Harman Kardon GO AND PLAY (serv.man2) EMC - CB Certificate ▷ View online
<12007721 001>
Page 75 of 102
TRF No.: IECEN60950A
TRF originator: SGS FIMKO
Measured min. creepages
Location
inside (mm)
outside (mm)
prim-sec
triple insulated wire
used
6.1 (via bobbin,
primary winding to
secondary pin 11)
prim-core
%
%
sec-core
triple insulated wire
used
3.5 (via bobbin) + 4.5
(via tape) (core to
secondary pin 11)
prim-prim
%
%
Measured min. clearances
Location
inside (mm)
outside (mm)
prim-sec
triple insulated wire
used
6.1 (via bobbin,
primary winding to
secondary pin 11)
prim-core
%
%
sec-core
triple insulated wire
used
3.5 (via bobbin) + 4.5
(via tape) (core to
secondary pin 11)
prim-prim
%
%
Construction:
Concentric windings on PQ-2620 type bobbin, two layers insulation tape between secondary (triple insulated
wire) and primary windings (enamelled copper wire and inner copper foil). Winding ends additionally fixed with
tape, outer winding is primary. Tubing on all secondary winding exit ends are provided.
Core is considered as primary. One layer insulation tape are wrapped around the bottom core near secondary
Core is considered as primary. One layer insulation tape are wrapped around the bottom core near secondary
pin.
One layer insulation tape are wrapped around the outer copper foil which is connected to pin 1 of transformer,
One layer insulation tape are wrapped around the outer copper foil which is connected to pin 1 of transformer,
overlapping at secondary sides of at least 3.0mm
Details of triple insulated wire used, see appended table 1.5.1.
Details of triple insulated wire used, see appended table 1.5.1.
Pin numbers
Prim.
4-5-6, 1-3, outer copper foil connected pin 1
Sec.
P1-P2
Bobbin
Material
Hitachi Chemical Co., Ltd., phenolic type
CP-J-8800, flammability V-0.
Sumitomo., phenolic type PM-9820,
Sumitomo., phenolic type PM-9820,
flammability V-0.
Thickness
0.6mm min.
<12007721 001>
Page 76 of 102
TRF No.: IECEN60950A
TRF originator: SGS FIMKO
Electric strength test
With AC 3000V after humidity treatment
Result
Pass
<12007721 001>
Page 77 of 102
National Differences
Clause
Requirement
−
Test
Result – Remark
Verdict
Canadian National Differences according to CB Bulletin No. 105A, May 2003
APPENDIX Canadian National Differences according to CB Bulletin No. 105A, May 2003
(CAN/CSA C22.2 No. 60950/UL60950, Third edition)
(IEC Publication 60950:1999)
(IEC Publication 60950:1999)
P
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N=Not applicable. Placed in the column to the right.
P=Pass, F=Fail, N=Not applicable. Placed in the column to the right.
Special National Conditions
1.1.1
All equipment design and installations are
required to be in accordance with the Canadian
Electrical Code (CEC), Part 1, CAN/CSA C22.1,
and with National Electrical Code (NEC),
ANSI/NFPA 70, and, unless marked or otherwise
identified, the Standard for the Protection of
Electronic Computer/Data-Processing
Equipment, ANSI/NFPA 75.
Unit was evaluated according
to IEC 60950.
The requirements have to be
The requirements have to be
checked during national
approval.
N
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the CEN/NEC.
For lengths 3.05 m or less, external
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies which are not types specified in the
CEN/NEC are required to have special
construction features and identification markings.
No power supply cord
provided.
N
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
Single phase.
N
2.5
Where a fuse is used to provide Class 2, Limited
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
Fuse within the unit, no
operator accessible.
N
<12007721 001>
Page 78 of 102
National Differences
Clause
Requirement
−
Test
Result – Remark
Verdict
Canadian National Differences according to CB Bulletin No. 105A, May 2003
2.7.1
Suitable CEC/NEC branch circuit protection is
required for all standard supply outlets,
receptacles and medium-base or smaller
lampholders if the supply branch circuit protection
is not suitable.
Power distribution transformers distributing power
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
No standard supply outlets.
N
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the CEC/NEC.
Pluggable equipment type A.
N
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
No power supply cord
provided.
N
3.2.3
Permanent connection of equipment to the mains
supply by a power supply cord is not permitted,
expect for certain equipment, such as ATMs.
Pluggable equipment type A.
N
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
Flexible power supply cords are required to be
Flexible power supply cords are required to be
compatible with Table 11 & 12 of the CEC, and
Article 400 of the NEC.
No power supply cord
provided.
N
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
Not permanently connected
equipment.
N
3.3
Wiring terminals and associated spacings for
field wiring connections shall comply with
CAN/CSA C22.2 No. 0.
Neither wiring terminal nor
associated spacings.
N
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
No wire binding screws.
N
3.3.4
Terminals for permanent wiring, including
protective earthing terminals are required to be
suitable for Canadian/U.S. wire gauge sizes,
rated 125 percent of the equipment rating, and
specially marked when specified (1.7.7).
No terminals for permanent
wiring.
N
3.4.2
Motor control devices are required for cord-
connected equipment with a motor if the
equipment is rated more than 12 A, or if the
motor has a normal voltage rating greater than
120 V or is rated more than 1/3 hp (locked rotor
current over 43 A).
No motor control devices.
N
3.4.8
Vertically-mounted disconnect switches and
circuit breakers are required to have the ”on”
position indicated by the handle in the up
position.
No such switch.
N
Click on the first or last page to see other GO AND PLAY (serv.man2) service manuals if exist.