7. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as
following.
8. Hot- Start Control
• The indoor fan stops until the evaporator piping temperature will be reached at 28°C.(BY TEMPERATURE)
• The operation diagram is as following.
- 17 -
A
A
B
Intake Air temp.
SETTING TEMP. +3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
Selecting
fan speed
Selecting
fan speed
minimum
10sec.
minimum
10sec.
minimum
10sec.
Hot 
Start
COMPRESSOR
ON
OFF
ON
OFF
• A point; The indoor pipe temperature to be 35°C
The indoor fan operates minimum 10sec. even if falls lower than 35°C
• B point; The indoor pipe temperature to be 35°C
The indoor fan operates minimum 10sec. even if falls lower than 35°C
INDOOR FAN
OFF
LOW
LOW
OFF
LOW
OFF
ON
PIPING
TEMP 28°C
60sec.
INDOOR
FAN
OFF
LOW
SELECTING
FAN SPEED
COMPRESSOR
ON
(HOT-START BY TEMPERATURE)
9. Deice Control
• Deicing operation is controlled by timer and sensing the indoor pipe temperature.
• Deicing operation checks the indoor pipe temperature and Intake-air temperature at 25 minutes and 60 min-
utes on starting of heating operation, and discriminates by temperature difference.
• When the heating operation passed 25 minutes, the temperature (
T1= TE1-TR1) is checked and memo-
rized with checking the indoor pipe temperature (TE1) and the indoor Intake-air temperature (TR1).
• When the heating operation passed 60 minutes, deicing operation checks the indoor pipe temperature
(TE2) and the indoor Intake-air temperature (TR2), and checks the temperature difference (
T2=TE2-TR2)
and the temperature difference 
Td(=
T1-
T2) of 
T1, 
T2.
If the temperature difference (
Td) become more than the option temperature, deicing operation starts.
• At that time, deicing operation time is decided.
• The deicing operation time stops after deicing operation started.
• If deicing operation start, above heating operation time is reset, so if deicing operation is finished, the heat-
ing operation time is recounted.
• The deicing time and the operation diagram are as following.
- 18 -
TE1
TR1
TE2
TR2
TR1
TE1
T1
T2
T1
INDOOR FAN
ON
OFF
ON After HOT-START finished
OUTDOOR FAN
ON
OFF
ON
COMPRESSOR
ON
ON
ON
4-WAY VALVE
ON
OFF
ON
Deicing
TEMP. °C
25MINS
Heating
25MINS
Heating
60 minutes
Heating
Pipe Temp. 
Intake Air 
Temp.
Td(=
T1-
T2)
Over 3.5°C
3.0~3.5°C
2.5~3.0°C
2.0~2.5°C
below 2.0°C
Deicing Time
12 mins
11 mins
10 mins
9 mins
Heating Operation
10. Soft Dry Operation
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the com-
pressor OFF temperature is the setting temperature minus 0.5°C.
• When the room temperature rises over the compressor ON temperature, the operation mode is switched to
the cooling mode.
• When the room temperature falls between the compressor ON temperature and OFF temperature, the
operation mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry Operation, 5.5min operation OFF, 1.5min. only fan operation repeat.
During 10min Dry operation, even if the room temperature falls below compressor OFF temperature,
10min(MAX) Compressor ON from starting of Dry operation which includes 4 min. Compressor ON opera-
tion below the comperssor OFF temperature.
• In micom dehumidify mode, control of fan speed is as following.
11. Forced Operation.
• If you lose wireless remote controller, you can operate the unit with forced operation switch.
• The standard conditions are as following.
- 19 -
Heat pump Model
Room Temp 
24°C
21°C 
Room Temp < 24°C
Room temp < 21°C
Cooling
Soft Dry 
Heating
High
Low
High
24°C
Room Temp.
22°C
Cooling Model
Operation Mode
Cooling
FAN Speed
High
Setting Temp.
24°C
ROOM TEMP.
SETTING TEMP. +1°C
(COMP. ON)
SETTING TEMP. 
(COMP. OFF)
Selecting
fan speed
Operation
Cooling
Dry operation
maximum
4 minutes
maximum
10 minutes
5.5 minutes
1.5 minutes
10 minutes
1 minute
2 minutes
COMPRESSOR
ON
OFF
ON
OFF
ON
INDOOR FAN
OFF
LOW
LOW
OFF
LOW
LOW
• Cooling, Soft Dry, Heating
• Timer Mode
• Sleep Mode
• Hot-start, Deice
Note: For normal operation after checking by test mode, you should press SW1 nine times for resetting or
reconnect the power cord.
1. Protection of the evaporator pipe from frosting
If the temperature of the indoor pipe is below 0°C after 7 mins from starting the compressor, the compressor
and the outdoor fan is stopped, and then after 3 mins delay of the compressor and the temperature of the
indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.
2. Thermistor Cut Off or Short
Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF).
- 20 -
Display Function
Self-diagnosis Function
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Deice Indicator
: Heating Model only