13. Test Operation
•  When pressing forced operation switch about 3 seconds, the unit operates in cooling mode at high speed fan
regardless of room temperature and resets in 18 min.
•  During test operation, if remote controller signal is received, the unit operates as remote controller sets.
Test Mode
Test operation will be setted by pushing the “Testkey” in the main P.C.B ASM. Each test operation by pushing
Count of “Testkey” is as well as the following.
(In the case of power cord is plugged and Air Conditioner is not operating.)
1) Indoor
• 1 Time push  : Ignore communication error.
• 2 Times push  : Shorten the proceeding time. (1min  
¡
1sec)
• 3 Times push  : Shorten the proceeding time. (1hour 
¡
1sec)
• 4 Times push  : All LED ON
• 5 Times push  : Indoor Fan Check. (Fan : Hi)
Up/Down Step Motor ON.
• 6 Times push  : Right Step Motor ON. (Not on alll Models)
• 7 Times push  : Left Step Motor ON. (Not on all Models)
• 8 Times push  : Negative Ion ON. (Not on all Models)
• 9 Times push  : Reset.
Note)
For normal operation after checking by test mode, you should press “Testkey” nine times for resetting or recon-
nect the power cord.
2) Outdoor
• 1 Time push  : Ignore Communication error.
• 2 Times push  : Comp. ON,
Outdoor Fan ON
Reversing Valve Coil ON
• 3 Times push  : Reversing Valve Coil OFF
Comp. ON
Outdoor Fan ON
• 4 Times push  : Comp. OFF
Outdoor Fan ON
• 5 Times push  : Reset.
Note)
For normal operation afterchecking by test mode, you should press “Testkey” five times for resetting or recon-
nect the power cord.
ƒ¡
26
ƒ¡
¡Æ
Cooling Mode with the Sleep Mode
ƒU
The setting temperature will be raised by 1
¡
30minutes  later and by 2
¡
1 hour later.
ƒU
The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
¡Æ
Heating Mode with the Sleep Mode. 
ƒU
The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
Intake Air temp.                   
COMP. ON
(SET TEMP.+0.5
¡
COMP. OFF
(SET TEMP. -0.5
¡
)
Morethan
More than
3 minutes
3 minutes
INDOOR FAN
Low
Low
Low
Low
Low
COMPRESSOR
ON
OFF
ON 
OFF
ON
30 minutes
30 minutes
1
¡
1
¡
ƒ¡
18
ƒ¡
Setting Temp. +3
¡
(Compressor OFF) 
Setting Temp.
(Compressor ON)
Indoor Fan
Med.
Med.
Med.
Med.
Med.
Med.
Compressor
ON
OFF
ON
OFF
ON
OFF
5. Auto Operation 
ƒU
The operation procedure is as following. (Cooling & Heating Model)
ƒN
If initial mode is decided, that mode is continued without the room temperature changing.
ƒN
For cooling operation mode over 24°C setting temperature and fan speed are same as cooling only model.
ƒ
ƒU
U
Auto Operation for Cooling. (Cooling only Model)
ƒ¡
19
ƒ¡
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
Operation mode
Indoor fan speed
are automatically decided by Fuzzy rule.
Setting temperature
Intake-air
temperature
Operation Mode
Heating
Soft Dry 
Cooling
Operation Condition 
Intake-air Temperature
Setting temperature
Fan speed 
Air Direction Control
Over 26°C
25°C
Over 24
¡
~below 26°C
Intake air -1°C
Over 22
¡
~below 24°C
Intake air -0.5°C
Over 20°C~below 22°C intake air temperture
below 20°C
20°C
Over 20°C~below 30°C
Fuzzy control
below  20°C
20°C
over 30°C
30°C
below   21
¡
below   
24
¡
~
Over   24
¡
Over   
21
¡
When Auto Operation
initial start
When pressing room  temp-
erature setting button 
during Auto Operation
Controlled
by Fuzzy logic
In this mode, when
pressing the verti-
cal air diretion con-
trol.
Button, louvers
moves to 1/f
rhythm (refer to
page 17)
Intake-Air temp 
Setting Temp. +0.5
¡
(Compressor OFF) 
Setting Temp.-0.5
¡
(Compressor ON)
Indoor Fan
Compressor
ON
ON
OFF
OFF
Fuzzy Speed
ƒ
ƒU
U
Auto Operation for Soft Dry.
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1
¡
- Compressor OFF temperature; Setting temperature -0.5
¡
ƒ
ƒU
U
Auto Operation for Heating.
- Compressor ON temperature; Setting temperature 
- Compressor OFF temperature; Setting temperature +3
¡
ƒU
1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button,
louver moves as following cycle.
ƒ¡
20
ƒ¡
Intake Air temp.
below 20°C 
over 20
¡
~below 21°C
Setting temp.
20°C 
Intake air temp. +0.5°C
21.5¡
20¡
20¡
Intake-Air temp.
Setting temp.
20.5 ¡
21 ¡
MODE0
MODE1
MODE2
MODE3
MODE4
MODE5
MODE6
MODE9
(CLOSED)
End
Start
Page of 71
Display