 
10(6) minutes
Deicing
Deicing
ON
OFF
ON
ON
ON
ON
OFF
OFF
COMPRESSOR
4-WAY VALVE
INDOOR FAN
-6
°
C
DEICE ON
12
°
C
DEICE OFF
The outdoor
piping Temp.
ON
More than 45(30) minutes 
of heating operation
HOT-
START
ON
OFF
ON
INDOOR FAN
Low Fan
Low Fan
Intake Air temp.
Setting temp. +1.0˚C
(Compressor ON)
Setting temp. -0.5˚C
(Compressor OFF)
Setting temp.
2min.58sec.
2min.58sec.
10min.
10min.
7min.
Within 7min. Cooling
Cooling
OUTDOOR FAN
COMPRESSOR
Selected
Fan
Selected
Fan
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
10. Soft Dry Operation
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the operation
mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 7min operation OFF. During 10min Dry operation, if the room
temperature falls below compressor OFF temperature, Compressor OFF.
• In micom dehumidify mode, control of fan speed is as following.
12. Protection of the evaporator pipe from frosting
If the te
mperature of the indoor coil is below 0°C after 7 minutes from starting the compressor, the
compressor and the outdoor fan is stopped, and then after 3 minute delay of the compressor and
the temperature of the indoor coil is over 7°C, the compressor and the outdoor fan is reoperated.
Indoor fa
n operates at low speed (comp. OFF) or at selected speed (comp. ON)
13. Inlet grille open
Once the inlet grille is opened during operation of the unit, the unit automatically stops operation and the
lamps will be turned-off. But memorized functions are still available.
When the inlet grille is closed again, the unit become waiting state for operation. From then, the unit can be
operated by forced operation button or Start/Stop button of remote controller.
14. Test Operation
• When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed fan
regardless of room temperature and resets in 18 min.
• During test operation, if remote controller signal is received, the unit operates as remote controller sets.
15. Auto Restarting Operation
• When the power is restored after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance should be on the automatically operates in the mode
on the memory.
• Operation Mode that is kept on the memory
- State of Operation ON/OFF
- Operation Mode/Setting Temp/Selected airflow Speed
- Sleep Timer Mode/Remaining Time of Sleep Timer(unit of hour)
–20–
11. Forced operation
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
• Unit operates in low fan mode for first 15 seconds, then switched to proper operation mode according to
intake Air temperature.
Heat pump Model
Room Temp
24°C
21°C Room Temp 24°C
Room Temp 21°C
Operation Mode
Cooling
Cooling
Soft Dry
Heating
FAN Speed
High
High
Soft Dry Rule
High
Setting Temp.
24°C
22°C
Air Intake Temperature
24°C
Cooling Model
R
Forced
Operation Button
Press the Forced Operation Button.
•Press the Forced Operation Button once
  again to stop operation. 
–21–
Note)
For normal operation after checking by test mode, you should press SW1 nine times for resetting or reconnect
the power cord. 
Self-diagnosis Function
1. Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 mins from starting the compressor, the compressor
and the outdoor fan is stopped, and then after 3 mins delay of the compressor and the temperature of the
indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
2. Thermistor Cut Off or Short 
Cut Off/Short  : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
• Coolling, Soft Dry, Fan, Heating 
• Timer Mode 
• Sleep Mode 
• Hot-start, Deice
Operation Indicator
Timer Indicator 
Sleep Timer Indicator 
Deice Indicator 
• Coolling, Soft Dry, Fan, Heating 
• Timer Mode 
• Sleep Mode 
• Outdoor Unit Operating
Operation Indicator
Timer Indicator 
Sleep Timer Indicator 
Outdoor Unit Operation
1. Heating Model
2. Cooling Model
Display Function 
–21–
Note)
For normal operation after checking by test mode, you should press SW1 nine times for resetting or reconnect
the power cord. 
Self-diagnosis Function
1. Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 mins from starting the compressor, the compressor
and the outdoor fan is stopped, and then after 3 mins delay of the compressor and the temperature of the
indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
2. Thermistor Cut Off or Short 
Cut Off/Short  : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)
• Coolling, Soft Dry, Fan, Heating 
• Timer Mode 
• Sleep Mode 
• Hot-start, Deice
Operation Indicator
Timer Indicator 
Sleep Timer Indicator 
Deice Indicator 
• Coolling, Soft Dry, Fan, Heating 
• Timer Mode 
• Sleep Mode 
• Outdoor Unit Operating
Operation Indicator
Timer Indicator 
Sleep Timer Indicator 
Outdoor Unit Operation
1. Heating Model
2. Cooling Model
Display Function 
Page of 63
Display

LG LV-B1861CL / LV-B1861HL / LV-B1864CL / LV-B1864HL / LV-B2461CL / LV-B2461HL / LV-B2464CL / LV-B2464HL Service Manual ▷ Download