–21–
6. Defrost Control(30K/36K/42K/48K/60K)
• Defrost control is availavle 45 minutes later since heating mode operation started, and it will not prolong over
10 minutes.
• Defrost control is carried out when the outdoor pipe temp. falls below -6°C for more than 3 minutes after 45
minutes passed from starting of heating operation.
• Defrost ends after 10 minutes passed from starting of defrost operation or when the outdoor pipe temp. rises
over 12°C after 5 minutes passed from starting of defrost.
Defrost Control (New Type Defrost Control) (18K/24K)
• While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to
cooling cycle to defrost the evaporator pipe of the outdoor unit.
• Defrost control is available 45 min. later since heating mode operation started, and it will not prolong over 10 min.
• Defrost control is carried out according to the following priority order while in heating mode operation.
1st priority : Defrost control is carried out according to the indoor pipe temp 60 min. later since heating mode opera-
tion started.
2nd priority : The temp differences between the indoor pipe temp and the intake air temp 25 min. later(
T1) and 45
min. later (
T2) since heating mode operation started are measured, then defrost control is carried out
according to the dirrerence (
T=
T1-
T2)
3rd priority : Defrost control is carried out according to the temp dirrerence (E=TE1-TE2) between the indoor pipe
temperatures of 25 min later(TE1) and 45 min later (TE2) after heating mode operation started.
• When the indoor pipe temp is 41°C or above, defrost control is not carried out even if the condition is one of the
defrost conditions above.
• While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.
7. Self-diagnosis Function
• 'CHECK' will flash in the remote controller display when a problem occurs. Then please contact your dealer.
• Correct the accident point as shown in the table below before restarting operation.
• During the normal operation 'CHECK' won't be displayed in the remote controller.
Remote controller LCD
Accident Point
CH 01
Indoor room temperature thermistor error
CH 02
Indoor piping thermistor error
CH 03
Indoor main body / Remote controller unit communication error
CH 04
(Optional)
Water level float switch error
More than 45 minutes 
of heating operation
Within 
9min. 45sec.
ON
OFF
ON
ON
ON
ON
OFF
OFF
COMPRESSOR
4-WAY VALVE
INDOOR FAN
-6
°
C ON
12
°
C OFF
The outdoor
piping Temp.
ON
More than 10 min. 
running of compressor
More than 45 minutes 
of heating operation
5sec.
HOT-
START
ON
–22–
Installation of Indoor, Outdoor Unit
1. Selection of the best location
1) Indoor unit 
Select location
Install the air conditioner in the location that satis-
fies the following conditions.
• The place shall easily bear a load exceeding four
times the indoor unit’s weight.
• The place shall be able to inspect the unit as the
figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suit-
able dimension “H” is necessary to get a slope to
drain as figure.)
• The place shall easily connect with the outdoor
unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam
near the unit.
2) Outdoor unit
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, be careful that heat
radiation from the condenser is not restricted. 
• There should not be any animals or plants which
could be affected by hot air discharged. 
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
3) Piping length and the elevation
Indoor unit
Outdoor unit
B
A
More than
30cm
More than
30cm
More than
70cm
Sunr
oof
Fence or
obstacles
Top view
(unit: mm)
H
Front view
600
600
Front
Inspection hole
(600X600)
Control box
1000
• If 18K Model is installed at a distance of 15m, 
188g of refrigerant should be added (15-7.5) x 25g = 188g
• Capacity is based on standard length and maximun allowance length is on the basis of reliability.
18K BTU/h
5/8"
5/8"
5/8"
1/4"
7.5
50
5
30
25
30K BTU/h
5/8"
3/8"
7.5
50
5
30
50
42K BTU/h
3/4"
3/8"
7.5
50
5
30
50
H/P
1/4"
7.5
50
5
30
30
5/8"
3/8"
7.5
50
5
30
40
5/8"
3/8"
7.5
50
5
30
40
C/O
H/P
C/O
1/4"
7.5
50
5
30
30
30
25
48K BTU/h
3/4''
3/8"
7.5
50
5
50
3/4"
1/2"
7.5
50
5
60
60K BTU/h
24K
BTU/h
36K
BTU/h
Capacity
Gas
Liquid
Elevation B(m)
Length A(m)
* Additional
refrigerant
(g/m)
Pipe Size
(Diameter: Ø)
Standard
Standard
Max.
Max.
2. Ceiling dimension and hanging
bolt location
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
• A place where the unit will be leveled and that can
support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
–23–
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Drainage hole
M10 Nut
M10 SP. washer 
M10 washer 
X 4
X 4
(Local
supply)
X 4
M10 Nut
M10 SP. washer 
M10 washer 
X 4
X 4
(Local
supply)
X 4
A
B
C
1-3 mm
D
(G)
H
I
E
F
A
B
C
D
E
F
(G)
H
I
18K BTU/h 942 880 466
54
575
30
87
750 186
24K BTU/h 942 880 466
54
575
30
87
750 186
30K BTU/h 1242 1180 492
54
600
30
87
830 186
1072 1010 492
54
600
30
87
750 186
1242 1180 492
54
600
30
87
830 186
1242 1180 492
54
600
30
87
830 186
1292 1230 650.5 54
760
30
120 1006 294
1292 1230 570.5 54
680
30
120 1006 294
1292 1230 650.5 54
760
30
120 1006 294
1292 1230 570.5 54
680
30
120 1006 294
Dimension
Capacity
36K BTU/h
(LB-C36)
36K BTU/h
(LB-F36)
42K BTU/h
48K BTU/h
(LB-B48)
60K BTU/h
(LB-B60)
48K BTU/h
(LB-E48)
60K BTU/h
(LB-E60)
NOTE:
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
• Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
–24–
3. The Indoor Unit Installation
• Select and mark the position for fixing bolts.
• Drill the hole for set anchor on the face of ceiling.
• Insert the set anchor and washer onto the suspen-
sion bolts for locking the suspension bolts on the ceil-
ing.
• Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.
4. Remote Controller Installation
• Although the room temperature sensor is in the indoor unit, the remote controller should be installed
in such places away from direct sunlight and high humidity.
Installation of the remote controller
• Select places that are not splashed with water.
• Select control position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult
to see.(The standard height is 1.2 ~ 1.5m high)
Routing of the remote controller cord
• Keep the remote controller cord away from the refrigerant piping and the drain piping.
• To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power
cables (audio equipment, television set, etc.)
• If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water
droplets from running.
Tighten the nut and bolt to prevent unit falling.
CAUTION
1 Set anchor
Old building
New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
   bolts
• Local supply
➀ 
Set anchor
Plate washer 
- M10
Spring washer
- M10
Nut 
- W3/8 or M10
Suspension bolt
- W3/8 or M10
Page of 55