Panasonic WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 Service Manual ▷ View online
121
12.14 Outdoor Ambient Thermo OFF Control
Purpose
- Stop provides heating to room side during high outdoor ambient condition.
ON
OFF
Outdoor thermo off
set temperature +3°C
set temperature +3°C
Outdoor thermo off
set temperature +1°C
set temperature +1°C
Control content
- Heating outdoor ambient thermos OFF control only applicable when heat pump operate in heat mode. (This
control will not activate when running in tank side)
- Heat pump and water pump will turn OFF when outdoor ambient is higher than outdoor thermo OFF set
temperature.
- Heat pump thermos ON when outdoor ambient < outdoor thermos OFF set temperature + 1°C.
122
12.15 Alternative Outdoor Ambient Sensor Control
Purpose of the Alternative Outdoor Ambient Sensor:
- It is some possibility that the air to water heat pump unit will install at a location where the original ambient
sensor is expose to direct sunlight. Therefore, another optional ambient sensor can be connect to indoor
PCB and locate at new and better reading location to improve the heat pump performance.
PCB and locate at new and better reading location to improve the heat pump performance.
Control Detail:
- Remocon can select either the extra outdoor ambient sensor is connected or not. (YES/NO)
- The alternative outdoor ambient sensor will connect to indoor unit main PCB terminal.
- The alternative outdoor ambient sensor will connect to indoor unit main PCB terminal.
a) when alternative sensor select NO
- Original Outdoor temperature sensor will use for Indoor & Outdoor heat pump operation reference sensor.
- Data communication direction : OUTDOOR send outdoor temperature reading to INDOOR.
- Error judge : OUTDOOR will judge the original outdoor sensor error (F36 display if error detect). No
- Data communication direction : OUTDOOR send outdoor temperature reading to INDOOR.
- Error judge : OUTDOOR will judge the original outdoor sensor error (F36 display if error detect). No
judge error on alternative outdoor sensor
b) when alternative sensor select YES
- Alternative Outdoor temperature sensor will use for Indoor & Outdoor heat pump operation reference
sensor.
- Data communication direction : INDOOR send outdoor temperature reading to OUTDOOR.
- Error judge : INDOOR will judge the Extra outdoor sensor error only after operation ON request received
- Error judge : INDOOR will judge the Extra outdoor sensor error only after operation ON request received
from remocon.
(F36 display if error detect). No judge error on original outdoor sensor.
(F36 display if error detect). No judge error on original outdoor sensor.
12.16 Force DHW mode
Purpose:
When user want to use hot water now, user can press this force DWH mode under the quick menu to operate tank
only mode to boil up the tank temperature.
Remocon setting:
Force DHW function can be activate under quick menu.
Control Content:
When user want to use hot water now, user can press this force DWH mode under the quick menu to operate tank
only mode to boil up the tank temperature.
Remocon setting:
Force DHW function can be activate under quick menu.
Control Content:
a) when press the Force DHW function during operation OFF condition:
- When receive this Force DHW bit from remocon, indoor will run tank only mode regardless of the mode
- When receive this Force DHW bit from remocon, indoor will run tank only mode regardless of the mode
selection.
- After tank temperature achieve tank thermo off temperature, turn OFF force DHW bit and return to operation
OFF with previous mode selection.
b) When press the Force DHW function during operation ON condition:
- When receive this Force DHW bit from remocon, indoor will memories the running mode and run tank only
- When receive this Force DHW bit from remocon, indoor will memories the running mode and run tank only
mode regardless of the mode selection.
- After tank temperature achieve tank thermo off temperature, turn OFF force DHW bit and return to previous
memories running mode.
* when operation OFF or mode change request from remocon during force DHW mode operation, End force
DHW mode and follow the new request operation.
* Once receive force DHW mode from remocon, indoor direct start tank mode and consider tank thermo ON.
Thermo OFF only when achieve tank thermo OFF depend on the Tank System Setting.
DHW mode and follow the new request operation.
* Once receive force DHW mode from remocon, indoor direct start tank mode and consider tank thermo ON.
Thermo OFF only when achieve tank thermo OFF depend on the Tank System Setting.
123
12.17 Anti Freeze Control
Anti freeze protection control menu can be set YES or NO by control panel.
In heatpump system, there are 3 types of anti freeze control:
1. Expansion tank anti-freeze control
Expansion tank anti freeze heater ON condition:
o Outdoor ambient temp. < 3°C
Expansion tank anti freeze heater OFF condition:
o Outdoor ambient temp. > 4°C
2. Water pump circulation anti freeze control
Water pump turns ON when ALL below conditions are fulfilled:
o Heatpump OFF (stand by) OR error occurs.
o Water flowing flag is ON.
o Water flow switch is not abnormal.
o Outdoor ambient temp. < 3°C OR outdoor ambient temp. sensor is abnormal.
o Water inlet/outlet temp. < 6°C.
o After 5 minutes from previous water pump OFF.
o Water flowing flag is ON.
o Water flow switch is not abnormal.
o Outdoor ambient temp. < 3°C OR outdoor ambient temp. sensor is abnormal.
o Water inlet/outlet temp. < 6°C.
o After 5 minutes from previous water pump OFF.
Water pump turn OFF when ANY of below conditions is fulfilled:
o Outdoor ambient temperature ≥ 4°C.
o During -5°C < outdoor ambient temp. < 4°C
o During -5°C < outdoor ambient temp. < 4°C
After water pump ON for 4 minutes, and water inlet temp. ≥ 8°C.
Else, shift to back up heater anti freeze control.
o During outdoor ambient temp. < -5°C
After water pump ON for 4 minutes, and water inlet/outlet ≥ 20°C.
Else, shift to back up heater anti freeze control.
However, if flow switch is abnormal (H62), then water pump circulation anti freeze control will not activate.
3. Back up heater anti freeze control:
Back up heater turn ON when ALL below conditions is fulfilled:
o Water inlet/outlet temp. < 6°C.
o Water pump circulation anti freeze control activated and water pump ON for 4 minutes.
o Water pump circulation anti freeze control activated and water pump ON for 4 minutes.
Back up heater turns OFF when ANY of below conditions is fulfilled:
o Water inlet/outlet temp. > 28°C.
o Water pump circulation anti freeze control deactivated/water pump OFF.
o Water pump circulation anti freeze control deactivated/water pump OFF.
However, if back up heater is abnormal (H70) then back up heater anti freeze control will not activate.
12.17.1 Zone Anti-Freeze Control
If buffer tank selection is “NO” and Anti- Freeze function select “NO” from remote control, this control cannot
activate.
Start condition:
a) After [5] min from previous Zone pump off. AND
b) Outdoor air temp < [3] °C OR Outdoor sensor is abnormal. AND
c) Zone water temperature < [6]°C OR Zone Sensor Short or Open
b) Outdoor air temp < [3] °C OR Outdoor sensor is abnormal. AND
c) Zone water temperature < [6]°C OR Zone Sensor Short or Open
Cancel condition:
a) After water Zone pump ON [4] min AND
b) Outdoor air temp ≥ [4]°C OR
c) During -5 °C ≤ Outdoor air temp < [4] °C OR
b) Outdoor air temp ≥ [4]°C OR
c) During -5 °C ≤ Outdoor air temp < [4] °C OR
Zone water temperature sensor > [8] °C
d) During Outdoor air temp < [-5] °C
Zone water temperature sensor > [20] °C
*However, Zone water temperature sensor is Open or Short, Condition C and D is ignored.
*However, Zone water temperature sensor is Open or Short, Condition C and D is ignored.
124
12.18 Solar Operation (Optional)
12.18.1 Solar Operation:
Solar function:
- This function allow user to control the solar pump to operate depend on the solar sensor reading compare to
the tank installed. Solar pump will circulate the hot water energy store at solar panel to heat up the DHW
Tank or Buffer Tank.
Tank or Buffer Tank.
Solar Connection Diagram:
a) Solar function can only enable when the Optional PCB is connected.
b) Few part as below need to install to control the solar operation:
- Solar
b) Few part as below need to install to control the solar operation:
- Solar
Panel
- Solar
Pump
- Solar Panel Sensor
- Tank Sensor (Buffer tank sensor OR DHW Tank sensor depend on the connection direction)
- Tank Sensor (Buffer tank sensor OR DHW Tank sensor depend on the connection direction)
* During Solar Connection to the system, installer need to alert on the high water temperature may flow to the
zone circuit or DHW piping circuit. Therefore pipe which withstand higher water temperature need to be
installed.
zone circuit or DHW piping circuit. Therefore pipe which withstand higher water temperature need to be
installed.
Click on the first or last page to see other WH-SXC09H3E5 / WH-SXC12H6E5 / WH-UX09HE5 / WH-UX12HE5 service manuals if exist.