Dimensions
–7–
W
H
D
(1) Indoor Unit
MODEL
DIM
W(mm)
880
880
1180
H(mm)
260
260
298
D(mm)
450
450
450
18K
24K
36K
(2) Outdoor Unit
–8–
H
W
D
(18K/24K/36K)
MODEL
DIM
W(mm)
870
870
870
H(mm)
655
655
800
D(mm)
320
320
320
18K
24K
36K
Refrigeration Cycle Diagram
• HEAT PUMP (LB-H1860HL / LB-H2460HL / LB-G3680HL)
• Rated performance for refrigerant line length of: 7.5m
• If 18K Model is installed at a distance of 15m, 255g of refrigerant should be added (15-7.5)x30g=225g
• If 18K Model is installed at a distance of 15m, 255g of refrigerant should be added (15-7.5)x30g=225g
–9–
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
EXCHANGER
HEAT
EXCHANGER
EXCHANGER
COMPRESSOR
GAS SIDE
LIQUID SIDE
COOLING
HEATING
REVERSING
VALVE
VALVE
CAPILLARY TUBE
LB-H1860HL
5/8"
1/4"
7.5
50
5
30
30
LB-H2460HL
5/8"
1/4"
7.5
50
5
30
35
LB-G3680HL
5/8"
1/4"
7.5
50
5
30
45
*Additional
refrigerant
(g/m)
Pipe size(Diameter: ø)
Piping length(m)
Elevation(m)
MODEL
Gas
Liquid
Rated
Max.
Rated
Max.
–10–
• COOLING ONLY (LB-H1860CL / LB-H2460CL / LB-G3680CL)
• Rated performance for refrigerant line length of: .7.5m
• If 18K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5)x30g=225g
• If 18K Model is installed at a distance of 15m, 225g of refrigerant should be added (15-7.5)x30g=225g
INDOOR UNIT
OUTDOOR UNIT
HEAT
EXCHANGER
(CONDENSER)
EXCHANGER
(CONDENSER)
HEAT
EXCHANGER
(CONDENSER)
EXCHANGER
(CONDENSER)
COMPRESSOR
GAS SIDE
LIQUID SIDE
CAPILLARY TUBE
LB-H1860CL
5/8"
1/4"
7.5
50
5
30
30
LB-H2460CL
5/8"
1/4"
7.5
50
5
30
35
LB-G3680CL
5/8"
1/4"
7.5
50
5
30
45
*Additional
refrigerant
(g/m)
Pipe size(Diameter: ø)
Piping length(m)
Elevation(m)
MODEL
Gas
Liquid
Rated
Max.
Rated
Max.