DOWNLOAD LG LS-K1863HL Service Manual ↓ Size: 2.62 MB | Pages: 70 in PDF or view online for FREE

Model
LS-K1863HL
Pages
70
Size
2.62 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner
File
ls-k1863hl.zip
Date

LG LS-K1863HL Service Manual ▷ View online

- 54 -
2. The product is not operate with the remote control.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote control
Cause by the remote control
When the mark(       ) is displayed in LCD screen, replace
battery.
Check the contact of CN-DISP1 connector.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote control.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN DISP1 
: DC +5V
When the detect switch(double key) inside the remote 
control door is fault, it is impossible to operate 
temperature regulating( / ) and wind speed selecting.
Check the connecting circuit between the remote control
MICOM (No.  ) - R17(2
) - IR LED - Q1 - R16(2.2K
).
Check point
• Check the connecting circuit between PIN 
R02L 1k 
- Cø1L(680PF) - MICOM PIN No. 43
• Check Receiver Ass'y
- 55 -
3. Compressor/Outdoor Fan are unable to drive.
Turn on Main Power
Operate "Cooling Mode(     )" by setting the desired temperature of the
remote control is less than one of the indoor temperature by 1°C at least.
When in Air Circulation Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the related circuit of R02H(12.1K), R04H(6.2K), Micom (No.26, 27)
(Indoor unit).
• Check the indoor temperature sensor is disconnected or not(About 10k
/ at 25°C).
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor.
• Check the "open" or "short" of conmecting wires between indoor and
outdoor.
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC220V/240V) is applied to the connecting wire
terminal support transferred to compressor, PWB Ass'y is normal.
• Check the circuit related to the relay.
Check point
COMP ON
COMP OFF
Between Micom(No.
DC5V
DC0V
59) and GND
Between IC01M(No. 15)
Below DC 1V
About DC12V
and GND
(app)
- 56 -
Check the TRIAC high speed operation by Remote control.
(The Indoor Fan Motor is connected)
Turn off Main power
Check the connection of CN-MOTOR
Check the Fan Motor
Check the Fuse(AC250V/T2A)
Turn ON Main Power
Check the related circuit of indoor Fan Motor.
• The pin NO 58 of Micom, and the part for driving TRIAC(the input and
output signal of IC01M, PIN NO 1, 16)
• Check the pattern
• Check the TRIAC
- TRIAC Open: Indoor Fan Motor never operate
- TRIAC short: Indoor Fan Motor always operates in case of ON or OFF.
4. When indoor Fan does not operate.
The voltage of PIN NO 1(blue) and 3(yellow) of CN-MOTOR.
About AC 180V over
About AC 50V over
TRIAC is not damaged
TRIAC Check
- 57 -
6. When Heating does not operate
Operate “Heating Mode(     )” by setting the desired temperature of the
remote control is higher than one of the indoor temperature by 2°C at
least.
In heating Mode, the indoor fan operates in case the pipe temperature
is higher than 28°C.
Turn ON Main Power
• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands 
Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PWB) of CN-U/D Connector
If there are no problems after above checks
• Confirm the assembly conditions that are catching and interfering parts
in the rotation radial of the Vertical Louver
5. When Vertical Louver does not operate.
Check the operating circuit of the Vertical Louver
• Confirm that there is DC +12V between pin
(RED) of CN-U/D and
GND.
• Confirm that there is a soldering short at following terminals.
- Between 
and 
of MICOM
- Between 
,    , 
and 
of IC01M
- Between 
,    , 
and 
of IC01M
60
61
62
63
3
4
5
6
11
12
13
14
Page of 70
Display

Click on the first or last page to see other LS-K1863HL service manuals if exist.