DOWNLOAD LG LS-P1260BB Service Manual ↓ Size: 2.37 MB | Pages: 55 in PDF or view online for FREE

Model
LS-P1260BB
Pages
55
Size
2.37 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-p1260bb.zip
Date

LG LS-P1260BB Service Manual ▷ View online

-5-
Healthy Dehumidification Operation Mode.(       )
Remote Controller
Operation ON/OFF
Reset
Operation Mode Selection
Temperature Setting
Timer Selection
Timer Setting
JET COOL
Timer Cancel
Sleep Operation
Airflow Direction Control
(Cooling 
model only)
(Heating 
model only)
TEMPERATURE
LOW
HIGH
Cooling Operation Mode.(       )
Heating Operation Mode.(       )
Auto Operation Mode.(       )
Fan Operation Mode
Room, Temperature Display
Setting the Time or Timer
ON
OFF
SET
CANCEL
Fan Speed Selection
(Low)
(Med)
(High)
(CHAOS)
: (High:39°C
Low:11°C)
: OFF, ON, OFF
ON
: Cancel Sleep Mode, Timer ON or Timer OFF
: 1, 2, 3, 4, 5, 6, 7, Off Timer
: Fan Operates without cooling or heating.
Cooling
Down to 18°C
Up to 30°C
Heating
Down to 16°C
Up to 30°C
Cycle Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference
: approx. 0°C
Current
: less than 80% of
rated current
Temp. difference
: approx. 8°C
Current
: less than 80% of
rated current
Temp. difference
: less than 8°C
Current
: over the reated
current
Temp. difference
: over 8°C
Operating Current
• All amount of refrigerant leaked
out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
• Excessive amount of refrigerant
• Normal
Notice :
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Notice :
1. The suction pressure is usually 4.5~6.0 kg/cm
2
G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
Defective compressor
Current is low.
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of
operation.
Insufficient amount of
Current is low.
Lower
Higher
refrigerant (Leakage)
Clogging
Current is low.
High
Higher
-41-
-7-
Pipe Hole
Fix Hole
Hanger Hole
H
W
D
MODEL
DIM
Unit
W
mm
570
H
mm
568
D
mm
137
12K Btu Series
Dimensions
(1) Indoor Unit
-8-
(2) Outdoor Unit
W
L2
L3
L1
D
H
L4
L5
Gas side
(3-way valve)
Liquid side
(2-way valve)
MODEL
12K Btu Series
DIM
unit
W
mm
770
H
mm
540
D
mm
245
L1
mm
287
L2
mm
64
L3
mm
518
L4
mm
10
L5
mm
100
Page of 55
Display

Click on the first or last page to see other LS-P1260BB service manuals if exist.