5. Auto Operation (Fuzzy Operation)
• The operation procedure is as following. (Cooling & Heating Model)
❋ 
If initial mode is decided, that mode
is continued without the room temper-
ature changing.
❋ 
For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.
■ 
Auto Operation(Fuzzy Operation) for Cooling (Cooling only Model)
- 15 -
Press Start/Stop Button
Select Auto Operation (Fuzzy Operation) Mode
Check the Room temperature
Operation mode
Indoor fan speed
are automatically decided by Fuzzy rule.
Setting temperature
Intake-air
temperature
Operation Mode
Over
below
21°C
24°C
Soft Dry
below 21°C
Heating
Over 24°C
Cooling
~
INTAKE-AIR TEMP.
SETTING TEMP. +0.5°C
(Compressor OFF)
SETTING TEMP. -0.5°C
(Compressor ON)
COMPRESSOR
ON
OFF
ON
OFF
INDOOR FAN SPEED
Fuzzy Speed
Intake-air Temperature
Setting Temperature
Over 26°C
25°C
Over 24°C~below 26°C
Intake air -1°C
Over 22°C~below 24°C
Intake air -0.5°C
Over 20°C~below 22°C
Intake air temperature
below 20°C
20°C
Over 20°C~below 30°C
Fuzzy control
below 20°C
20°C
over 30°C
30°C
Operation Condition
When Auto Operation
initial start
Controlled by
Fuzzy logic
In this mode,
when pressing
the vertical air
direction control
button, louvers
moves to 1/f
rhythm (refer to
page 17)
Fan Speed
Air DirectionControl
When pressing room
temperature setting 
button during Auto
Operation
■ 
Auto Operation (Fuzzy Operation) for Soft Dry
• The Setting temperature will be same that of the auto operation for cooling.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperture -0.5°C
■ 
Auto Operation (Fuzzy Operation) for Heating
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +3°C
- 16 -
Intake Air temp.
Below 20°C
Over 20°C~below 21°C
Over 30°C
Setting temp.
20°C
Intake air temperature +0.5°C
30°C
• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, 
louver moves as following cycle.
MODE0
MODE1
MODE2
MODE3
End
Start
MODE9
(CLOSED)
MODE4
MODE5
MODE6
- 17 -
6.Natural Wind by CHAOS logic
There are common rules in the irregular changes amid the breeze of highlands and valleys, the sound of
streams, the songs of birds in the forest and brain waves of relaxation.
Mmm.... the breath-taking and touchy feeling of wind from the deep mountains and dark valleys.
Through analysis in its chaos simulator, Goldstar had successfully created such a feeling of freshness and
serenity by analyzing the frequency of natural wind.
Generally natural wind has the following character (frequency-Magnitude), for example dark valley, sea, mountain
wind.
So as to make a similar Natural wind function, Indoor fan speed is shifted to high from low or reversely according
to the CHAOS logic.
Natural wind function
Magnitude
Frequency(Hz)
- 18 -
7.Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol-
lowing.
INTAKE AIR TEMP.
SETTING TEMP. +3°C
(Compressor OFF)
SETTING TEMP.
(Compressor ON)
Selecting
fan speed
Selecting
fan speed
A
B
A
minimum
1 min
minimum
10sec.
minimum
10sec.
COMPRESSOR
ON
OFF
ON
OFF
• A point; While the indoor Heat-Exchanger temperature is higher than 35°C fan operates at low speed, when it
becomes lower than 35°C fan stops.
• B point; When the indoor Heat-Exchanger temperature is higher than 28°C, fan operates at selected fan
speed.
INDOOR FAN SPEED
LOW
OFF
LOW
LOW
OFF
Page of 105