DOWNLOAD Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ↓ Size: 7.25 MB | Pages: 127 in PDF or view online for FREE

Model
U-4LE1E5 U-4LE1E8 U-5LE1E5 U-5LE1E8 U-6LE1E5 U-6LE1E8
Pages
127
Size
7.25 MB
Type
PDF
Document
Service Manual
Brand
Device
Air Conditioner / MINI VRF SYSTEM
File
u-4le1e5-u-4le1e8-u-5le1e5-u-5le1e8-u-6le1e5-u-6le.pdf
Date

Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online

Mini VRF SYSTEM
Service Checker
6
Contents
6-1
6. Service Checker
1.  Outdoor Unit Maintenance Remote Controller ................................................................. 6-2
1-1. Overview ........................................................................................................................ 6-2
1-2. Functions ........................................................................................................................ 6-3
1-3. Ordinary Display Controls and Functions ....................................................................... 6-4
1-4. Monitoring Operations .................................................................................................... 6-9
1-5. Outdoor Unit Alarm History Monitor ............................................................................. 6-11
1-6. Setting the outdoor unit EEPROM data ........................................................................ 6-12
SM830196-03_Mini_VRF SYS.indb   1
SM830196-03_Mini_VRF SYS.indb   1
2014/09/09   14:59:24
2014/09/09   14:59:24
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-2
1-1. Overview
 
  About the outdoor unit maintenance remote 
controller
The outdoor unit utilizes nonvolatile memory (EEP-
ROM) on its PCB. This allows EEPROM data to 
replace the setting switches that were present on pre-
vious PCBs. The outdoor unit maintenance remote 
controller is used to set and change these EEPROM 
data.
In addition to setting and checking the outdoor unit 
EEPROM data, this remote controller can also be 
used to monitor the outdoor unit alarm history, monitor 
the various indoor and outdoor temperatures, and 
check the indoor unit connection status (number of 
units, operating mode, etc.).
System Diagram
•  
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller 
to the outdoor unit PCB.
•  
Ordinary remote controllers or other controllers are still required for the indoor units, even when the outdoor unit 
maintenance remote controller is connected.
[Service Checker Section]
Outdoor unit maintenance
remote controller
Special service checker wiring
(Servicing No. CV6231785082)
Remote controller Ass'y
* Operation manual included in package.
Outdoor unit
control PCB
Indoor unit
Indoor unit
Remote 
controller
Remote 
controller
Inter-unit control wiring
SM830196-03_Mini_VRF SYS.indb   2
SM830196-03_Mini_VRF SYS.indb   2
2014/09/09   14:59:37
2014/09/09   14:59:37
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-3
1-2. Functions
 
 Functions on the ordinary display
(1) Press the buttons to execute the following functions.
•  All indoor units stop/start
• Cooling/heating change
•  All indoor units test run
(2) Display: The following displays are possible.
• Alarm display
•  No. of indoor/outdoor units
•  Unit Nos. of connected indoor/outdoor units
•  Operating status of indoor/outdoor units (Blinks when alarm occurs.)
•  Indoor thermostat ON
•  Display of individual outdoor unit alarms
•  Total operating time of outdoor unit compressors
•  Oil level of the outdoor unit oil sensor
•  Total outdoor unit power ON time
•  Outdoor unit microcomputer version, other information
 
 Temperature monitor
Displays the temperature from each indoor/outdoor sensor.
 
 Outdoor unit alarm history monitor
Displays the outdoor unit alarm history.
 
 Settings the outdoor unit EEPROM data
Settings mode 1 and settings mode 2 can be used to make outdoor unit EEPROM data settings.
SM830196-03_Mini_VRF SYS.indb   3
SM830196-03_Mini_VRF SYS.indb   3
2014/09/09   14:59:37
2014/09/09   14:59:37
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-4
1-3. Ordinary Display Controls and Functions
 
 Functions on the ordinary display
Connect the special service checker wiring to the outdoor unit PCB.
The connection diagram is shown below.
•  If the communications line in the inter-unit control wiring is connected, it can be left as-is.
•  In the case of an independent outdoor unit (1 maintenance remote controller connected to 1 outdoor unit, 
automatic address setting for indoor units not completed), both setting mode 1 and setting mode 2 can be used 
for outdoor unit EEPROM data settings.
•  The overall system status for that refrigerant system is displayed.
Special service checker wiring
PCB connector (3P, blue)
RC (3P, blue)
Outdoor unit PCB
Relay connector (2P, white)
Remote controller Assy