Service Manual  5
Safety Precautions  
Installation
Do not open the inlet grill of the product during
operation. (Do not touch the electrostatic filter,
if the unit is so equipped.)
• There is risk of physical injury, electric shock, or prod-
uct failure.
Be cautious that water could not enter the
product.
• There is risk of fire, electric shock, or product damage.
Always check for gas (refrigerant) leakage after
installation or repair of product.
• Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is
drained away properly.
• A bad connection may cause water leakage.
Do not store or use flammable gas or com-
bustibles near the product.
• There is risk of fire or failure of product.
If strange sounds, or small or smoke comes
from product. Turn the breaker off or discon-
nect the power supply cable.
• There is risk of electric shock or fire.
Gasolin
50 Floor Standing Type Air Conditioner
Troubleshooting guide
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
No cooling and heating operation performed
1) Both the blower and the compressor do not work
NAME PLATE RATING
MINIMUM
MAXIMUM
380 V
342 V
418 V
220 V
198 V
242 V
380 - 415 V
342 V
456 V
2) Only blowers do not work
WHAT TROUBLED 
COMPLAINTS
HOW TO CHECK
REMEDY
Other parts than the unit
Magnetic switch for com-
pressor & fan motor 
Operating switch
Protection devices
Electric supply interrupted
Defective power wiring
Cut of power fuse
Too low voltage
Control point is on condi-
tion of "OFF" due to trou-
ble.
Troubled or defective
contactor
Opened the contact point
with trouble
Measure it with a tester in
case that the same
power source is supplied
to other equipment than
the unit, what and where
trouble can be discov-
ered by checking the
operation of other equip-
ment.
Measure it with a tester.
Make short-circuit, then
measure it with a tester. 
Check it with the eyes or
tester.
Check it with the eyes or
tester.
Repair a switch box and
is relative instrument.
Replacement of fuse
Request a power 
supplier to repair.
Check the power source.
Use a thick cable if nec-
essary.
Replace it if necessary.
Repair or replace it.
Discover the trouble
cause and push the rest
button.
WHAT TROUBLED 
COMPLAINTS
HOW TO CHECK
REMEDY
Air volume change over
switch
Capacitor
Troubled or defective 
contact point
Defected
Check it with the eyes or a
tester
Check it with a tester.
Repair or replace it.
Replace it.
Service Manual  51
Troubleshooting guide
3) Only outdoor fan does not work
WHAT TROUBLED 
COMPLAINTS
HOW TO CHECK
REMEDY
Motor
Electric Wiring
Over-heated
Layer short
Open wire on operation
Short circuited on 
operation
Check how it is insulated.
Check it with a tester.
Repair or replace it.
Rewiring or repair.
4) Only compressor does not work
WHAT TROUBLED 
COMPLAINTS
HOW TO CHECK
REMEDY
Magnetic switch for
compressor motor
Compressor motor
Compressor
High pressure switch
Electric circuit
Defective contact, 
magnetic coil troubled.
Troubled over-heated 
(layer short)
Troubled or over-heated 
(lock)
Troubled or defective 
contact or operating
Defective connection or
disconnection of the circuit
for compressor.
Check it with the eyes on
with a tester.
Check how it is insulated.
Groaned noise of motor
Check it with a tester.
Check it with a tester.
Repair or replace it.
Replace or repair the
compressor.
Repair or replace it.
Replace it if necessary.
Rewiring or push reset
button.
52 Floor Standing Type Air Conditioner
Troubleshooting guide
Note: Use an appropriate measuring instrument for readjustment.
*1:  Check the High-pressure switch indication.
*2: Check the Low- pressure switch indication.
The Units discontinue after the operation started
WHAT TROUBLED 
COMPLAINTS
HOW TO CHECK
REMEDY
Other parts than the unit
Outdoor coil
In-condensable gas
blended.
High pressure switch
Refrigerant
Outdoor Fan
Improper opening of the
service valves in the
refrigerant line
Coil is dirty *1
Air intruded into the 
refrigerant pipe line *1
Improper adjustment
A shortage of refrigerant
amount. * 2
Reverse rotation of fan 
Obstacle
Air short circuit *1
Checking
Checking
In the event that 
difference between the
saturating temperature
corresponding to high
pressure and the 
temperature of air 
discharged from the 
outdoor coil is more than
15°C, incondensable gas
may be blended.
Check it with a pressure
gauge.
Confirm the wind blowing
out.
Check it with eyes.
Open it properly
Wash it by means of
something like chemical
washing.
Extract air by vacuum
pump, then recharge the
refrigerant.
Readjust it to normal
operating pressure. 
(Note)
Don't alternate the 
specified adjusting 
pressure. If the adjusted
pressure exceeds the
specified range, it will
cause a great accident.
Recharge the 
refrigerant. Repair the
spot where it leaks.
If reversed, connect
interchanged wires to
each terminal. 
Power wirings.