LG AS-C0764DM0 / AS-H0764DM0 / LS-C1264DM0 / LS-H0764DM0 / AS-C0964DM0 / AS-H0964DM0 / LS-C1865DM0 / LS-H0964DL0 / AS-C1264DM0 / AS-H1264DM0 / LS-C2665DM0 / LS-H1264DM0 / AS-C1865DM0 / AS-H1865DM0 / LS-C0964DA0 / LS-H1865DM0 / AS-C2465DM0 / AS-H2465DM0 / LS-C0964DM0 / LS-H2665DM0 / AS-C0764DB0 / AS-H0764GM0 / LS-C1865DB0 / LS-H2465DM0 / AS-C0964DB0 / AS-H0964GM0 / LS-C1264DA0 / LS-H0964DM0 / AS-C1264DB0 / AS-H1264GM0 / LS-C2465DB0 / AS-C1865DB0 / AS-H1865GM0 / LS-C2465GB0 / AS-C2465DB0 / AS-H2465GM0 / LS-C1865DM1 / LS-C1865GB0 / LS-C2665DM1 / AS-C0764DH0 / AS-C0964DH0 / AS-C1264DH0 / AS-C1865DH0 / AS-C2465DH0 / AS-C0964DA0 / AS-C1264DA0 / AS-C0964GA0 / AS-C1264GA0 / AS-C1865GB0 / AS-C2465GB0 / AS-H0964DA0 / AS-H1264DA0 / AS-H1865DB0 / LS-C1264DM1 / AS-H2465DB0 / LS-C1264GA0 / AS-H0964GA0 / LS-C1264GB0 / AS-H1264GA0 / LS-C0964DM1 / AS-H1865GB0 / AS-H2465GB0 / AS-H2465DM1 / LS-H0964DY0 / LS-H1264DY0 / LS-H1865DY0 / LS-H2465DY0 / LS-H0764DM1 / LS-H0964DM1 / LS-H1264DM1 / LS-H1865DM1 / LS-H2465DM1 / LS-H2665DM1 / LS-H2465GB0 / LS-H0964GB0 / LS-H1264GB0 Service Manual ▷ View online
and lift it off.
portion of the indoor unit with insulation mate-
rial and secure it with two kinds of vinyl tapes.
the drain hose appropriately.
below the indoor unit perform the following.
above the Indoor unit perform the following.
the left side.
drain water
dipped in water
leakage
leakage
50mm gap
leakage
hose
cable
from entering into electrical parts.
around pipings with a
gum type sealer.
around the pipings
with gum type sealer.
undesirable effects as indicated below.
outdoor unit must be leak tested and evacuated to remove
any noncondensables and moisture from the system.
Bubbles indicate a leak. Be sure to wipe off the soap with a
clean cloth.
at the nitrogen cylinder. When the system pressure is
reduced to normal, disconnect the hose from the cylinder.
connected and all wiring for the test run has been complet-
ed. Remove the service valve caps from both the gas and
the liquid side on the outdoor unit. Note that both the liquid
and the gas side service valves on the outdoor unit are
kept closed at this stage.
gauge reading reached 150 P.S.I.G. Next, test for leaks
with liquid soap.
available, use a stop valve for this purpose. The "Hi" knob
of the manifold valve must always be kept close.
state, the top of the cylinder must be higher than its bottom
when you pressurize the system. Usually, the cylinder is
used in a vertical standing position.
cylinder(in vertical
standing position)
gauge
indoor unit.
Confirm the "Lo" knob of the manifold valve is open. Then,
run the vacuum pump.
The operation time for evacuation varies with tubing length
and capacity of the pump. The following table shows the
time required for evacuation.
wrench. This process is very important to prevent leakage
from the system.
The air conditioner is now ready to test run.
close it.
soft brush to check for leakage of the connecting points
of the piping.
gauge
influence of wind and earthquake.
If the actual pressure are lower than shown, the system is
most likely undercharged, and charge should be added.
(beep~beep~).
refrigerant charge:
(Heating).
temperature
the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the outdoor
unit without loss in refrigerant gas.
Be sure to perform Pump Down procedure with the unit
cooling mode.
valve stem and then quickly turn off the unit. At that time,
Pump Down has been completed and all refrigerant gas
will have been collected in the outdoor unit.
Click on the first or last page to see other AS-C0764DM0 / AS-H0764DM0 / LS-C1264DM0 / LS-H0764DM0 / AS-C0964DM0 / AS-H0964DM0 / LS-C1865DM0 / LS-H0964DL0 / AS-C1264DM0 / AS-H1264DM0 / LS-C2665DM0 / LS-H1264DM0 / AS-C1865DM0 / AS-H1865DM0 / LS-C0964DA0 / LS-H1865DM0 / AS-C2465DM0 / AS-H2465DM0 / LS-C0964DM0 / LS-H2665DM0 / AS-C0764DB0 / AS-H0764GM0 / LS-C1865DB0 / LS-H2465DM0 / AS-C0964DB0 / AS-H0964GM0 / LS-C1264DA0 / LS-H0964DM0 / AS-C1264DB0 / AS-H1264GM0 / LS-C2465DB0 / AS-C1865DB0 / AS-H1865GM0 / LS-C2465GB0 / AS-C2465DB0 / AS-H2465GM0 / LS-C1865DM1 / LS-C1865GB0 / LS-C2665DM1 / AS-C0764DH0 / AS-C0964DH0 / AS-C1264DH0 / AS-C1865DH0 / AS-C2465DH0 / AS-C0964DA0 / AS-C1264DA0 / AS-C0964GA0 / AS-C1264GA0 / AS-C1865GB0 / AS-C2465GB0 / AS-H0964DA0 / AS-H1264DA0 / AS-H1865DB0 / LS-C1264DM1 / AS-H2465DB0 / LS-C1264GA0 / AS-H0964GA0 / LS-C1264GB0 / AS-H1264GA0 / LS-C0964DM1 / AS-H1865GB0 / AS-H2465GB0 / AS-H2465DM1 / LS-H0964DY0 / LS-H1264DY0 / LS-H1865DY0 / LS-H2465DY0 / LS-H0764DM1 / LS-H0964DM1 / LS-H1264DM1 / LS-H1865DM1 / LS-H2465DM1 / LS-H2665DM1 / LS-H2465GB0 / LS-H0964GB0 / LS-H1264GB0 service manuals if exist.