-52-
Turn on the main power.
When in air circulation mode, compressor/outdoor fan is stopped.
Turn off main power.
Check the electrical wiring diagram of Outdoor side.
Check the open or short of connecting wires between Indoor and Outdoor.
Check the sensor for Indoor temperature is attatched as close as to be effected by the
themperature of Heat Exchange (EVA.)
When the sensor circuit for Indoor temperature and connector are in bad connection or are
not engaged, Compressor/Outdoor fan is stopped.
• Check the related circuit of R03H(12.1K), R01H(1K), R04H(6.2K), R02H(1K), C01H(104),
C02H(104), Micom(62,63).
• Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).
Check the Relay(RY-PWR) for driving Compressor.
• Check the voltage between brown and blue cable of terminal to connect the Outdoor
(About AC220V / 240V).
• Check the related circuit of relay in Outdoor PCB Ass'y.
Operate Cooling Mode by setting the disired temperature of the remote controller is less
than one of the Indoor temperature by 1°C at least.
The Compressor/Outdoor Fan are unable to drive.
Trouble 3
Check Point
Between Micom(No. 19) and
GND
DC 5V
DC 0V
DC 12V
DC 1V
Between IC01M(No. 12) and
GND
Comp. ON
Comp. OFF
-53-
When indoor Fan does not operate.
Trouble 4
Check the SSR high speed operation by remote control.
(the Indoor Fan Motor is connected)
Turn off main power.
Check the connection of CN-FAN.
Check the Fan Motor.
Check the Fuse(AC250V, T3.15A).
Turn on the main power
Check the related circuit of indoor Fan Motor.
• The pin No.9 of micom and the part for driving SSR.
• Check the related pattern.
• Check the SSR.
- SSR Open: Indoor Fan Motor never operate.
- SSR short: Indoor Fan Motor always operates in case of ON or OFF.
The voltage of Pin No 1(orange) and 3(black) of CN-FAN.
About AC 180V over
About AC 50V over
SSR is not damaged
Check SSR
-54-
• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands
Normal
• Check the connecting condition of CN-UP Connector
• Check the soldering condition(on PCB) of CN-UP Connector
Check the operating circuit of the vertical louver
• Confirm that there is DC +12V between pin
of CN-UP and GND.
• Confirm that there is a soldering short at following terminals.
- Between
,
,
and
of MICOM
- Between
,
and
of IC4
- Between
14
,
15
and
16
of IC4
When the vertical louver does not operate.
Trouble 5
If there are no problems after above checks.
• Confirm the assembly condition that are catching and interfering parts in the rotation
radial of the vertical louver
-55-
Does the Operating LED of indoor unit blink
when Operation's ON?
Is the Connection between indoor power
relay Pin
and terminal block No. 1 right?
Refer to the self-diagnosis function.
The Outdoor Unit does not operate at all.
Trouble 6
YES
Check the connecting state of connector
NO
NO
Is the connection of cable between indoor
and outdoor unit right?
Indoor
Outdoor
1(Brown)
1(Brown)
2(Blue)
2(Blue)
3(Green/YL)
3(Green/YL)
4(Red)
4(Red)
NO
YES
Is the voltage of CN-POWER
,
in
outdoor PCB Ass'y about AC220V / 240V
when Operation's ON?
Check the Fuse of Outdoor PCB Ass'y.
NO
YES
Is the voltage of CN-AC
,
in outdoor
PCB Ass'y about AC220V / 240V?
Check the PTC and RY-PWR.
NO
YES
Is the Bridge Diode(DB01Z) right?
Replace the Bridge Diode.
NO
YES
Replace the PCB Ass'y.
NO