- 17 -
6.Natural Wind by CHAOS logic
There are common rules in the irregular changes amid the breeze of highlands and valleys, the sound of
streams, the songs of birds in the forest and brain waves of relaxation.
Mmm.... the breath-taking and touchy feeling of wind from the deep mountains and dark valleys.
Through analysis in its chaos simulator, Goldstar had successfully created such a feeling of freshness and
serenity by analyzing the frequency of natural wind.
Generally natural wind has the following character (frequency-Magnitude), for example dark valley, sea, mountain
wind.
So as to make a similar Natural wind function, Indoor fan speed is shifted to high from low or reversely according
to the CHAOS logic.
Natural wind function
Magnitude
Frequency(Hz)
- 18 -
7.Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol-
lowing.
INTAKE AIR TEMP.
SETTING TEMP. +3°C
(Compressor OFF)
SETTING TEMP.
(Compressor ON)
Selecting
fan speed
Selecting
fan speed
A
B
A
minimum
1 min
minimum
10sec.
minimum
10sec.
COMPRESSOR
ON
OFF
ON
OFF
• A point; While the indoor Heat-Exchanger temperature is higher than 35°C fan operates at low speed, when it
becomes lower than 35°C fan stops.
• B point; When the indoor Heat-Exchanger temperature is higher than 28°C, fan operates at selected fan
speed.
INDOOR FAN SPEED
LOW
OFF
LOW
LOW
OFF
- 19 -
8.Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°C.
• During heating operation, if piping temperatures falls below 26°C fan stops.
• The operation diagram is as following.
9.Defrost Control
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 60 minutes passed from
starting of heating operation and more than 10 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation or when the outdoor pipe temperature
rises over 12°C even if before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 60 minutes passed from
ending of the first defrost and more than 10 minutes operation of compressor.
OUTDOOR
PIPE TEMP.
More than 60 minutes of
heating operation
More than 10 min.
running of compressor
More than 60 minutes of
heating operation
More than 10 min.
running of compressor
Within 
12minutes
Defrost
Defrost
HOT-
START
12°C
(DEFROST OFF)
-6°C
(DEFROST ON)
INDOOR FAN
ON
OFF
ON
OFF
COMPRESSOR
ON
ON
ON
ON
4-WAY VALVE
ON
OFF
ON 
OFF
INDOOR PIPE
TEMP.
28°C
26°C
1min
OFF
OFF
LOW
Selecting
fan speed
INDOOR FAN
SPEED
COMPRESSOR
ON
Functions ...................................................................................................................................... 3
Product Specifications  ............................................................................................................... 5
Dimensions................................................................................................................................... 6
Refrigeration Cycle Diagram....................................................................................................... 8
Pipe length and the elevation ..................................................................................................... 9
Wiring Diagram .......................................................................................................................... 10
Operation Details ....................................................................................................................... 13
Display Function ........................................................................................................................ 22
Self-diagnosis Function ............................................................................................................ 22
Installation .................................................................................................................................. 23
Operation .................................................................................................................................... 38
Disassembly of the parts (Indoor unit) .................................................................................... 40
2-way, 3-way Valve ..................................................................................................................... 43
Cycle Troubleshooting Guide ................................................................................................... 50
Electronic Parts Troubleshooting Guide ................................................................................. 51
Electronic Control Device ......................................................................................................... 62
Schematic Diagram.................................................................................................................... 66
Exploded View & Replacement Parts List ............................................................................... 68
- 2 -