–29–
2) Group Control(Optional Wiring)
• You can use a group control operation after connecting the brown and yellow wire of each  air-conditioner.
• Remove the resistor "OP 7" in remote controller.
• It operates maximum 16 Units by only one Wired Remote Controller,
and each Unit starts sequentially to prevent overcurrent.
Wiring design
Features
• Use Only One Wired Remote Controller with several air conditioners(max. 16 Units)
• Random starting to prevent overcurrent.
Operation unit
ZONE
1 2 3 4
Humidify
JET
AUTO
AUTO SWING
OPERATION
FAN SPEED
Program set
SUB FUNCTION
SET TEMP
Room Temp
HI
MED
LO
Heater
Defrost
Filter
Preheat
Out door
Time
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
Indoor Unit 1
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Terminal(Local Supply)
Block
Main PCB
#1
Main PCB
#2
Main PCB
#16
Wired Remote Controller
Slide Switch
OP7
Remote
Controller
PCB
Indoor Unit 2
Main PCB
Indoor Unit 16
Connector
RED(12V)
YL(SIGNAL)
BR(GND)
RED(12V)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
YL(SIGNAL)
BR(GND)
Connecting Cable(Local Supply)
Connector
Connector
....
....
• Be careful not to exchange the color of wires.
• The maximum length of connecting wire should be below 200m(25
) on connecting each units.
• Use a wire more than 0.5mm
2
CAUTION
–30–
E.S.P.(External Static Pressure) Setting
(1) Open the rear cover of the wired remote-controller to set the mode.
(2) Select one of three selectable modes as follows.
Without Zone System
1. Position V-H, F-H:
• This position sets the maximum E.S.P as a default set.
2. Position V-L:
• This position sets the minimum E.S.P as a default set.
With Zone System
1. Position V-H:
• Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
2. Position F-H:
• Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers.
3. Position V-L:
• Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom.
*Maximum: 18/24K-8mmAq
36K-10mmAq
Minimum: All-0mmAq
(3) Move the slide switch to set position.
(4) Close the rear cover and check if it works normally.
TH
R14H
SW TH
REMO
MAIN
2TH
OP7
R18H
R17H
OP6
LO
STAND
SW
HIGH
HI
R03S
C070
R04S
R02S
R01S
OP3
OP2
OP1
R19H
R11H
R13H
R12H
OP5R16H
OP4
R15H
CO1H
V-H
V-L
F-H
Slide switch for ceiling height
• Select the position after checking duct work and E.S.P of the unit. 
• Maunfactured in the position F-H.
CAUTION
–31–
How to Set E.S.P?
Preheat
ZONE
Operation unit
Program set
Room Temp
MED
LO
AUTO
JET
Heater
Defrost
Filter
Humidify
Out door
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
1 2 3 4
OPERATION
FAN SPEED
SUB FUNCTION
SET TEMP
HI
AUTO SWING
Time
Preheat
ZONE
Operation unit
Program set
Room Temp
MED
LO
AUTO
JET
Heater
Defrost
Filter
Humidify
Out door
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
1 2 3 4
OPERATION
FAN SPEED
SUB FUNCTION
SET TEMP
HI
AUTO SWING
Time
Time
SUB FUNCTION
SET TEMP
OPERATION
AUTO SWING
Preheat
ZONE
Operation unit
Program set
Room Temp
MED
LO
AUTO
JET
Heater
Defrost
Filter
Humidify
Out door
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
1 2 3 4
FAN SPEED
HI
Time
SUB FUNCTION
SET TEMP
OPERATION
AUTO SWING
Preheat
ZONE
Operation unit
Program set
Room Temp
MED
LO
AUTO
JET
Heater
Defrost
Filter
Humidify
Out door
Timer
On
Set no. Time
Off
01
03
05
07
09
11
13
15
17
19
21
23
1
3 4
FAN SPEED
HI
2
Timer
1
2
3
5
4
Timer
Procedure of RPM change:
Ex) External Static pressure is 6mmAq for Model Name "LB-G3680HL"
• To protect the unit, compressor is designed to be off during E.S.P. setting.
Push the "On/Off" button. 
The unit will start.
Push the "Timer" and "Wind" button simultaneously for more then 3 seconds.
Push the "Up" of "Down" button for E.S.P adjustment.
And, adjust the number which you want.(In this example, the number is "220". Refer to the table
1 on the next page.)
Shift the fan speed mode by pressing the fan speed button.
And then, Adjust numbers of next steps by repeating the stage 3.
(In this example, the numbers are "235" and "243" respectly)
Push the "Timer" and "Wind" button simultaneously for more than 3 seconds.
Then, Wind Data is memorized by the EEPROM of the main PCB.
Note: The range of selection is from 1~254. Since, the display is two Digit only.
If the range selection is above 100 then the third digit will appear in the screen as shown.
–32–
Static Pressure(mmAq)
Setting Value
0
2
4
6
8
10
Model Name Step(Hi/Med/Lo)
LB-H1860HL/CL
LB-H2460HL/CL
LB-G3680HL/CL
16.5 CMM
14.5 CMM
13 CMM
18 CMM
16.5 CMM
14 CMM
32 CMM
29 CMM
26.5 CMM
235
245
254
220
235
250
230
240
245
230
238
252
205
230
240
230
238
245
225
235
248
190
220
235
225
237
243
215
230
245
50
200
230
220
235
243
180
215
240
1
100
210
150
230
240
1
220
240
[Table. 1]
Note:  1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.