2. Protection of the evaporator pipe from frosting
• If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode, 
➔ 
compressor, outdoor fan are turned off.
• When indoor pipe temp. is 7°C or higher after 2 min pause of compressor 
➔ 
compressor, outdoor fan is turned on according to the condition of the room temperature.
3. Protection of the indoor fan from droplet formation (Enclosure
sweat and condensed disposal test)
• Control condition : The system operates standard operation without this condition as follows.
- Setting temperature <25°C
- Indoor fan speed  
low speed
- Outdoor temperature < 31°C
• Control method
- Operation frequency of compressor must be below 
(refer to the comp. Freq. table)
- The indoor fan operates at medium speed.
Comp. free
Comp. off
0˚C
7˚C
Indoor pipe
temp.
Comp. frequency
4
Comp. free
5˚C
3˚C
4˚C
2˚C
Indoor pipe
temp.
4
-14-
4. Cooling mode operation
• Operating frequency of compressor depend on the difference of the temperature.
(= intake air Temp.- Compressor off Temp.
• Compressor off temp.= setting temp. -0.5°C
on temp. = setting temp. +0.5°C
• If compressor operates at some operating frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp. -0.5°C and setting temp. 
-1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp. -1.0°C.
• Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences
over 2.5°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
¤
¤
¤
¤Œ
¤Ł
¤
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
LS-J0760NL
LS-J0961NL/NT
LS-L1260NL/NT
Comp. Operating frequency
35
38
47
56
66
73
41
53
64
73
80
86
35
38
47
58
66
73
¤
¤Ł
¤Œ
¤
(Fc)
¤
¤
-15-
5. Healthy Dehumidification mode operation
• When the dehumidification operation is set by the remote controller the intake air temperature is detected and
the setting temp. is automatically set according to the intake air temperature.
• Operating frequency of compressor and indoor fan speed.
Temp. differences
32°C 
intake air temp.
26°C 
intake air temp. < 32°C
24°C 
intake air temp.< 26°C
18°C < intake air temp. < 24°C
intake air temp. 
18°C
Comp. Operating frequency
25°C
25°C
intake air temp. -1°C
intake air temp. -0.5°C
18°C
Cooling operation area
Dehumidification
operation area
After 3 min off
OFF instantly
Low
speed
Low
speed
After 5 min OFF
low speed
Setting
speed
+1.0˚C
+0.5˚C
Setting temp. +0˚C
-1.0˚C
-2.0˚C
Operating frequency of compressor
Indoor fan speed
43Hz
38Hz
35Hz
-16-
6. Heating mode operation
• Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
• Compressor off temp. = setting temp.+3.0°C
on temp. = setting temp.
• If compressor operates at some operation frequency, the operating frequency of  compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature reaches +3°C above the setting temperature.
• Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 26°C
off: indoor pipe temp. < 37°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
over 3.0°C
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
§
¤ı
¤
¤
¤º
¤Ø
¤
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Model
LS-J0760NL
LS-J0961NL/NT
LS-L1260NL/NT
Comp. Operating frequency
35
43
53
66
78
83
92
40
56
68
78
90
96
105
43
47
53
64
73
83
90
¤