Control detail:
During operation ON at Heat Mode
During operation ON at Heat Mode
- Boiler signal turns ON when
a. Outdoor ambient < Outdoor Ambient Set AND
b. Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER]
b. Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER]
AND
c. Heat pump operate at room side AND
d. Connection of Boiler to Heating Select "YES" From installer menu AND
e. Buffer Tank connection select "YES" AND
f. Boiler prohibit flag = 0
d. Connection of Boiler to Heating Select "YES" From installer menu AND
e. Buffer Tank connection select "YES" AND
f. Boiler prohibit flag = 0
- Boiler signal turns OFF when
a. Outdoor ambient > Outdoor Ambient Set + [-2°C] OR
b. Buffer Tank temperature > Target Buffer Tank temperature + [STOP_TEMP] for [STOP_TIMER] OR
c. Heat pump not at room side. OR
d. Boiler prohibit flag = 1
b. Buffer Tank temperature > Target Buffer Tank temperature + [STOP_TEMP] for [STOP_TIMER] OR
c. Heat pump not at room side. OR
d. Boiler prohibit flag = 1
During operation ON at Tank Mode
- Boiler signal turns ON when
a. Outdoor ambient < Outdoor Ambient Set AND
b. Heat pump operate at tank side for continuous | DELAY_TIMER | AND
c. Connection of Boiler to DWH Tank select "YES" from installer menu. AND
d. Boiler prohibit flag = 0
b. Heat pump operate at tank side for continuous | DELAY_TIMER | AND
c. Connection of Boiler to DWH Tank select "YES" from installer menu. AND
d. Boiler prohibit flag = 0
- Boiler signal turns OFF when
a. Outdoor ambient > Outdoor Ambient Set + [2°C] OR
b. Heat pump not operates at tank side. OR
c. Boiler prohibit flag = 1
b. Heat pump not operates at tank side. OR
c. Boiler prohibit flag = 1
Boiler prohibit flag control
Purpose:
Purpose:
- For product safety. Boiler signal is OFF when water temperature is too high.
Start condition:
a. Water
outlet
≥ 85°C continues for 5 minutes.
b. Water
inlet
≥ 85°C continues for 5 minutes.
c. Zone1
water
temp
≥ 75°C continues for 5 minutes.
d. Zone2
water
temp
≥ 75°C continues for 5 minutes.
Contents:
After start condition fulfilled, set boiler prohibit flag = 1
Cancel condition:
- After 30 minutes from start condition fulfilled.
Contents:
Set boiler prohibit flag = 0
128
12.20 External Room Thermostat Control (Optional)
Purpose:
1 Better room temperature control to fulfill different temperature request by external room thermostat.
Recommended external room thermostat:
Maker Characteristic
Siemen (REV200)
Touch panel
Siemen (RAA20)
Analog
Connection of external room thermostat:
Wire Connection and thermo characteristic of Siemen REV200:
Wire Connection and thermo characteristic of Siemen REV200:
Setting
L/L1 (H)
Heat Thermo
L/L2 (C)
Cool Thermo
Set Temp < Actual Temp
Open Circuit OFF Short
Circuit ON
Set Temp > Actual Temp
Short Circuit
ON
Open Circuit
OFF
Cooling
Heating
Siemen REV200
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
heating and cooling line for heat + cool model.
Indoor Unit
9
L (label)
10
11
12
L1 (label)
L2 (label)
9 : Terminal Bord No.
Wire Connection and thermo characteristic of Siemen RAA20:
Setting
L/Y1
(H) Heat
Thermo L/Y2
(C) Cool
Thermo
Set Temp < Actual Temp
Open Circuit OFF Short
Circuit ON
Set Temp > Actual Temp
Short Circuit
ON
Open Circuit
OFF
Cooling
Heating
Siemen RAA20
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
heating and cooling line for heat + cool model.
Indoor Unit
9
L (label)
10
11
12
Y1 (label)
Y2 (label)
9 : Terminal Bord No.
Control Content:
External room thermostat control activate only when remote thermostat connection select YES by Indoor
control panel.
When indoor running heat mode, refer thermo On/Off from heating line feedback. And when indoor running
cool mode, refer thermo On/Off from cooling line feedback.
Heat pump Off immediately when receive thermo off feedback.
129
12.21 Three Ways Valve Control
Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side.
Control contents:
1 3 ways valve switch Off:
o
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2 3 ways valve switch On:
o
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3 Stop
condition:
o
During stop mode, 3 ways valve will be in switch off position.
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
M
L
N1
N2
COM
Open
Close
M
L
NC
N1
N2
M
L
NO
N1
N2
AC230V
* During pump down and force mode, fix 3 ways valve in close condition.
* Recommended Parts : SFA 21/18 (Siemens)
12.22 Two Ways Valve Control
Functionality of 2 ways valve:
Use to allow hot water to floor heating panel or block cold water to floor heating panel.
Control contents:
1 When indoor running in heat mode, OPEN the 2 ways valve.
2 When indoor running in cool mode, CLOSE the 2 ways valve.
3 Stop
2 When indoor running in cool mode, CLOSE the 2 ways valve.
3 Stop
condition:
a.
During stop mode, fix 2 ways valve in close condition.
L
N2
Indoor Unit
N1
Spring Return 2 point
SPDT 3 wire
M
L
N1
N2
COM
Open
Close
M
L
NC
N1
N2
M
L
NO
N1
N2
AC230V
* During pump down mode, fix 2 ways valve in close condition.
* During force mode, open 2 ways valve.
* During force mode, open 2 ways valve.
* Recommended Parts : SFA 21/18 (Siemens)
130
12.23 External OFF/ON Control
Communication circuit between indoor unit and external controller is as per below.
External
Controller
Controller
Panasonic
PCB
CN-THERMO
5V
12V
1
2
2
mico
Maximum length of communication cable is 50 meter.
Control
content:
External Control Switch
Control Panel OFF/ON
Control Panel Power LED
System Status
ON ON ON ON
ON OFF OFF OFF
ON OFF OFF OFF
OFF ON ON OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
Remocon Screen Display and Control Detail:
REMOTE
ON
ON
ON
ON
OFF
OFF
UNIT
OFF
OFF
OFF
ON
CONTROLLER
LED
REMOTE
CONTROLLER
SIGNA
LED
REMOTE
CONTROLLER
SIGNA
L
EXTERNA
L
CONTROLLER
SWITCH
SWITCH
23
1
44
40
10:34am , Mon
18
˚
c
˚
c
˚
c
˚
c
2
Turned off by external switch.
CANCEL
When External SW connection select "YES" from remocon installer menu:
- Heating or Cooling system will operate normally if the External Switch signal is ON.
- Once the External Switch turn OFF, System Turn OFF ( Heat pump, water pump, heater etc…)
- Remocon LED remain ON or OFF according to the current operation request.
- Pop up menu at remocon main screen as above screen to inform customer system stop by External Switch.
- It is possible to press cancel and return to main screen to do change of operation setting while waiting the
- Once the External Switch turn OFF, System Turn OFF ( Heat pump, water pump, heater etc…)
- Remocon LED remain ON or OFF according to the current operation request.
- Pop up menu at remocon main screen as above screen to inform customer system stop by External Switch.
- It is possible to press cancel and return to main screen to do change of operation setting while waiting the
External Switch turn ON back.
- Remocon LED will always follow the latest changes from remocon.
- If no action on remocon for continuous 5 minutes, the pop up screen will show again on the screen.
- But once the External Switch Turn ON back, pop up screen will dsappear and system can operate normally
- If no action on remocon for continuous 5 minutes, the pop up screen will show again on the screen.
- But once the External Switch Turn ON back, pop up screen will dsappear and system can operate normally
according to the latest operation setting and request.