Panasonic U-4LE1E5 / U-4LE1E8 / U-5LE1E5 / U-5LE1E8 / U-6LE1E5 / U-6LE1E8 Service Manual ▷ View online
Mini VRF SYSTEM
Service Checker
6
Contents
6-1
6. Service Checker
1. Outdoor Unit Maintenance Remote Controller ................................................................. 6-2
1-1. Overview ........................................................................................................................ 6-2
1-2. Functions ........................................................................................................................ 6-3
1-3. Ordinary Display Controls and Functions ....................................................................... 6-4
1-4. Monitoring Operations .................................................................................................... 6-9
1-5. Outdoor Unit Alarm History Monitor ............................................................................. 6-11
1-6. Setting the outdoor unit EEPROM data ........................................................................ 6-12
SM830196-03_Mini_VRF SYS.indb 1
SM830196-03_Mini_VRF SYS.indb 1
2014/09/09 14:59:24
2014/09/09 14:59:24
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-2
1-1. Overview
About the outdoor unit maintenance remote
controller
The outdoor unit utilizes nonvolatile memory (EEP-
ROM) on its PCB. This allows EEPROM data to
replace the setting switches that were present on pre-
vious PCBs. The outdoor unit maintenance remote
controller is used to set and change these EEPROM
data.
In addition to setting and checking the outdoor unit
EEPROM data, this remote controller can also be
used to monitor the outdoor unit alarm history, monitor
the various indoor and outdoor temperatures, and
check the indoor unit connection status (number of
units, operating mode, etc.).
ROM) on its PCB. This allows EEPROM data to
replace the setting switches that were present on pre-
vious PCBs. The outdoor unit maintenance remote
controller is used to set and change these EEPROM
data.
In addition to setting and checking the outdoor unit
EEPROM data, this remote controller can also be
used to monitor the outdoor unit alarm history, monitor
the various indoor and outdoor temperatures, and
check the indoor unit connection status (number of
units, operating mode, etc.).
System Diagram
•
The special service checker wiring is required in order to connect the outdoor unit maintenance remote controller
to the outdoor unit PCB.
to the outdoor unit PCB.
•
Ordinary remote controllers or other controllers are still required for the indoor units, even when the outdoor unit
maintenance remote controller is connected.
maintenance remote controller is connected.
[Service Checker Section]
Outdoor unit maintenance
remote controller
Special service checker wiring
(Servicing No. CV6231785082)
(Servicing No. CV6231785082)
Remote controller Ass'y
* Operation manual included in package.
Outdoor unit
control PCB
control PCB
Indoor unit
Indoor unit
Remote
controller
controller
Remote
controller
controller
Inter-unit control wiring
SM830196-03_Mini_VRF SYS.indb 2
SM830196-03_Mini_VRF SYS.indb 2
2014/09/09 14:59:37
2014/09/09 14:59:37
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-3
1-2. Functions
Functions on the ordinary display
(1) Press the buttons to execute the following functions.
• All indoor units stop/start
• Cooling/heating change
• All indoor units test run
(2) Display: The following displays are possible.
• Alarm display
• No. of indoor/outdoor units
• Unit Nos. of connected indoor/outdoor units
• Operating status of indoor/outdoor units (Blinks when alarm occurs.)
• Indoor thermostat ON
• Display of individual outdoor unit alarms
• Total operating time of outdoor unit compressors
• Oil level of the outdoor unit oil sensor
• Total outdoor unit power ON time
• Outdoor unit microcomputer version, other information
Temperature monitor
Displays the temperature from each indoor/outdoor sensor.
Outdoor unit alarm history monitor
Displays the outdoor unit alarm history.
Settings the outdoor unit EEPROM data
Settings mode 1 and settings mode 2 can be used to make outdoor unit EEPROM data settings.
SM830196-03_Mini_VRF SYS.indb 3
SM830196-03_Mini_VRF SYS.indb 3
2014/09/09 14:59:37
2014/09/09 14:59:37
Mini VRF SYSTEM
Service Checker
6
1. Outdoor Unit Maintenance Remote Controller
6-4
1-3. Ordinary Display Controls and Functions
Functions on the ordinary display
Connect the special service checker wiring to the outdoor unit PCB.
The connection diagram is shown below.
The connection diagram is shown below.
• If the communications line in the inter-unit control wiring is connected, it can be left as-is.
• In the case of an independent outdoor unit (1 maintenance remote controller connected to 1 outdoor unit,
automatic address setting for indoor units not completed), both setting mode 1 and setting mode 2 can be used
for outdoor unit EEPROM data settings.
for outdoor unit EEPROM data settings.
• The overall system status for that refrigerant system is displayed.
Special service checker wiring
PCB connector (3P, blue)
RC (3P, blue)
Outdoor unit PCB
Relay connector (2P, white)
Remote controller Assy