11. Auto restarting operation
• When the power is restarted after a sudden power failure while in appliance operation, the mode before the
power failure is kept on the memory and the appliance automatically operates in the mode on the memory.
• The slide switch on the indoor unit of the appliance should be on the AUTO RESTART position in order that
the Auto restarting operation is available.
• Operation mode that is kept on the memory
— State of operation ON/OFF
— Operation mode/setting temp./selected airflow speed
— Sleep timer mode/remaining time of sleep timer
• If no input by the remote control or no switching of the slide
switch within 7 hours after the appliance operates by the
Auto restarting operation, the appliance is forced to stop
at the moment of 7 hr elapse.
12. Forced operation
For Cooling Only Model
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• When the power is supplied while the slide switch is on the forced operation position, or when the slide switch
position is switched from the Auto Restarting position or switched from the remote control position to the
forced operation position while the power is on, the forced operation is carried out.
• When the slide switch position is switched from the forced operation position to the Auto Restarting position or
the remote control position, the forced operation is canceled and the appliance stops operating.
• The forced operation is carried out in cooling mode with the setting temperature 22°C and the high speed of
airflow.
• While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to
indicate the forced operation.
For Heat Pump Model
• To operate the appliance by force in case that the remote control is lost, the forced operation selection switch
is on the main unit of the appliance to operate the appliance in the standard conditions.
• The operation condition is set according to the outdoor temp. and intake air temperature as follows.
-19-
Outdoor temp.
over 24°C
21~24°C
18~21°C
below 18°C
Setting temp.
22°C
23°C
23°C
24°C
24°C
Setting speed of
indoor fan
High speed
Operating Mode
Cooling
Healthy Dehumidification
Intake air temp.
25°C
Dehumidification
Intake air temp. < 25°C
Heating
Heating
Slide Switch
FORCED
OPERATION
AUTO
RESTART
REMOTE
CONTROL
13. Remote Control Operation
• When the remote control is selected by the slide switch on the main unit, the appliance operates according to
the input by the remote control.
14. Power relay control
• Power relay turns on 1 second later after the power is input to the outdoor unit.
• Control sequence : power on
PTC operating
power relay on
15. Timer Opeation
On-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance starts to operate.
• The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached.
• If the appliance is operating at the time set by the timer, the operation continues.
Off-Timer Operation
• When the set time is reached after the time is input by the remote control, the appliance stops operating.
• The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached.
• If the appliance is on pause at the time set by the timer, the pause continues.
Off-Timer <=> On-Timer Operation
• When the set time is reached after the on/off time is input by the remote control, the on/off-timer operation is
carried out according to the set time.
16. Protection from total current control
CT1 control
• If the operating current reaches I1, the operating frequency of the compressor decrease.
• After decreasing the operating frequency by 1step, if operating current is below I1 for 24 seconds
continuously, the operating frequency of compressor increase by 1step.
CT2 control
• If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the
compressor restart again.
• If CT2 occurs twice within 1hour, the appliance turn off and display ERROR CODE 7.
I1:Current of operating frequency down
I2: Current of compressor cut off
-20-
Model
LS-J0960NL/NT
Cooling
Heating
8.5A
10A
13.5A
8.5A
10A
13.5A
Cooling
Heating
9.5A
11A
13.5A
9A
10.5A
13.5A
Operating mode
below 38°C
(outdoor temp.)
I1
I2
I1
I2
over 38°C
(outdoor temp.)
LS-F1260NL/NT
Condition
17. Protection from DC Peak Current
DC Peak Current Error by a fault signal of IPM
• If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.
• If DC PEAK occurs 3 times within 1 hour, the appliance turns off and display ERROR CODE
.
DC Peak Current Error by the compressor lock
• If the DC LINK voltage below DC 350V occurs 5 times within 1 hour while the compressor is operating, the
appliance turns off and display ERROR CODE
.
DC Peak Current Error by the Outdoor Fan Lock
• If it’s 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the copressor is
operating, the appliance turns off and display ERROR CODE
.
18. Portection from overheating of compressor
• If the temperature of the dome of compressor reaches over 130°C or below -30°C the compressor stop
instantly.
• It will be limited the compressor operating frequency according to the compressor dome TH.(Refer to below
Fig.)
-21-
130˚C
113˚C
105˚C
98˚C
-13˚C
-30˚C
101˚C
93˚C
35Hz
OFF
OFF
0Hz
43Hz
47Hz
Setting frequency
18 . Defrosting control
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing,
reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrosting control is available 45 minutes later since heating cycle started and the pipe temperature of
outdoor unit reaches below -6°C.
-22-
45 min
Setting frequency
Setting speed
Setting
speed
OFF
OFF
ON
OFF
10 sec
OFF(Cooling cycle)
Setting
frequency
30 sec
Fc-1 step
Operating
frequency
of compressor
4 Way valve
Outdoor fan
Indoor fan
Defrost LED
Fc-1
Fc+1
OFF
ON
ON(Heating cycle)
ON
ON
Low
(FhMAX-1 or FhMAX-2)
30 sec
30 sec
8 min or
over 25˚C
30 sec
1 min
Page of 68